8 Failure
If during, the test run or during operation a functional fault of the pressure actuated valve should
occur you are requested to open the valve (in an emergency) with the (optional) manual override
by hand.
For this observe chapter:
7. Emergency operation with manual override
If necessary, inform the shift foreman / safety engineer or the manager about the disturbance
without delay in order, for example, to avoid an outflow / overflow of chemicals or a discharge
of gases in good time by means of suitable measures!
Next, using the following list (8.1 Failure causes), attempt to find the reason for the causes of the
failure and, if it lies within your capabilities, to correct this.
Do not try to repair the pressure actuated valve!
Isolate the failed pressure actuated valve from the power supply and disconnect the pilot pres-
sure port!
In case of defect in the valve make contact with the supplier.
The telephone number will be found on the back cover of these mounting and installation manuel.
8.1
Failure causes
• Is the power supply to the control switched on?
• Is the device for the compressed-air switched on?
• Are the leads from the controller to the pressure actuated valve undamaged?
• Are the leads from the controller to the pilot valve undamaged?
Failure