EdgeRack 3P Series

USER MANUAL

Содержание ECX-ER3P-42UXX

Страница 1: ...EdgeRack 3P Series USER MANUAL ...

Страница 2: ...siness interruption resulting from arising from or in connection with the use of or inability to use this publication or the content even if Enconnex has been expressly advised of the possibility of such damages Enconnex reserves the right to make changes or updates with respect to or in the content of the publication or the format thereof at any time without notice Copyright intellectual and all ...

Страница 3: ...is manual are only to be used as a reference Enconnex reserves the right to change the parameters without prior notice In case of a lost damaged or misplaced manual a replacement copy can be requested from the Enconnex website www enconnex com This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledg...

Страница 4: ...ply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons to avoid a hazard Enconnex LLC Address 4670 Aircenter Circle Reno NV 89502 USA Website www enconnex com Customer service mailbox sale enconnex com Customer service number 1 510 651 2205 3 ...

Страница 5: ... 2 6 Weight capacity 14 3 Installation 15 3 1 Installation Instructions 15 3 1 1 Tools 15 3 1 2 Accessories 16 3 1 3 Self Prepared Materials 16 3 2 Equipment transportation unpacking inspection 16 3 2 1 Transportation Movement 16 3 2 2 Unpacking 20 3 3 Installation 21 3 3 1 Installing the cabinet 21 3 3 2 Installation of cooling accessories 23 3 3 3 Install the air duct 23 3 3 4 Connect the power ...

Страница 6: ...nment 34 4 2 5 Setting Environment 34 4 2 6 Setting Cooling 36 4 2 7 Log 36 4 2 8 Alarm 37 4 2 9 System 38 4 2 10 Remote access 38 5 Maintenance 39 5 1 Cooling system maintenance 39 5 2 UPS system maintenance 39 5 2 1 Check the UPS status 39 5 2 2 Replace the battery 40 5 3 Alarm reference 40 5 4 Troubleshooting 44 5 5 Electrical system layout 48 5 ...

Страница 7: ... damage caused by natural disasters 1 2 Local Rules and Regulations Local rules and regulations should be followed during equipment operation Safety precautions in the manual serve as a supplementary guide to local safety specifications 1 3 Basic Installation Requirements Personnel performing the EdgeRack 3P installation and maintenance must receive authorized training Equipment installation opera...

Страница 8: ...vironmental sensors remote monitoring and intuitive controls this turn key solution is 100 ready to be outfitted with whatever equipment you need for your business to be successful The EdgeRack 3P is ideal for areas where space is limited and or heat levels could be a concern and is a perfect solution for small to medium offices retail outlets educational institutions and remote edge computing loc...

Страница 9: ...3 5 kW Dimension W x D x H 600 mm x 1100 mm x 2025 mm Net weight 330 kg 2 3 Components The Edge Rack 3P product mainly includes a cabinet structure power distribution module PDM UPS Battery cooling units emergency ventilation system monitoring system and LCD display The system components are shown in Figure 2 2 and Table 2 2 Figure 2 2 Components 8 ...

Страница 10: ...dity sensors door switch leak detector and other dry contacts All information can be monitored remotely by the network For details refer to the monitoring system chapter 5 Access control ECX EdgeRack 3P 005 This provides keypad and fingerprint access to the EdgeRack at the front and rear doors 6 Double layered glass door ECX EdgeRack 3P 006 Isolate the inside and outside of the cabinet and protect...

Страница 11: ...e sorting and fixing to make the cable tidier and more standardized 15 PDU ECX EdgeRack 3P 015 This provides integral power distribution for user installed equipment 16 Smoke sensor ECX EdgeRack 3P 016 The smoke sensor provides alerts when activated 17 Steel split doors ECX EdgeRack 3P 017 Isolate the inside and outside of the cabinet and protect the equipment in the cabinet 18 Network switch ECX ...

