background image

23466-4-0509

Page 9

3.  Add the BTU/Hr of all fuel burning appliances in the space.

 Vent-free heater    

 BTU/Hr

 Gas water heater   

 BTU/Hr

 Gas furnace 

 

 BTU/Hr

 Vented gas heater  

 BTU/Hr

 Gas fireplace logs  

 BTU/Hr

 Other gas appliances*  +   

 BTU/Hr

 Total 

 

 BTU/Hr

Example:  Vented gas heater   

20,000 

BTU/Hr

  

  Vent-free heater  

18,000 

BTU/Hr

  

  Total 

 

38,000 

BTU/Hr

*Do not include direct-vent gas appliances. Direct vent draws 

combustion air from the outdoors and vents to the outdoors.

4. Compare the maximum BTU/Hr the space can support with the 

actual amount of BTU/Hr used.

 

 BTU/Hr (maximum the space can support)

 

 BTU/Hr (actual amount of BTU/Hr used)

  Example: 

    25,600 

BTU/Hr (maximum the space can support)

    38,000 

BTU/Hr (actual amount of BTU/Hr used)

Warning:

 If the area in which the heater may be operated is smaller 

than that defined as an unconfined space or if the building is of 

unusually  tight  construction,  provide  adequate  combustion  and 

ventilation air by one of the methods described in the National 

Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and 

Ventilation, or applicable local codes.

The space in the above example is a confined space because the 

actual BTU/Hr used is more than the maximum BTU/HR the space 

can support. You must provide additional fresh air. Your options 

are as follows:

A.  Rework worksheet, adding the space of an adjoining room. If 

the extra space provides an unconfined space, remove door to 

adjoining room or add ventilation grills between rooms. See 

Ventilation Air From Inside Building.

 

B.  Vent room directly to the outdoors. See 

Ventilation Air From 

Outdoors.

C.  Install a lower BTU/Hr heater, if lower BTU/Hr size makes 

room unconfined.

If the actual BTU/Hr used is less than the maximum BTU/Hr the 

space can support, the space is an unconfined space. You will need 

no additional fresh air ventilation.

WARNING: You must provide additional ventilation air 

in a confined space.

This heater shall not be installed in a confined space or unusually 

tight  construction  unless  provisions  are  provided  for  adequate 

combustion and ventilation air.

The National Fuel Gas Code defines a confined space as a space 

whose volume is less than 50 cubic feet per 1,000 Btu per hour 

(4.8m

3

  per  kw)  of  the  aggregate  input  rating  of  all  appliances 

installed in that space and an unconfined space as a space whose 

volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m

3

 

per kw) of the aggregate input rating of all appliances installed in 

that space. Rooms communicating directly with the space in which 

the appliances are installed, through openings not furnished with 

doors, are considered a part of the unconfined space.

Unusually Tight Construction

The air that leaks around doors and windows may provide enough 

fresh air for combustion and ventilation. However, in buildings of 

unusually  tight  construction,  you  must  provide  additional  fresh 

air.

 

Unusually  tight  construction  is  defined  as  construction 

where:

a.  Walls and ceilings exposed to the outside atmosphere have 

a continuous water vapor retarder with a rating of one perm 

or less with openings gasketed or sealed, and

b.  Weatherstripping has been added on openable windows and 

doors, and

c.  Caulking  or  sealants  are  applied  to  areas  such  as  joints 

around window and door frames, between sole plates and 

floors, between wall-ceiling joints, between wall panels, at 

penetrations for plumbing, electrical, and gas lines, and at 

other openings.

  If your home meets all of the three criteria above, you must provide 

additional fresh air. See 

“Ventilation Air From Outdoors,”

 

page 10.

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined 

space.   

 

Space:

 Includes the room in which you will install heater plus any 

adjoining rooms with doorless passageways or ventilation grills 

between the rooms.
1. Determine the volume of the space (length x width x height).

