BA00413P/00/EN/03.14
71270370

Valid for software version:
02.10.54

Operating Instructions – Description of Device Functions

Cerabar S PMP71 with MID Part Certificate

Process pressure measurement

Содержание Cerabar S PMP7

Страница 1: ...BA00413P 00 EN 03 14 71270370 Valid for software version 02 10 54 Operating Instructions Description of Device Functions Cerabar S PMP71 with MID Part Certificate Process pressure measurement...

Страница 2: ...Cerabar S 4 to 20mA HART 2 Endress Hauser A0023555 TAG No XXX000 Ser No X000X000000 Order code 00X00 XXXX0XX0XXX www endress com deviceviewer Endress Hauser Operations App Serial number...

Страница 3: ...meter names index 4 2 Finding parameter description using ID numbers 5 3 Graphic representation of function groups 7 4 Pressure measurement 8 4 1 Calibration with reference pressure 8 4 2 Calibration...

Страница 4: ...e link takes you to the parameter in question In the operating program additional parameters and to an extent other parameters are displayed These parameters are not shown in Section 2 You can find th...

Страница 5: ...IME 12 16 250 SENSOR SER No 28 254 OUTPUT CURRENT 20 264 SOFTWARE VERSION 25 266 HARDWARE REV 25 270 SIM CURRENT 33 271 HART MESSAGE 24 272 ADDITIONAL INFO 25 301 PRESSURE Pressure measuring mode 30 3...

Страница 6: ...R PRESSURE Pressure measuring mode 30 591 MINIMUM SPAN 28 595 SELECT ALARMTYPE 34 597 ALT CURR OUTPUT 21 600 SELECT ALARMTYPE 34 603 RESET ALL ALARMS 34 679 MEASURED VALUE Pressure 29 688 MAIN DATA FO...

Страница 7: ...TUP pressure 11 OPERATING MENU 555 SETTINGS 557 POSITION ADJUSTMENT 12 BASIC SETUP pressure 14 EXTENDED SETUP pressure 17 SAFETY CONFIRM See 1 DISPLAY 558 18 OUTPUT 559 20 TRANSMITTER INFO 560 HART DA...

Страница 8: ...djustment if necessary See Page 12 Table 5 POSITION ADJUSTMENT P01 MIDxxxxx 05 xx xx xx 004 Fig 1 Calibration with reference pressure 1 See Table Step 5 2 See Table Step 6 2 If necessary select the Pr...

Страница 9: ...Table 12 PROCESS VALUES Note You can also perform calibration without reference pressure by means of the QUICK SETUP menu See Page 11 ff Table 2 QUICK SETUP menu You can also specify a customer speci...

Страница 10: ...the first row of the table Some parameters are only displayed if other parameters are appropriately configured Parameter names are written in upper case in the text In the Parameter name column the un...

Страница 11: ...quisite Digital communication Options Pressure Factory setting Pressure POS INPUT VALUE 563 Entry Position adjustment the pressure difference between zero set point and the measured pressure need not...

Страница 12: ...nge in the pressure Input range 0 0 to 999 0 s Factory setting 2 0 s or as per order specifications Table 2 GROUP SELECTION QUICK SETUP Pressure Parameter name Description 1 1 LANGUAGE BASIC SETUP DIS...

Страница 13: ...y which the MEASURED VALUE was corrected The following applies CALIB OFFSET MEASURED VALUEold POS INPUT VALUE here CALIB OFFSET 0 5 mbar 0 0075 psi 2 0 mbar 0 03 psi 1 5 mbar 0 0225 psi The current va...

Страница 14: ...RV SET URV 1 Display via on site display only 2 Display via digital communication Level not for PMP71 with MID provided Table 4 GROUP SELECTION OPERATING MENU SETTINGS BASIC SETUP Pressure Parameter n...

Страница 15: ...n limited to five For example if crates m2 is specified as the customer specific unit crate m2 is displayed In FieldCare all eight characters are displayed In the HART handheld terminal the customer s...

Страница 16: ...present at device The pressure for the upper current value 20 mA is present at device With the Confirm option you assign the upper current value to the pressure value present Onsite display the press...

Страница 17: ...display only Parameters marked with an asterisk are not always displayed The display depends on the settings of other parameters see the following Table Level not for PMP71 with MID provided Table 5 G...

Страница 18: ...r name Description MENU DESCRIPTOR 419 Options Specify contents for the main line of the onsite display in the measuring mode See also Operating Instructions BA00412P Section Onsite display Options Ma...