Страница 12: ...50 60 Hz Note During operation in high temperature and high humidity environments there may be condensation on the external surface of the front glass door However it is a normal phenomenon and doesn t affect the operations or usage Derating is required for altitudes above 1000 m For the UPS the altitude should be less than 1500 m Derating is required for altitudes above 1500 m with reference to l...

Страница 13: ...at least 2 6 ft 800 mm is recommended on all sides of the installed EdgeRack 3P 2 6 ft 800 mm is also recommended between adjacent EdgeRack 3P units At least 400 mm space shall be reserved on the top of the unit Figure 2 3 Before opening the enclosure the space required for the rear door Edge Rack 3P model product space requirements inside the room where it is to be installed are mentioned in the ...

Страница 14: ...Figure 2 4 Model space requirements Figure 2 5 Top space requirements 13 ...

Страница 15: ...oor must be considered However during installation the weight bearing capacity of the floor should also be estimated based on the cabinet s total weight which also includes the installed equipment Note If the weight bearing capacity cannot be estimated consult the nearest ENCONNEX office or the customer service support center 14 ...

Страница 16: ...aintenance space reserved Note Ensure the installation location is capable of supporting the total weight of a fully loaded EdgeRack To ensure proper airflow prepare to use blanking panels on the front in RU spaces not occupied by IT equipment It is recommended that the EdgeRack be installed in a room that does not have employees working on a continual basis The cooling runs at about 62 dBA 3 1 1 ...

Страница 17: ... Prepared Materials Please prepare the below materials before operating the unit Table 3 3 Self Prepared Materials Parts Specifications Plug EU 2 IEC30916 16A US 2 L6 20P 20A Power wire cable 4 mm2 Network cable CAT6 3 2 Equipment transportation unpacking inspection 3 2 1 Transportation Movement The EdgeRack should be considered fragile and care must be taken during transport handling and installa...

Страница 18: ... 710 1210 2180 374 The EdgeRack 3P including the cabinet closed frames and the cooling unit needs to be moved to the vicinity of the installation site EdgeRack 3P as a piece of equipment with large components is on the heavier side and needs to be transported using equipment such as a hand pallet truck or electric forklift Figure 3 3 shows the schematic diagram of a hand pallet truck and an electr...

Страница 19: ...gure 3 4 Figure 3 4 Forklift Direction During transportation and installation in order to avoid pipes from being damaged and refrigerant from leaking the equipment should not be excessively jolted or tipped Warning After transportation like any refrigerant system you must keep it in its final location for some hours before starting up Transportation inclination shall not exceed 15 Stay for 8 hours...

Страница 20: ...s during the unloading and moving process Place the unit in the middle to guarantee symmetry It is important to move slowly and carefully to prevent dents and scratches to the equipment Check the quantity and type for accessories according to the packing list In case of missing accessories or nonconformity of models please keep field records and immediately contact the Enconnex Customer Service Ce...

Страница 21: ...ons Please follow the steps and procedures below to unpack Step 1 Cut the packing strap remove the top cover the fixing buckle the outer box and the foam Figure 3 6 Remove the outer packaging Step 2 Remove the machine fixing bracket and lift the equipment away from the pallet Figure 3 7 Remove the cabinet fixing device Step 3 Lift the cabinet off the pallet with a forklift 20 ...

Страница 22: ...llation site is clear The site gradient level has to be confirmed and should meet the requirements Switch off the power during installation Operation on any electrified equipment is forbidden The connecting cable must comply with related requirements 3 3 1 Installing the cabinet Following are the steps that need to be observed while installing the cabinet Step 1 Measure the height from the ground ...

Страница 23: ... weight of the cabinet without reliance on the casters Leveling feet adjustment method Use a wrench to adjust the leveling feet A clockwise adjustment of the leveling feet will increase the cabinet height A counterclockwise adjustment will decrease the height The leveling feet have an adjustment range of 0 mm 80 mm Leveling criteria Use a level to ensure widthwise and depth wise stability of the E...

