CDS3-1H-DED
26
4.3.
E
QUIPMENT REPAIRS
Disconnect the battery charger from the AC power network and disconnect the batteries before undertaking
any repairs.
When fuses have blown, only use fuses of the type and size recommended in this manual.
Please contact a reseller or ENAG for any other repairs.
5.
TECHNICAL SPECIFICATIONS
Models
CDS3/12-100
CDS3/24-120
CDS3/48-60
Input
Voltage
from 85 to 265VAC single phase
Output power from 85 to 170Vac
100%
75%
75%
Frequency
From 47 to 65Hz
Current intensity 230/115Vac
7,4 A / 15,2 A
16,8 A / 26,2 A
15,2 A / 23 A
Power factor
0,9 in rated conditions
Efficiency
> 80% in rated conditions
Input fuses
2 x 32A 400Vac
(10x38) (F1/F2)
2 x 32A 400Vac (10x38)
(F1/F2)
2 x 32A 400Vac (10x38)
(F1/F2)
Sortie
Number of outputs
1 separated output BAT 1
1 additional output +SP (before integrated distributor) for specific use, do not
connect it directly to a battery
Each output can be used on its own and supply the entire current.
Total rated current (+/-7%) / Rated power
100A/1425W
120A/3420W
60A/3420W
Load curve
Type of charge selected using internal switch IU or IUoU (Boost, Absorption,
Floating – factory setting).
Type of batteries
See selection wheel setting table
Regulated and filtered output voltage
See selection wheel setting table. The chargers can operate on DC supply.
Regulation tolerance before distributors and
fuses
< 2% (in rated conditions)
Peak-to-peak ripple and noise
< 2% (in rated conditions)
Output fuses mounted in the BAT pole -
125A 150Vdc HRC
125LET
(F3)
160A 150Vdc HRC
160LET (F3)
80A 150Vdc HRC
80LET (F3)
Environment
Operating temperature
Rated conditions: from - 10°C to + 55 °C; over, de-rating : reduction of the output
power < than 2,5 %/°C up to 65°C
Cooling
Continuous draft fans
Relative humidity
Up to 70% (95% with no condensation)
Storage temperature
-20°C to +70°C
Casing
Material
Casing comprises :
Steel frame and steel front cover
-
Polycarbonate clasp
Paintwork
Grey, black matt epoxy coating
Dimensions excluding cable gland (length,
height, depth) / Weight
350 x 400 x 123mm / 12,7Kg
Fixing centre distances
328 x 292 mm
Fixing screw (wall)
4 M5 round screws
Protection factor
IP22 (with cable glands)
Board protection
Protected with water-repellent varnish (marine environment)
Standards
CE/EMC marking
NF EN61000-6-1, NF EN61000-6-2, NF EN61000-6-3, NF 61000-6-4
CE/safety marking
NF EN60950, NF EN60335-2-29
Electrical protections
- Against leaking input surges by rupture of VDR (voltage dependent resistor)
(not covered by warranty)
- Against output polarity reversals by rupture of fuses
- Against output short-circuits and surges
- Against abnormal overheating by cutting off the charger (internal temperature
probe 90°C), Automatic re-start
- Against output surges (17V
±
5% for12V)
(34V
±
5% for 24V)
(68V
±
5% for 48V)
Содержание CDS3/12-100
Страница 76: ...CDS3 1H DED 74 Annexe Appendix Anhang Anexo Allegato...
Страница 82: ......