  Length x Width x Height = 

 cu. ft. (volume of 

space)

Example: Space size 16 ft. (length) x 10 ft. (width) x 8 ft. (ceiling 

height) = 1,280 cu. ft. (volume of space)

  If additional ventilation to adjoining room is supplied with grills 

or openings, add the volume of these rooms to the total volume 

of the space.

2.  Divide  the  space  volume  by  50  cubic  feet  to  determine  the 

maximum BTU/Hr the space can support.

 

 (volume of space) ÷ 50 cu. ft. = (maximum 

BTU/Hr the space can support)

Example: 1,280 cu. ft. (volume of space) ÷ 50 cu. ft. = 25.6 or 

25,600 (maximum BTU/Hr the space can support)

PROVISIONS FOR ADEQUATE COMBUSTION & VENTILATION AIR

Содержание VFD26FM series

Страница 1: ...per hour Refer to page 8 WARNING If not installed operated and main tained in accordance with the manufacturer s in structions this product could expose you to sub stances in fuel or from fuel combus...

Страница 2: ...ERS ROCK WOOL 16 OPERATION INSTRUCTIONS FLAME APPEARANCE 16 A VFD26FP3L10 LIGHTING INSTRUCTIONS 17 A VFD26F M P 3 LIGHTING INSTRUCTIONS 18 A VFD26F M P 2 LIGHTING INSTRUCTIONS 19 PILOT FLAME CHARACTER...

Страница 3: ...e hazard of high surface temperature and should stay away to avoid burns or clothing ignition Young childrenshould becarefullysupervisedwhen they are in the same room with the appliance Do not place c...

Страница 4: ...ight pilot lights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or...

Страница 5: ...gas company before changing spud orifice size Warning Failure to keep the primary air opening s of the burner s clean may result in sooting and property damage Instructions to Installer 1 Installer m...

Страница 6: ...own in Figure 2 for corner rough opening Be sure to provide gas line for fireplace and electrical power for optional blower assembly 1 Attach two 2 nailing flanges to firebox sides with two 2 10 x 1 2...

Страница 7: ...E OPENING JUNCTION BOX ASSEMBLY GAS LINE OPENING J I K B C G A D E Figure 4 A VFD26 Series Dimensions Index Letter Dimension A 30 1 4 768mm B 30 762mm C 13 1 8 333mm D 18 1 8 460mm E 26 660mm G 25 635...

Страница 8: ...rmostat FREC Electric Remote Control FWS 1 Wall Switch TMV Wall Thermostat Millivolt Reed Switch TRW Wireless Remote Wall Thermostat Water vapor is a by product of gas combustion An unvented room heat...

Страница 9: ...e volume is less than 50 cubic feet per 1 000 Btu per hour 4 8m3 per kw of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not l...

Страница 10: ...e extra fresh air by using ventilation grills or ducts You must provide two permanent openings one within 12 of the ceiling and one with 12 of the floor Connect these items directly to the outdoorsors...

Страница 11: ...tors of Other Than All Metal Construction The above connectors may be used if acceptable by the authority having jurisdiction The state of Massachusetts requires that a flex ible appliance connector c...

Страница 12: ...rances from the top of the fireplace opening to the ceiling should not be less than 36 inches Mantel Clearances for Built in Installation Figure 9 Do not attach combustible material to the mantel of y...

Страница 13: ...Remove shrink wrap and logs from fireplace 6 Place back base and fireplace in desired location 7 Connect gas line and electrical wiring at this time in accor dance with local codes 8 Place mantel ass...

Страница 14: ...ogs per the Log Placement Instructions See Page 15 14 Install hood See Page 22 9 Attach mantel assembly to studs in the wall through the back brace using two 2 3 drywall screws provided 10 Slide front...

Страница 15: ...This step is optional for A VFD26FP3L10 log sets Place front twig 5 onto 1 log and flat area on 3 log The bottom of the front twig is to be placed behind the grate tang that is second from the left At...

Страница 16: ...burner as well as the main flame should be visually checked as the log set is installed In normal operation at full rate after 10 to 15 minutes the flame appearance should be sets of yellow flames NOT...

Страница 17: ...r assembly if applicable 3 Set REMOTE OFF ON switch to OFF 4 Turn off all electric power to the appliance if applicable 5 Push in gas control knob slightly and turn clockwise to OFF NOTE Knob cannot b...

Страница 18: ...able 3 Set REMOTE OFF ON switch to OFF 4 Turn off all electric power to the appliance if applicable 5 Push in gas control knob slightly and turn clockwise to OFF NOTE Knob cannot be turned from PILOT...

Страница 19: ...liance 1 Set thermostat gas control knob to lowest setting 2 Turn off all electric power to appliance if service is to be performed if applicable Lighting Instructions 7 Turn gas control knob counterc...

Страница 20: ...Troubleshooting page 25 Cleaning and Maintenance Pilot Oxygen Depletion Sensor Pilot When the pilot has a large yellow tip flame clean the Oxygen Depletion Sensor as follows 1 Clean the ODS pilot by...

Страница 21: ...FF is the OFF position PILOT is the PILOT position A VFD26F M P 3 Max 20 000 BTU HR Min 14 000 BTU HR A VFD26FP3L10 Max 10 000 Min N A A VFD26F M P 2 Main Burner Operation The gas control modulates fr...

Страница 22: ...fireplace Attach top frame to fireplace Use two 2 8 x 1 2 Phillips screws for top frame 5 Replace bottom louver 6 Replace top louver 3 PIECE FRAME KIT SIDE TRIM Figure 21 HOOD INSTRUCTIONS 1 Remove up...

Страница 23: ...burner assembly Note Do not let remote control receiver come in contact with burner assembly On circulating vent free firebox install remote control receiver behind bottom louver Refer to remote contr...

Страница 24: ...ELECTRICAL CODE ANSI NFPA 70 LATEST EDITION A factory installed junction box is located on the lower right side of the fireplace Wiring must be fed to the junction box and attached to the receptacle t...

Страница 25: ...ct Replace gas regula tor 7 ODS pilot lights but flame goes out when control knob is released a Control knob not fully pressed in Press in control knob fully b Control knob not pressed in long enough...

Страница 26: ...N S R3435 WIRE ASSEMBLY A VFD26F M P 3LP PART NUMBERS 10 R3623 PILOT ASSEMBLY 11 21590 PILOT BRACKET 14 R9022 BURNER TUBE 16 P182 ORIFICE 19 23493 TUBING ASSEMBLY 21 R3625 VALVE 23 23496 TUBING ASSEM...

Страница 27: ...e 27 PARTS VIEW 5 PIECE LOG Y ASSEMBL MILLIVOLT VALVE Y ASSEMBL THERMOSTATIC VALVE Y ASSEMBL 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 19 20 20 21 21 22 23 23 24 25 26 27 28 29 29 30 31 18 32 33...

Страница 28: ...of fireplace The magnets on the bottom of speed control will sufficiently hold the speed control in place 13 Attach fan control bracket to upper right side of firebox with one 10 x 1 2 hex screw prov...

Страница 29: ...r Kit 110 VOLT AC JUNCTION BOX WHITE SPEED CONTROL FAN SWITCH GROUND BLACK FAN WHITE BLACK SWITCH BRACKET FBBX Wiring Diagram FBBX BLOWER KIT EXTENSION INSTALLATION INSTRUCTIONS cont FBB4 OPTIONAL VAR...

Страница 30: ...e 1 side panel into firebox 5 Align clearance hole on brick panel bracket with screw hole in the left or right interior top of firebox Use two 2 10 x 1 2 screws to attach brick panel bracket to interi...

Страница 31: ...ne the Part Number not the Index Number and the Description of each part from the following appropriate illustration and list Be sure to give all this information Fireplace Number Part Description Fir...

Страница 32: ...23466 4 0509 Page 32 Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62222 PH 618 233 7420 or 800 851 3153 FAX 618 233 7097 or 800 443 8648 info empirecomfort com www empirecomfort com...

Отзывы: