PILOT FLAME CHARACTERISTICS

The correct flame will be almost horizontal, blue and will extend
past the thermocouple 1/4" (6mm).  The flame will surround the
thermocouple just below the tip.

On  Propane (LP-gas) slight yellow might occur where the pilot
flame and the burner flame meet.

Natural gas pilots require adjusting when the inlet pressure is
above 5" w.c. (1.25kPa)   Remove pilot adjustment cover.  Turn
adjustment screw clockwise to reduce flame.

Propane (LP-gas) will not require adjusting.

After use, cleaning of the pilot burner may be required for the
proper flame.  The pilot orifice can be cleaned with high pressure
air or by placing under running water.  Pilot orifice must be dry
before replacement.  Use a pipe cleaner to clean inside the pilot
after the pilot orifice has been removed.

To Remove Pilot Orifice
1.

Disconnect the pilot supply line at the pilot burner.

2.

Remove pilot orifice from pilot burner.It may be necessary to
tap on pilot burner in order to remove the pilot orifice.

Figure 5

MAIN BURNER FLAME CHARACTERISTICS

There will be a short blue inner flame with a  larger, lighter blue
secondary flame.  The burner flame may have yellow tips when
hot.  Dust in the combustion air will produce an orange or red
flame.    Do not mistake the orange or red flame for an improper
yellow flame.

Attention:   On Propane gas, if a whistling noise (resonation)
occurs close the air shutter on the main burner in order to reduce
the amount of primary air.  The reduction in primary air will soften
the main burner flame and will eliminate the whistling noise
(resonation).

On Propane or Natural gas if a yellow flame occurs open the air
shutter on the main burner in order to increase the amount of
primary air.  The increase in primary air will sharpen the main
burner and will eliminate the yellow flame.

After use, cleaning of the main burner may be required for the
proper flame.  The main burner may be cleaned by forcing water
into the ports and the throat of the burner.  The burner should be
blown dry or heated to remove all water before replacement.

Figure 6

On Propane Gas, if a whistling noise (resonation) occurs

a.

Close the air shutter on the main burner in order to reduce
the amount of primary air.

Содержание RH-25-6

Страница 1: ...iance Donottouchanyelectricalswitch donotuseanyphoneinyourbuild ing Immediatelycallyourgassupplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas sup plier...

Страница 2: ...ng 7 Vent Safety Shutoff System 8 Reversible Vertical or Horizontal Diverter 8 Thermostat Operation 8 Lighting Instructions 9 Pilot Flame Characteristics 10 Main Burner Flame Characteristics 10 Mainte...

Страница 3: ...ir passageways of the room heater be kept clean DO NOT put anything around the heater that will ob struct the flow of combustion and ventilation air See clearances DO keep the appliance area clear and...

Страница 4: ...service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on walls of n...

Страница 5: ...olor tile that can discolor Floor pad is available from Empire Comfort Systems Inc Part Number DVP 1 Qualified Installing Agency Installation and replacement of gas piping gas utilization equip ment o...

Страница 6: ...Never pressure test with appliance connected control valve will sustain damage A gas valve and ground joint union should be installed in the gas line upstream of the gas control to aid in servicing I...

Страница 7: ...l be installed in a location in which the facilities for ventilation permit satisfactory combustion of gas and proper venting under normal conditions In buildings of conventional frame brick or stone...

Страница 8: ...al position to the horizontal position 1 Remove L280 vent safety switch from the draft diverter 2 Inside your yellow instruction envelope will be a 1 1 2 x 2 1 4 38mm x 51mm vent safety switch hole co...

Страница 9: ...mediately call a qualified service techni cian to inspect the appliance and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS 1 Set thermos...

Страница 10: ...lot orifice Figure 5 MAIN BURNER FLAME CHARACTERISTICS There will be a short blue inner flame with a larger lighter blue secondary flame The burner flame may have yellow tips when hot Dust in the comb...

Страница 11: ...uple 3 Pilot flames but goes out when knob is released a Pilot flame not covering the thermocouple properly b Defective thermocouple c Defective magnet in the safety section of valve 4 Poor thermostat...

Страница 12: ...737 Burner RH 25 6 23 RH 738 Burner RH 35 6 24 R 1195 Thermocouple 36 25 R 1227 Pilot Burner with Orifice Nat 25 R 1228 Pilot Burner with Orifice LPG 26 11698 Pilot Tubing 27 R 6120 Electrode and Wir...

Страница 13: ...Page 13 12821 2 0903 PARTS VIEW...

Страница 14: ...5 6 and RH 35 1 2 4 5 6 replace casing front 5 For DV 25 1 2 SG and DV 35 1 2 SG replace heat shield and casing front Attention Wiring harness on blower is factory assembled and installed If wiring h...

Страница 15: ...rvicing WARNING Unplugging of blower accessory will not stop the heater from cycling To shut heater off 1 Turntemperaturedial orthermostattolowestsetting 2 Turnknobongascontrolto OFF depressingslightl...

Страница 16: ...E NOTES Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62220 2623 PH 1 618 233 7420 PH 1 800 851 3153 FAX 1 618 233 7097 FAX 1 800 443 8648 E MAIL info empirecomfort com WEB...

Отзывы: