Check the contents include:
1)
Check the UPS if it is faulty. Once there is an alarm, the fault light will be on.
2)
Check if the UPS is operating in bypass mode. Usually, UPS should operate
in a normal mode. If the UPS is operating in bypass mode. Please find out the
reason, such as the human operation, overload, internal fault, etc.
3)
Check whether the battery is in a discharge state. When the main supply is
normal, the battery should not be discharged. When the UPS is operating in
battery mode, find out the reason, such as mains failure, battery test, operator
intervention, etc.
5.2.2.
Replace the battery
If the battery warranty (3~5 years at 25°C ambient temperature) has been
exceeded, the batteries must be replaced. In this case, please contact
ENCONNEX customer service.
Note:
Be sure to deliver the spent battery to a recycling facility or ship it to ENCONNEX
with the packing material of the replacement battery.
5.3.
Alarm reference
For all of the alarms shown on the HMI, you can find the related information in the
table below.
Table 5-1 Alarm Instructions
Warning Subject
Warning Reason
Reset
Smoke
The smoke sensor detects
that the smoke concentration
exceeds the set value and
triggers an alarm.
Manual reset is required. After
the smoke concentration has
been reduced below the alarm
value, remove the smoke sensor
cable and plug it in again.
Leakage
An alarm is triggered when
the water leakage detection
rope detects the water.
The alarm will automatically
reset when there is no water
detected.
Door
The magnetic switch detects
the closing/opening state of
the door, the door opening,
alarms, and the door closing
without alarm.
The alarm is automatically
eliminated when the door is
closed, and there is no other
impact.