Страница 24: ...AC return A flexible tube 5 meter x Φ350 mm is included If there is a request for the long distance air duct installation please purchase it with a diameter of 350 mm from a local supplier Below is the installed procedure Install the air duct mounting flange with the supplied M6x16 combination screws Place a duct clamp over the air duct mounting flange Install the air duct over the mounting flange...

Страница 25: ...main power and cooling unit power Connect single phase power supply L N PE cooling input power 16A 20A and UPS input power 16A 20A Figure 3 12 Connect the power supply of the cabinet 3 3 5 Network connection Figure 3 13 Connect the network cable to a network switch 24 ...

Страница 26: ...st Inspection Items Checking details and requests Unit appearance Appearance without damage surface is clean insulation is in good condition Electric line Power supply connection should not be loose Measure and record the voltage value before starting up the unit Electric control box The electrical components of the control box are good Top cooling unit No blocked on air inlet and air outlet spot ...

Страница 27: ...fter turning on the UPS input breaker and the UPS output breaker press and hold the ENTER ON button on the UPS shown in Figure 3 16 for 5 seconds to transfer UPS mode from bypass to line mode Figure 3 16 UPS controller key After UPS is powered on the normal status of the UPS LCD display screen is shown in Figure 3 17 26 ...

Страница 28: ...tions on the menu As shown in Figure 3 19 the user with User ID 1 is a super admin Figure 3 19 Add a Super Admin Add a Normal User Choose Normal User in User Role When the Super Admin is set Normal Users can only use palm fingerprint or password for verification when the Super Admin is not yet set Normal Users can operate all functions on the menu Password 1 to 8 digits of password are accepted NO...

Страница 29: ...er group verification Duress Fingerprint Users can choose one or more registered fingerprint s as Duress Fingerprint When that fingerprint is verified a duress alarm will be triggered Example Among those registered fingerprints 6 7 8 choose the 8th fingerprint as the duress fingerprint Figure 3 22 Duress fingerprint Apply Group Time Period When this function is on the user uses the default time zo...

Страница 30: ...Before the unit is powered down set the cooling to off in the Setting interface After turning off the UPS input breaker you need to press the OFF button at the front of the UPS panel to turn off UPS mode or it will work in battery mode 29 ...

Страница 31: ... CAT6 Figure 4 1 Network switch 4 2 Management system interface After the unit is powered on the monitoring host HMI automatically starts to enter the monitoring system The default password to enter the Setting and System interface is 4321 The management system also needs the password to access It is used to log out of the management system to the android interface The user name is admin password ...

Страница 32: ... such as the UPS Cooling Access control Temp sensor Smoke and Water leakage and when it turns red it indicates that the detection item has an alarm Curve The curve of the cold air temperature in the middle of the interface is used to monitor the cold channel temperature of the cabinet and can display the curve of the hour day month and year The curve of UPS output power shows the real time IT load...

Страница 33: ... mode of the unit Power Load Shows the current IT load which is also the output power load of UPS UPS Status Shows the operating information of the UPS Real time data Shows the UPS real time parameters such as input voltage output voltage battery cell voltage frequency and max temp Details Click to view all real time parameters of the UPS 32 ...

Страница 34: ...ature is detected by the temperature sensor which is on the compressor s suction pipe It is a critical parameter to reflect the operating status of the cooling unit Status Shows the operating status of cooling including operation status and the compressor output Setting Via this setting part you can set some parameters according to the application situation including Temp setting Humidity setting ...

Страница 35: ...e viewed Cold Air Humidity The cold air humidity data is regularly kept in the database and the data curves of the hour day month and year can be viewed 4 2 5 Setting Environment This part shows the current set point clicking on the back of the data box the setting parameters can be change it will pop up the keyboard for inputting data then click on the Set to complete the change After the success...

Страница 36: ...larm Low Humid 10 0 shows the low humidity alarm set point When the T H sensor located in the cold air side detects the humidity is less than this set humidity there will be a low humidity warning Emergency Ventilation Start Temp 45 When the detected temperature is higher than the set temperature the unit starts the emergency ventilation mode and the cabinet door will automatically open Stop Temp ...