Страница 19: ...ions Deutsch English Fran ais Italiano Espa ol Nederlands Chinese CHS Japanese JPN Factory setting English DISPLAY CONTRAST 339 Entry Adjust contrast of onsite display You specify the contrast of the...

Страница 20: ...ng mode only ALT CURR OUTPUT TOTALIZER SETUP OUTPUT CURRENT CURR CHARACT OUTPUT FAIL MODE SET MAX ALARM LANGUAGE OUTPUT SETTINGS POSITION ADJUSTMENT OPERATING MENU GROUP SELECTION Measured value 1 Dis...

Страница 21: ...UTPUT FAIL MODE 388 Entry Select the current value in the event of an alarm In the event of an alarm the current assumes the current value specified with this parameter Options Max alarm 110 can be se...

Страница 22: ...m alarm current See also OUTPUT FAIL MODE Input range 21 23 mA Factory setting 22 mA SET MIN CURRENT 343 Entry Enter lower current limit Some switching units do not accept current values lower than 4...

Страница 23: ...AG NUMBER PROC CONN TYPE MAT PROC CONN MAT PROC CONN PRESS SENS LOLIM PRESS SENS HILIM MINIMUM SPAN HART DATA BUS ADRESS TRANSMITTER INFO TRANSMITTER DATA DEVICE SERIAL No PROCESS CONNECTION Pmax PROC...

Страница 24: ..._ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ or as per order specifications HART DATE 481 Entry Enter the date of the last configuration change Factory setting DD MM YY date of final test PRIMARY VALUE IS Display...

Страница 25: ...ng _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ or as per order specifications ADDITIONAL INFO 272 Entry Enter the tag description max 16 alphanumeric characters Factory setting _ _...

Страница 26: ...ter name Description Pmax PROC CONN 570 Entry For entering and displaying the maximum permitted pressure of the process connection Factory setting as per nameplate data see also Operating Instructions...

Страница 27: ...requisite Digital communication THREAD PROCESS For selecting and displaying the process connection thread Prerequisite Digital communication MOUNTING THREAD For selecting and displaying the ways of se...

Страница 28: ...isplay Displays the smallest possible span SENSOR MEAS TYPE 581 Display Displays the sensor type Cerabar S with absolute pressure sensor Absolute MAT MEMBRANE 365 Display Displays the material of the...

Страница 29: ...JUSTMENT OPERATING MENU GROUP SELECTION Measured value 1 Display via on site display only 2 Display via digital communication Level not for PMP71 with MID provided Table 12 GROUP SELECTION OPERATING M...

Страница 30: ...PRESSURE diagram SENSOR PRESSURE 584 Display Displays the measured pressure before sensor trim position adjustment and damping See also PRESSURE diagram SENSOR TEMP 367 Display Displays the temperatu...

Страница 31: ...ON MODE MESSAGES RESET ALL ALARMS SELECT ALARMTYPE ALARM DELAY ALARM DISPL TIME ALARM STATUS LAST DIAG CODE ACK ALARM MODE ACK ALARM Pmin ALARM WINDOW Pmax ALARM WINDOW Tmin ALARM WINDOW Tmax ALARM WI...

Страница 32: ...tions Select download function from HistoROM to device The option selected has no effect on an upload from the device to the HistoROM Prerequisite A HistoROM M DAT is attached to the electronic insert...

Страница 33: ...ation value See also SIMULATION MODE Prerequisite SIMULATION MODE Current value Factory setting Current current value SIM ERROR NO 476 Entry Enter message number See also SIMULATION MODE See also thes...

Страница 34: ...essages of the LAST DIAG CODE parameter Options Abort Confirm Factory setting Abort ERROR No Entry For Error type messages you can decide whether the device should behave as in the event of an alarm A...

Страница 35: ...ESS SENS LOLIM Pmax ALARM WINDOW 333 Entry Customer specific process monitoring enter upper pressure limit You can use the SELECT ALARMTYPE parameter to enter how the device responds if the operating...

Страница 36: ...via the SIMULATION MODE parameter 3 Enter 4 mA for the SIM CURRENT parameter 4 Select the SYSTEM 2 group Menu path GROUP SELECTION OPERATING MENU SERVICE 5 Enter the current value measured with the sw...

Страница 37: ...rence between 4 mA and the value entered for the CURR TRIM 4mA parameter Factory setting 0 OFFSET 20mA TRIM 044 Display Displays the difference between 20 mA and the value entered for the CURR TRIM 20...

Страница 38: ...are generated For the error messages see Page 45 Section 6 1 1 Onsite display error messages For support and further information please contact Endress Hauser Service Code Error type NA 64 Message de...

Страница 39: ...ective Replace main electronics 10 131 A131 Alarm B B Checksum error in EEPROM min max segment Main electronics defective Replace main electronics 9 132 A132 Alarm B B Checksum error in totalizer EEPR...

Страница 40: ...P Section Copying configuration data 703 A703 Alarm B B Measurement error Fault in the main electronics Briefly disconnect device from the power supply 22 Main electronics defective Replace main elect...

Страница 41: ...r than the upper nominal temperature of the sensor See also these Operating Instructions parameter description for Tmax SENSOR Reduce process temperature ambient temperature 32 Unsuitable download car...

Страница 42: ...s are greater than specifications in the technical data See Technical Information TI00383P Block off electromagnetic effects or eliminate source of disturbance 28 Pressure is outside permitted range C...

Страница 43: ...tronics Briefly disconnect device from the power supply 23 Main electronics defective Replace main electronics 741 A741 Alarm B B TANK HEIGHT out of edit limits LEVEL MIN or LEVEL MAX has been changed...

Страница 44: ...bance 26 Overpressure or low pressure present Reduce or increase pressure 747 A747 Alarm B B Sensor software not compatible to electronics Sensor does not suit the device electronic sensor nameplate R...

Страница 45: ...Warning column See also these Operating Instructions parameter description for SELECT ALARMTYPE Bar graph onsite display The bar graph adopts the value defined by the OUTPUT FAIL MODE 1 parameter The...

Страница 46: ...the messages present Settings1 1 Menu path for ALARM DISPL TIME and ACK ALARM MODE GROUP SELECTION OPERATING MENU DIAGNOSTICS MESSAGES Measures ALARM DISPL TIME 0 s ACK ALARM MODE Off Rectify the cau...

Страница 47: ...on groups are only displayed for one measuring mode In addition there are also parameters that are only displayed if other parameters are appropriately configured For example the CUSTOMER UNIT P param...

Страница 48: ...SITION ADJUSTMENT There are parameters that are only displayed if other parameters are appropriately configured For example the CUSTOMER UNIT P parameter is only displayed if the User unit option was...

Страница 49: ...0P 2 Display via HART handheld terminal only Pressure OUTPUT SET MAX ALARM SET MIN CURRENT OUTPUT CURRENT OUTPUT FAIL MODE ALT CURR OUTPUT ASSIGN CURRENT CURR CHARACT DISPLAY SAFETY CONFIRM ALTERNATE...

Страница 50: ...E TYPE TRANSMITTER DATA DEVICE SERIAL No CUST TAG NUMBER ELECTR SERIAL No DEVICE DESIGN HARDWARE REV ADDITIONAL INFO SOFTWARE VERSION CONFIG RECORDER PCB TEMPERATURE ALLOWED MIN TEMP ALLOWED MAX TEMP...

Страница 51: ...PE ALARM DELAY ALARM DISPL TIME ALARM STATUS LAST DIAG CODE ACK ALARM MODE ACK ALARM ERROR NO SIMULATION MODE OPERATING HOURS INSERT PIN NO HistoROM AVAIL DOWNLOAD SELECT OPERATION DIAGNOSTICS SIMULAT...

Страница 52: ...Appendix Cerabar S 4 to 20mA HART 52 Endress Hauser...

Страница 53: ...Cerabar S 4 to 20mA HART Appendix Endress Hauser 53...

Страница 54: ...T 841 Safety confirm group 6 DIGITS SET Display group 19 DIP STATUS 363 26 DISPLAY CONTRAST 339 19 DOWNLOAD SELECT 014 32 DRAIN VENT MAT 27 DRAIN VENT POS 27 E ELECTR SERIAL No 386 25 ENTER RESET CODE...

Страница 55: ...0 34 SENS H WARE REV 487 28 SENSOR MEAS TYPE 581 28 SENSOR PRESSURE 584 Pressure measuring mode 30 SENSOR SER No 250 28 SENSOR TEMP 367 30 SET LRV 245 Pressure measuring mode 12 15 SET LRV 852 Safety...

Страница 56: ...www endress com worldwide BA00413P 00 EN 03 14 71270370 CCS FM SGML9 0 71270370...

Отзывы: