Cerabar PMP23 IO-Link
Description of device parameters
Hauser
55
14.3.2 System
HI Max value (maximum indicator)
Navigation
System → HI Max value (maximum indicator)
Description
This parameter is used as the maximum indicator and makes it possible to call up
retroactively the highest value ever measured for pressure.
A pressure that is present for at least 2.5 ms is logged to the maximum indicator.
The maximum indicators cannot be reset.
LO Min value (minimum indicator)
Navigation
System → LO Min value (minimum indicator)
Description
This parameter is used as the maximum indicator and makes it possible to call up
retroactively the lowest value ever measured for pressure.
A pressure that is present for at least 2.5 ms is logged to the maximum indicator.
The maximum indicators cannot be reset.
Revisioncounter (RVC)
Navigation
System → Revisioncounter (RVC)
Description
Counter that indicates the number of parameter changes.
Reset to factory settings (RES)
Navigation
System → Reset to factory settings (RES)
Description
L
WARNING
Confirming the "Standard Command" with "Reset to factory settings" causes an
immediate reset to the factory settings of the order configuration.
If the factory settings have been changed, downstream processes might be affected
following a reset (the behavior of the switch output or current output might be changed).
‣
Make sure that downstream processes are not started unintentionally.
The reset is not subject to additional locking, such as in the form of device locking. The
reset also depends on the device status.
Any customer-specific configuration carried out at the factory is not affected by a reset
(customer-specific configuration remains).
The following parameters are
not
reset when a reset is performed:
• LO Min value (minimum indicator)
• HI Max value (maximum indicator)
• Last Diagnostic (LST)
• Revisioncounter (RVC)