Страница 37: ...fans for operation Temp Band 6 00 is the parameter that cooperates with the temperature to control the inverter compressor and fans for operation Humid Setting and Humid band are the parameters to control the operation of the humidifier which is an optional component 4 2 7 Log This part is the data record center for the key components such as UPS Cooling Environment Sensors and album The pictures ...

Страница 38: ...he toolbar to view all the alarm information click UPS Cooling Environment and Sensor respectively to view the corresponding alarm data It is by default that it will automatically show the alarms for all devices in the past one week Select the start time xxxx xx xx and the end time xxxx xx xx and click Update to view the historical alarm data of the time period 37 ...

Страница 39: ...in the email server address for the email sent Port Fill in the email server port for the email sent Account Send from Fill in the email account for the email sent Password Send from Fill in the email password for the email sent Account Send to Click Edit to enter the mailbox input interface and you can fill three mailbox accounts that will receive the alarm prompt Station Name Fill in the remark ...

Страница 40: ...l 1 Open the access panel on the side panel of the cooling unit Figure 5 1 Access panel of the cooling unit 2 Check the evaporative water tray 3 Open the hole cover at the bottom of the side panel and then take out the drain pipe through the hole for condensate drainage Figure 5 2 Condensate drainage diagram 5 2 UPS system maintenance 5 2 1 Check the UPS status Check the working status of the UPS ...

Страница 41: ...vice Note Be sure to deliver the spent battery to a recycling facility or ship it to ENCONNEX with the packing material of the replacement battery 5 3 Alarm reference For all of the alarms shown on the HMI you can find the related information in the table below Table 5 1 Alarm Instructions Warning Subject Warning Reason Reset Smoke The smoke sensor detects that the smoke concentration exceeds the ...

Страница 42: ...tting value High Humidity An alarm will be triggered when the humidity exceeds the setting value The alarm will be automatically reset when the humidity is lower than the setting value Low Humidity An alarm will be triggered when the humidity is lower than the setting value The alarm will be automatically reset when the humidity is higher than the setting value Communication Status The temperature...

Страница 43: ...e set value it will be reset automatically for 3 times If it exceeds 3 times it will not be reset automatically and manual reset is required on the HMI Suction Pressure Sensor Failure The suction pressure sensor failed to detect the pressure which is located on the suction pipe of the compressor After checking the wiring or refrigerant leakage pressure returns to normal it needs to be reset manual...

Страница 44: ...ct the temperature which is located on the liquid pipe inside the cooling unit After checking that the wiring or sensor replacement is normal it needs to be reset manually High Pressure Alarm The high pressure sensor detects that the pressure is higher than the setting pressure limit After the pressure returns to the set value it will be reset automatically for 3 times If it exceeds 3 times it wil...

Страница 45: ...connex technical support Communication Status The cooling unit doesn t communicate Check the cable connection and contact Enconnex technical support 5 4 Troubleshooting Below are basic troubleshooting steps Contact Enconnex technical support for further instruction Table 5 2 Troubleshooting Symptom Possible Causes Measures UPS has input and no output and the LED display of UPS does not light up Th...

Страница 46: ... 15 16 17 or 18 on the LCD display of UPS A UPS internal fault has occurred Contact your Enconnex technical support Battery backup time is shorter than nominal value Batteries are not fully charged Charge the batteries for at least 5 hours and then check capacity If the problem still persists contact Enconnex technical support Batteries are defective Contact Enconnex technical support Compressor o...

Страница 47: ...ndition and remove some heat load when necessary Cooling unit is not operating Contact Enconnex technical support Low temperature alarm Lower limit temperature settings are not reasonable Reset on the HMI The abnormal situations Check the room s sealed condition in winter and if there s any abnormal situation No web interface on the login page Common Problem a Confirm on the monitoring screen whet...

Страница 48: ...ck if the mailbox setting is correct the port supports 25 and 465 c Check whether the mailbox is authorized to be used on the client 5 5 Electrical system layout Below is the electrical system distribution diagram 47 ...