Screw together up to the
retaining ring . . .

. . .continue screwing on the housing
together with the retaining ring

Set screw,

(for mounting loosen halfways)

Tab on

retaining ring

Retaining ring is positioned in the lower
groove of the housing by screwing the
housing together with the sensor

Set screw

KA00640P/00/a2/13.11

Assembly diaphragm seal on Cerabar S PMP71

Hauser

Both O-rings must be installed at the sensor head.
Insert the included retaining ring must at the sensor head.
After assembly, it will limit the rotation of the housing.
Position housing on sensor head and screw on up to the edge of the
retaining ring (approximately 5 turns), refer to illustration below.
Position retaining ring towards set screw (see center line).
Continue rotating the housing together with the retaining ring
such that the tab slips into the guide groove in the housing, then
screw housing onto sensor head until stop.
If assembled correctly, the housing can be rotated back for over a full
turn (380°) to a noticeable stop.
Install electronics module
Unplug and remove shorting plug from sensor plug and plug sensor
cable into electronics.
If applicable, plug display module to electronics.
Screw lid on electronic compartment.

Install instrument at desired location, connect wires

Adjust housing to the desired position

Important: the set screw must be tightened securely after
positioning of the housing in order to provide an optimum
potential equalization between the process tank and the
ground potential of the housing.
This also has a positive effect on the EMC characteristics of
the electronics.

After the complete assembly the instrument is operational.

After switching on the instrument, code 7864 (general reset) must
be entered in the operation menu --> operation --> in the field
“reset”. The electronics then reads the specific sensor data from the
sensor electronics.
The instrument must then be calibrated to the process measuring
range according to the manual.

1.
2.

3.

4.
4a.

5.
6.

Startup

Setup / calibration

Assembly of sensor assembly and aluminum housing T14

2

Guide

9 turns total

Groove in housing

Guide

Bottom view of housing

enclosed
retaining ring

O-rings
45.69 x 2.62
EPDM

Set screw

Remove
shorting plug

Assembling the retaining ring

4

6

3

1

2

5

4a

Sensor

Содержание Cerabar S PMP71

Страница 1: ...tronik Modul ausschrauben und das Elektronik Modul aus dem Geh use ziehen Steckverbindung Die Feststellschraube etwa 1 2 Umdrehungen l sen Das leere Geh use linksdrehend vom Sensor abschrauben 9 Umdre...

Страница 2: ...e positionieren siehe Mittellinie Geh use weiterdrehen sodass die Lasche in die F hrung am Geh use eintaucht dann das Geh use bis zum Anschlag auf das Sensoroberteil schrauben Nach sachgem em Zusammen...

Страница 3: ...die Elektronik anstecken Deckel aufschrauben Ger t an der Messstelle einbauen Verkabelung anschlie en Geh use in die gew nschte Position ausrichten Wichtig Nach dem Ausrichten ist ein festes Anziehen...

Страница 4: ...KA00640P 00 a2 13 11 Druckmittleranbau am Cerabar S PMP71 Endress Hauser 4...

Страница 5: ...be filled after the welding After the filling of the diaphragm seal the instrument may indicate at the zero point no more than 10 of the maximum cell range The internal pressure of the diaphragm seal...

Страница 6: ...onics module Unplug and remove shorting plug from sensor plug and plug sensor cable into electronics If applicable plug display module to electronics Screw lid on electronic compartment Install instru...

Страница 7: ...nect wires Adjust housing to the desired position Important the set screw must be tightened securely after positioning of the housing in order to provide an optimum potential qualization between the p...

Страница 8: ...KA00640P 00 a2 13 11 Assembly diaphragm seal on Cerabar S PMP71 Endress Hauser 4...

Отзывы: