PROFIBUS-PA Electronics
A Cerabar M with PROFIBUS-PA
electronics has the following operating
options.
•
You can set a damping of between 0
and 40 s using communication.
•
You can set instrument bus address
direct in the instrument using the
address switch.
•
The digital display gives the pressure
as a four-digit number. The bar graph
depicts the current pressure value
related to the measuring range. The
measuring range can be set either on
site using the Zero and Span keys or
remotely using an operating program,
such as Commuwin II.
•
Error codes on the digital display and
in Commuwin II simplify error
diagnosis.
Smart Electronics Operation Using a
Handheld Terminal
Using the Universal HART
Communicator DXR 275 handheld
terminal, you can set the Cerabar M,
make checks and use additional
functions such as "Damping" and
"Calibration without reference pressure"
all along the 4...20 mA line.
4...20 mA
R
EX
EX
I
O
I
O
minimum line resistance
250
Ω
Universal HART Comunicator
DXR 275
Cerabar M
*
*
Use an
intrinsically
safe supply
voltage for Ex i
(e.g. RN 221 N)
Cerabar M
operation with Smart
electronics using a
handheld terminal
Zero Span
0,753
Zero Span
Display
address
on
off
1 2 3
1
2
3
4
5
6
7
8
ON
OFF
1
4
16 32 64
Switch No.
Value
SW
HW
2
8
Digital display
(optional)
Keys for
calibrating the
lower range-
value
and upper
range-value
Lower range-
value:
Display
1 x
Registration
1 x
Upper range-
value:
Display
2 x
2 x
Registration
Operating elements
DIP switches to set
bus address
8