Figure 4-6 Setting-Environment page
●
Temp Humidity Alarm Setting
"High Temp 41.0
℃
" shows the high-temperature alarm set point. When the T/H
sensor located in the cold air side detects the temperature is greater than this set
temperature, there will be a high-temperature alarm.
"Low Temp 10.0
℃
" shows the low-temperature alarm set point. When the T/H
sensor located in the cold air side detects the temperature is less than this set
temperature, it will appear as a low-temperature alarm.
"High Humid 95.0%" shows the high-humidity alarm set point. When the T/H
sensor located in the cold air side detects humidity greater than this set humidity,
there will be a high-humidity alarm.
"Low Humid 10.0%" shows the low-humidity alarm set point. When the T/H sensor
located in the cold air side detects the humidity is less than this set humidity, there
will be a low-humidity warning.
●
Emergency Ventilation
“Start Temp 45
℃
” When the detected temperature is higher than the set
temperature, the unit starts the emergency ventilation mode, and the cabinet door
will automatically open.
“Stop Temp 35
℃
” When the detected temperature is lower than or equal to the
set temperature, the cabinet door can be closed. However, the door needs to be
closed manually.
“Reset door” If the temperature has dropped after the alarm and did not reach the
stop temperature point, you can click reset to close the door normally.
“Open door” If you need to test or check the state of the door, click on it to open
the door; the magnetic power will be turned off, and the door will be open.