THERMOSTAT LOCATION (SG MODELS)
CAUTION —
Do not run wire behind flanges of Header Plate
or in any location where it might be damaged.
Millivolt wall thermostats are specially designed for use on self-
generating systems. They should
never
be used on
line
or
low
voltage A.C. circuits.
Interior Wall —
The thermostat should be installed on an inside
wall away from the furnace but in the same room.
It is important to use wire of a gauge proper for the length of the
wire:
RECOMMENDED WIRE GAUGES
Maximum Length
Wire Gauge
1' to 10'
18
10' to 25'
16
25' to 35'
14
Proper operation depends on a good pilot flame. The flame must
cover the top of the thermopile. Cleaning of the pilot orifice and
burner may be required due to spiders.
System Check (Figure 7)
A millivolt meter is required to check the system. Millivolt
readings should be:
• Across the thermopile terminals, 400-450 millivolts with
thermostat OFF.
• Across the thermopile terminals, 150-250 millivolts with
thermostat ON.
• Across the thermostat wires at the valve, less than 30 millivolts
with thermostat ON.
• Across the thermostat wires at the thermostat, less than 5
millivolts with thermostat ON. (Dirty pilot or low pressure
will reduce readings.)
Connect thermostat wires to gas valve as shown in Figure 7.
Figure 7
12425-9-0107