37754-6-1019
Page 16
Termination clearance for buildings with combustible and noncombustible exteriors.
Figure 13
VENT TERMINATION CLEARANCES
Vertical Sidewall Installations
Important!
Minimum clearance between vent pipes and
combustible materials is 3 inches (76 mm) on top, and 1 inch
(25 mm) on bottom and sides.
Important!
When vent termination exits through foundation less
than 20 inches (508 mm) below siding outcrop, the vent pipe
must extend outward so that the horizontal vent termination is
located flush to, or beyond the outcrop siding.
Information on Various Venting Routes and Components
Important:
It is always best to locate the fireplace in such a way
that minimizes the number of offsets and horizontal vent length.
Since it is very important that the venting system maintain its
balance between the combustion air intake and the flue gas
exhaust, certain limitations as to vent configurations apply and
must be strictly adhered to.
The venting graph on page 28 shall be used to determine the
allowable vertical and horizontal vent lengths.
The horizontal vent run refers to the total length of vent pipe from
the flue collar of the fireplace to the face of the outer wall.
Venting termination shall not be recessed into wall or siding.
ATTENTION: Vinyl Soffit, Vinyl Ceiling, Vinyl Overhang
Disclaimer
Clearances are to heat resistant material (i.e. wood, metal).
This does not include vinyl. Empire Comfort Systems Inc.
will not be held responsible for heat damage caused from
terminating under vinyl overhangs, vinyl ceilings or vinyl
ventilated/unventilated soffits.
RECESSED LOCATION
OUTSIDE CORNER
INSIDE CORNER
“A” = COMBUSTIBLE 9” (229mm)
= NONCOMBUSTIBLE 2” (51mm)
“F” = COMBUSTIBLE 6” (152mm)
= NONCOMBUSTIBLE 6” (152mm)
BALCONY
WITH PERPENDICULAR SIDE WALL
BALCONY
WITH NO SIDE WALL
“C” = CLEARANCE FROM CORNER
IN RECESSED LOCATION
COMBUSTIBLE 9” (229mm)
NONCOMBUSTIBLE 2” (51mm)
“D” = MINIMUM WIDTH FOR BACK WALL
OF A RECESSED LOCATION
COMBUSTIBLE 38” (965mm)
NONCOMBUSTIBLE 24” (610mm)
“E” = MAXIMUM DEPTH OF 48” (1219mm)
FOR RECESSED LOCATION
“G” = COMBUSTIBLE 9” (229mm)
= NONCOMBUSTIBLE 2” (51mm)
“H” = COMBUSTIBLE 18” (457mm)
= NONCOMBUSTIBLE 12” (305mm)
“I” = COMBUSTIBLE 12” (457mm)
= NONCOMBUSTIBLE 12” (305mm)