ENCO Control  

Technical description 

 

Kulautuvos g. 45a , LT-47190 Kaunas

 

Tel. (+370 37) 360234 

Faks. (+370 37) 360358 

 

[email protected]  

 www.axis.lt 

 

Remote communication

 

The device can communicate via Ethernet, GSM / GPRS. It supports protocols TCP / IP, UDP, 
DHCP. 
There is possibility to setup parameters, download archive files, and update the firmware 
remotely. 

The selected

 

system messages

 

are sent

 

to the user

 

remotely:

 

     -     Power supply Off / On; 
     -     Changing of firmware (updating); 
     -     Changing of  the state of the logic inputs (high / low level); 
Read archived data;  
Change settings of HVAC and meter reading. 
 
 

Explanation of Abbreviations 

 

PSU 

Power supply unit 

MCU 

Microprocessor 

LCD 

Liquid Crystal Display 

SIM 

Subscriber identification module (card) 

RFID 

Radio frequency identification  

CN1 

USB port 

RTC 

Real-time clock 

DC 

Direct current 

AC 

Alternating current 

HVAC 

Heating, ventilation and air conditioning systems  

 

 

 

 
 

Environmental conditions 

 

Ambient temperature 

5°C ÷ 55°C 

Relative humidity    

Up to 93% 

 

 

Degree of protection  of housing to IEC 60529 

IP30    (The  device  is  designed  for 
installation in a cabinet, corresponding to 
the class IP65) 

Overall dimensions  
 

202 mm x 126 mm x 100 mm 

Power supply 

 

Power  supply for  9 NO semiconductor  relays 
 

230 V, 50 Hz, ~ 1,2 A for each of 9 relays, 
~ 4 A total 

Mains supply for internal PSU 

230 V, 50 Hz, ~100 mA max; 

Backup battery 

12 V, 

800 mA max., 1,2 - 2.2 Ah 

Internal  Lithium battery for real time clock (RTC) 

3 V 

 

 

Inputs / outputs for connecting remote devices

 

 

Содержание Control

Страница 1: ...ENCO Control Technical description Kulautuvos g 45a LT 47190 Kaunas Tel 370 37 360234 Faks 370 37 360358 info axis lt www axis lt 1 Universal controller ENCO Control Technical description Lithuania 2015 ...

Страница 2: ...ed the switch is built in the same cabinet as the controller electromagnetic actuators pumps actuators etc to make sure that they are not powered Protection of circuits of external battery is provided by fuse RXE185 50V 1 8A Controller does not protect external circuits of circulation pumps and valve actuators It is necessary to use additional protection circuits to protect circulation pumps and v...

Страница 3: ...ment should be protected against mechanical damage and shock Equipment should be stored in dry heated premises where environment temperature is not lower than 5 c o No aggressive chemical substances should be stored together because of corrosion hazard SWITCHING ON OFF Switch on the power Fig 1 The device is ready for operation Device status indicates LED1 Fig 2 Power is on the LED1 lights up and ...

Страница 4: ...electing of the frequency period archiving from 1s Archiving of parameters technological process and variables in the heating system every 5 minutes to 7 days Sending of message if parameter value exceeds the limits up to 32 selected parameters Meter reading The controller can read all meters that support MBUS protocol Reading is performed Wild addresses There is a possibility to read out only one...

Страница 5: ...nit MCU Microprocessor LCD Liquid Crystal Display SIM Subscriber identification module card RFID Radio frequency identification CN1 USB port RTC Real time clock DC Direct current AC Alternating current HVAC Heating ventilation and air conditioning systems Environmental conditions Ambient temperature 5 C 55 C Relative humidity Up to 93 Degree of protection of housing to IEC 60529 IP30 The device is...

Страница 6: ...er of pressure measuring inputs 4 20 mA measurement channels 4 Number of temperature sensors 16 Communication modules and interfaces GPRS 900 1800 MHz 1 Ethernet 1 RS232 2 3 3V 1 RS485 1 Mbus CL 1 Card reader RFID 1 Screens displayed on LCD during operation are linked together and form well organized menu structure For convenience the screens are grouped into levels Review of menu items is perform...

Страница 7: ...he controller 6 Outputs Inputs Review and control of status of Outputs Inputs 7 Connection state Status of communication systems 8 Set date time Setting up date and time 9 Lock configuration Lock possibility of configuration 1 HVAC system type selection The controller is capable of controlling different HVAC systems circuits 1 HVAC 1 HVAC 2 HVAC 3 HVAC 1 1 HVAC settings 1 HVAC type 1 1 1 HVAC type...

Страница 8: ...on time of drive control 4 Transition Transition time period during which circuit gradually changeovers from one schedule to another 5 Integration Integration time 6 ECO temper Desired temperature for economic mode 7 NIGHT temper Desired night temperature 8 DAY temper Desired day temperature 9 Valves settings Settings of drive valve control address 10 Pump settings Settings of pump control address...

Страница 9: ...dem settings 3 DHCP settings 4 Ping settings 5 NTP settings 6 Summer correct On 7 Reboot On 8 Reboot per 1440 9 UDP hello 37770 10 Device ID 1 11 Firmw Vers 1 16 12 FDate Apr 27 2012 13 FTime 15 41 31 You can select LAN or GPRS 2 1 Connect type 1 Ethr 2 GPRS If you use GPRS connection then you will need to set your modem settings Modem settings 2 2 Modem settings 1 Port settigs 2 GPRS ping On 3 GP...

Страница 10: ...g period 4 IP Remote server s IP address if Ping does not take place with gateway Setting time synchronization of device via network 2 5 NTP settings 1 Check time Off 2 NTP interface Ethr 3 NTP period 1440 4 NTP port 123 5 IP 192 168 0 1 6 Time zone 2 Field Description 1 Check time Time synchronization On Off 2 NTP interface Communication interface to synchronize the time 3 NTP period Time synchro...

Страница 11: ...P address DHW UDP hello Yes No 37770 3 settings for reading external devices meters 3 Modules 1 Module 2 Module 3 Module 4 Module 5 Module 6 Module 7 Enable connect On 8 Connect type Ethr 9 Connect prt 37777 10 Remote enable Off 11 IP 192 168 0 211 12 Remote port 37775 13 Connect per 3600 Select the required device type 3 1 Module 1 Type 3 1 1 Module 1 2 SKS 3 3 SKM 1 M 4 SKM 01M 5 SKU01 6 SKU01SF...

Страница 12: ... 19200 8 38400 9 56700 10 115200 Set up parity It should be the same as stated on readout device settings 3 1 6 Parity 1 None 2 Odd 3 Even 4 Mark 5 Space Select database data archive wherein will be stored data collected from an external device 3 1 7 Array 1 0 2 1 3 2 4 3 Set up device address or number depending what applicable DHW Addr ID Yes No 254 Meter reading period DHW Period Yes No 3600 3 ...

Страница 13: ...the number of sensors that have been found 3 T xx Shows temperature value of corresponding sensor It is possible to change the sensor number review and control of inputs outputs status 6 Outputs Inputs 1 Output0 2 Output1 3 Output2 4 Output3 5 Output4 6 Output5 7 Output6 8 Output7 9 Output8 10 Input0 11 Input1 12 Input2 13 Input3 14 Input4 15 Input5 16 Input6 The black dot inside the circle means ...

Страница 14: ... Selecting of the frequency period archiving from 1s Archiving of parameters technological process and variables in the heating system every 5 minutes to 7 days Sending of message if parameter value exceeds the limits up to 32 selected parameters The controller can read all meters that support MBUS protocol Reading is performed Wild card search algorithm The data from the meters can be read out to...

Страница 15: ...Figure 20 Figure 21 The necessary switches must be provided during the installation distance between switches contacts must be 3 mm With which you can turn off the power supply It is recommended to establish the device in the same cabinet as the switches for cutting off power supply The switches should be adjusted for the power used by the equipment max 15VA Connection cables must comply with IEC ...

