6.6.1 TANK CONFIG submenu
Enter specific data for the measuring point using the submenu TANK CONFIG.
Zero point
Scraper
Tank depth:
Set the tank depth for each sensor position. To obtain the correct display of the sludge level, it is
important to enter the exact tank depth. The reference point is the water surface.
Setting range: 0 ... 100m
Zero adjust:
Enter the position of the sensor below the water surface using this function (normal OFFSET of sensor
position below water surface: +0.2m).
Setting range: –100 ... + 100m
Dwell time:
This function is required when several sensors operate from one transmitter. When the information
from one sensor is more important than from one of the others, the system can be set so that it spends
more time at this measuring position. A typical setting is 10. With this setting, the system makes 10
updates for this basin before moving on to the next measuring point. If the dwell time is set to 0, the
system ignores this measuring point.
One update (measuring cycle) lasts 2 seconds. For systems with only one sensor, any positive value
can be set here.
Setting range: 0 ... 100 updates
Min. range:
Enter the minimum depth below the water level at which you expect to find a separation zone. The MIN
HEIGHT must be at least 20cm below the set zero value.
Setting range: –100 ... + 100m
Max. range:
Enters the maximum design tank depth. The default Max. range is a "Tank depth + 20cm".
Setting range: 0 ... 100m
Operation:
Move through the submenu by pressing the '
→
→
→
→
‘ key, select numeric values by pressing the '
↑↑↑↑
‘ / '
↓↓↓↓
‘ keys
(see Chap. 6.1 "Key assignment"). Confirm and return to the main menu by pressing the ‘E’ key.
Max
. height
Bas
in depth
Min.
height