Page 11

12821-2-0903

To Remove Main Burner
1.

Disconnect the thermocouple and pilot supply line at the pilot
burner.

2.

Unscrew the nut on the orifice fitting union.  Orifice fitting is
threaded into the main burner.

3.

Remove screw on each side of the main burner and lift out.

To Remove Main Burner Orifice
1.

Unscrew the nut on the orifice fitting union.  Orifice fitting is
threaded into the main burner.

2.

Unthread the orifice fitting from the main burner.

3.

Main burner orifice is located at the end of the orifice fitting.

4.

Remove main burner orifice from orifice fitting with a 1/2"
(13mm) wrench.

MAINTENANCE

TROUBLESHOOTING

Cleaning Combustion Chamber
A qualified serviceman should remove the chamber and apply air
pressure to the inside in order to clear all passageways.

1.  Impossible to light pilot

a.

If using piezo ignitor, check electrode location.

b.

Remove nut at orifice and check for gas.

c.

If gas available, check for blocked orifice or pilot.

2. Pilot outage

a.

Proper size of pilot flame.

b.

Defective or weak thermocouple.

3. Pilot flames but goes out when knob is released

a.

Pilot flame not covering the thermocouple properly.

b.

Defective thermocouple.

c.

Defective magnet in the safety section of valve.

4. Poor thermostat control

a.

Thermostat needs calibrating.

b.

Defective thermostat section.

 5. Noisy blower

a.

Tighten blower screws.

b.

Check blower wheel in the open for balance.

6. Yellow main burner flame

a.

Remove main burner to check for obstructions in throat,
ports and orifices.

b.

Install new main burner orifice and pilot orifice.

c.

Check gas valve for leaking.

d.

Open the air shutter on the main burner in order to
increase the amount of primary air.

 7. Yellow pilot flame

a.

Small yellow tip not objectionable.

b.

Remove pilot orifice. Check and clean.

8. Pilot and main burner goes out after burning a few

minutes
a.

Improper venting of flue products.  Relight and check for
improper venting.

b.

If vented properly, check vent safety switch, replace if
defective.

 9. Burner flashes- back or “pops” and burns 

at 

main

burner orifice
a.

Examine main burner for defects.

10. Inoperative blower

a.

Check fan control by shorting across terminals.

b.

Check for blower wheel bind by removing wheel and
operating motor.

c.

Check for frozen bearings due to lack of oil.

Содержание RH-25-6

Страница 1: ...iance Donottouchanyelectricalswitch donotuseanyphoneinyourbuild ing Immediatelycallyourgassupplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas sup plier...

Страница 2: ...ng 7 Vent Safety Shutoff System 8 Reversible Vertical or Horizontal Diverter 8 Thermostat Operation 8 Lighting Instructions 9 Pilot Flame Characteristics 10 Main Burner Flame Characteristics 10 Mainte...

Страница 3: ...ir passageways of the room heater be kept clean DO NOT put anything around the heater that will ob struct the flow of combustion and ventilation air See clearances DO keep the appliance area clear and...

Страница 4: ...service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on walls of n...

Страница 5: ...olor tile that can discolor Floor pad is available from Empire Comfort Systems Inc Part Number DVP 1 Qualified Installing Agency Installation and replacement of gas piping gas utilization equip ment o...

Страница 6: ...Never pressure test with appliance connected control valve will sustain damage A gas valve and ground joint union should be installed in the gas line upstream of the gas control to aid in servicing I...

Страница 7: ...l be installed in a location in which the facilities for ventilation permit satisfactory combustion of gas and proper venting under normal conditions In buildings of conventional frame brick or stone...

Страница 8: ...al position to the horizontal position 1 Remove L280 vent safety switch from the draft diverter 2 Inside your yellow instruction envelope will be a 1 1 2 x 2 1 4 38mm x 51mm vent safety switch hole co...

Страница 9: ...mediately call a qualified service techni cian to inspect the appliance and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS 1 Set thermos...

Страница 10: ...lot orifice Figure 5 MAIN BURNER FLAME CHARACTERISTICS There will be a short blue inner flame with a larger lighter blue secondary flame The burner flame may have yellow tips when hot Dust in the comb...

Страница 11: ...uple 3 Pilot flames but goes out when knob is released a Pilot flame not covering the thermocouple properly b Defective thermocouple c Defective magnet in the safety section of valve 4 Poor thermostat...

Страница 12: ...737 Burner RH 25 6 23 RH 738 Burner RH 35 6 24 R 1195 Thermocouple 36 25 R 1227 Pilot Burner with Orifice Nat 25 R 1228 Pilot Burner with Orifice LPG 26 11698 Pilot Tubing 27 R 6120 Electrode and Wir...

Страница 13: ...Page 13 12821 2 0903 PARTS VIEW...

Страница 14: ...5 6 and RH 35 1 2 4 5 6 replace casing front 5 For DV 25 1 2 SG and DV 35 1 2 SG replace heat shield and casing front Attention Wiring harness on blower is factory assembled and installed If wiring h...

Страница 15: ...rvicing WARNING Unplugging of blower accessory will not stop the heater from cycling To shut heater off 1 Turntemperaturedial orthermostattolowestsetting 2 Turnknobongascontrolto OFF depressingslightl...

Страница 16: ...E NOTES Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62220 2623 PH 1 618 233 7420 PH 1 800 851 3153 FAX 1 618 233 7097 FAX 1 800 443 8648 E MAIL info empirecomfort com WEB...

Отзывы: