6.6 Measuring point information
The following information on the measuring point can be retrieved:
Display messages for
diagnosis
The level indicator enables the smallest and largest measured values for pressure and
temperature to be called up. The value is not lost on switching off the device.
Communication level
The matrix line "VA Communication" can only be called up and calibrated with the
Commuwin II operating program or the Universal HART Communicator DXR 275
handheld.
Matrix field
Display or entry
Measured values
V0H0
Main measured value: level, volume or weight
V2H6
Sensor temperature (units in V7H9 selectable)
V7H0
Output current in mA
V7H8
Sensor pressure (units in V0H9 selectable)
Sensor data
V0H1
Lower range-value, (pressure for level "empty")
V0H2
Upper range-value, (pressure for level "full")
V2H5
Overload counter pressure (0…255)
V3H1
Lower range-value for level, volume or weight ("empty")
V3H2
Upper range-value for level, volume or weight ("full")
V7H4
Low Sensor Trim (units in V0H9 selectable)
V7H5
High Sensor Trim (unit in V0H9 selectable)
V7H6
Lower range-limit of sensor (units in V0H9 selectable)
V7H7
Upper range-limit of sensor (units in V0H9 selectable)
Measuring point information
V2H2
Device and software number
Error response
V2H0
Actual diagnostic code
V2H1
Last diagnostic code
VAH0
Measuring point tag
The measuring point can be identified with a max. of 8 (ASCII) characters
VAH1
User text
VAH2 – VAH8
Information about the device
Matrix field
Display
V2H3
Peak hold P Min (Maximum pointer for minimum pressure)
V2H4
Peak hold P Max (Maximum pointer for maximum pressure)
V2H7
Peak hold T Min (Maximum pointer for minimum temperature)
V2H8
Peak hold T Max (Maximum pointer for maximum temperature)
V2H5
Overload counter pressure (0…255)
V2H6
Current sensor temperature (units in V7H9 selectable)