Technical data
Cerabar PMP23 IO-Link
62
Hauser
16.2.5 Signal on alarm 4 to 20 mA
The response of the output to error is regulated in accordance with NAMUR NE43.
Factory setting MAX alarm: >21 mA
alarm current
Device
Description
Option
PMP23
Adjusted min. alarm current
IA
1)
1)
Product Configurator order code for "Service"
16.2.6 Dead time, time constant
Presentation of the dead time and the time constant:
I
63 %
100 %
t
t
1
t
2
90 %
t
3
A0019786
16.2.7 Dynamic behavior
Dead time (t
1
) [ms]
Time constant (T63), t
2
[ms]
Time constant (T90), t
3
[ms]
7 ms
11 ms
16 ms
16.2.8 Dynamic behavior of switch output
Response time ≤20 ms