Страница 16: ...s 370 37 360358 info axis lt www axis lt 16 Numbering of terminals 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48 47 46 45 44 43 42 41 40 39 38 37 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 LCD GPRS modem CN1 J28 J27 J29 J21 R F SIM PSU ...

Страница 17: ...iscrete input 2 10 m 17 Discrete input 2 18 D3 D3 Discrete input 3 10 m 19 Discrete input 3 20 15 V 100 mA max GND Ground 10 m 21 V Power supply output for external devices z 10 m 22 RFID Antenna R1 Antenna RFID 0 3 m 23 R2 24 T sensor GND GND for digital temperature sensors 70 m 25 DATA Signal terminal for digital temperature sensors 70 m 26 5 V 5 V power supply voltage for digital temperature se...

Страница 18: ... R 3 m 43 D4 44 15 V 100 mA max V Power supply for external devices 10 m 45 GND Ground 10 m 46 Discrete inputs D5 D6 0 3 V 10 mA max D 5 Discrete input 5 0 3V Rin 100 R 3 m 47 48 GND Ground 10 m 49 D 6 Discrete input 6 0 3V Rin 100 R 3 m 50 51 Semiconductor relays NO O0 O5 230 V 50Hz 1 2A each Total current for all relays 4 A Max O5 O5 Power output 5 3 m 52 53 O4 O4 Power output 4 3 m 54 55 O3 O3 ...

Страница 19: ...2 61 60 59 58 57 56 55 54 53 52 51 50 49 48 47 46 45 44 43 42 41 40 39 38 37 J28 J27 J21 J29 PSU 230V Enco Control DIN0 DIN1 DIN2 DIN3 б Power is supplied from the external DC voltage 24 V 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48 47 46 45 44 43 42 41 40 39 38 37 J28 J27 J21 J29 PSU 230V Enco Cont...

Страница 20: ...0R 100R 5V 100R 100R M BUS device connection 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48 47 46 45 44 43 42 41 40 39 38 37 J28 J27 J21 J29 PSU 230V Enco Control GND GND A1 A3 A2 V A0 M BUS device M BUS device Pressure sensors wiring diagram 4 sensors 4 20 мА 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ...

Страница 21: ... control output connection 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48 47 46 45 44 43 42 41 40 39 38 37 J28 J27 J21 J29 Enco Control Out 0 Out 1 Out 2 Out 3 Out 4 Out 5 Out 8 Out 7 Out 6 M1 M2 M3 SF4 SF5 SF6 230 N 230 L SF1 SF2 SF3 V1 V2 V3 ...

Страница 22: ...Kulautuvos g 45a LT 47190 Kaunas Tel 370 37 360234 Faks 370 37 360358 info axis lt www axis lt 22 Wiring diagram for connecting of the temperature sensors and RFID antennas 22 24 23 26 25 T0 T1 T2 T3 T15 Blue Brown Yellow RF ID T sensor ...

Страница 23: ...mber Description Serial interface connector J28 type RJ11 J28 1 Port 1 signal TX RS232 J28 2 Port 1 GND J28 3 Port 1 signal RX RS232 J28 4 Port 2 GND J28 5 Port 2 TX TTL J28 6 Port 2 RX TTL Serial interface connector J27 type RJ11 J27 1 Port 0 signal TX RS232 J27 2 Port 0 GND J27 3 Port 0 signal RX RS232 J27 4 J27 5 J27 6 Expansion connector J29 type RJ11 J29 1 J29 2 GND J29 3 J29 4 GND J29 5 RS48...

Страница 24: ...ENCO Control Technical description Kulautuvos g 45a LT 47190 Kaunas Tel 370 37 360234 Faks 370 37 360358 info axis lt www axis lt 24 Enco Control into the cabinet with the opened first transparent door ...

Страница 25: ...description Kulautuvos g 45a LT 47190 Kaunas Tel 370 37 360234 Faks 370 37 360358 info axis lt www axis lt 25 AB Axis Industries Kulautuvos g 45a LT 47190 Kaunas Lithuania Tel 370 37 36 02 34 Faks 370 37 36 03 58 info axis lt ...

Отзывы: