INSTALLATION (CONT'd)
minimum Framing dimensions
BVd34
BVd36
BVP42
"A"
35 3/4"
(908mm)
37 3/4"
(959mm)
37 3/4"
(959mm)
"B"
37 3/8"
(949mm)
39 3/8"
(1,000mm)
43 3/8"
(1,102mm)
"C"
14 3/8"
(378mm)
17 7/8"
(454mm)
17 7/8"
(454mm)
NOTE:
Dimension "C" is the minimum with the fireplace face extending 1/2"
in front of the framing to allow for finishing materials.
Figure 11
Attention:
Add 3-3/4" to “A” dimensions when using a flush
mantel base.
Attention:
If a base or mantel is not used and the appliance
is installed directly on carpeting, tile or other combustible
material other than wood flooring, it shall be installed on a
metal or wood panel extending the full width and depth of
the appliance. The vertical dimension in
Figure 11
must be
adjusted when a metal or wood panel is placed beneath the
appliance.
Finishing (Figure 12)
Finish the walls with the material of your choice. Only
non-combustible materials may be used to cover the black
fireplace front.
WARNING
When finishing the fireplace never obstruct or modify
the air inlet/outlet louvers in any manner. Provide
adequate clearances around air openings into the
combustion chamber.
Caution:
If the joints between the finished wall and the fire
-
place surround (top and sides) are sealed, a 300°F minimum
sealant material must be used. These joints are not required
to be sealed. Only non-combustible material (using 300°F
minimum adhesive if needed), can be applied as facing to
the fireplace surround.
Combustible Surround Installation
Louvered models
Figure 12a
Flush Face models
Figure 12b
Attention: Cold climate installation recommendation:
When installing this unit against a non-insulated
exterior wall, it is recommended that the outer walls
be insulated to conform to applicable insulation
codes.
FINISHED WALL
JOINT BETWEEN FINISHED WALL AND
UNIT SEALED WITH 300° F 149
MATERIAL (SEALANT IS OPTIONAL)
° C
SEALANT
COMBUSTIBLE SURROUND
MANTELSHELF
2 X 4
HEADER
STAND OFF
FRONT TRIM OR NON-COMBUSTIBLE
MATERIAL MAY OVERLAP BLACK PAINTED
FACE (INSTALLATION IS OPTIONAL)