70
GB
GB
9. ANOMALIES AND FUNCTIONING
CODE
DESCRIPTION
LED1
LED2
LED3
POSSIBLE CAUSE
Normal
Outdoor coil temperature sensor
in trouble
a. the outdoor coil sensor connect loose;
b. the outdoor coil temperature sensor is failure;
c. the outdoor control board is failure
Compressor exhaust
temperature sensor in
trouble
a. the compressor exhaust temperature sensor connect loose;
b. the compressor exhaust temperature sensor is failure;
c. the outdoor control board is failure
Communication failure between
the indoor unit and outdoor unit
O
a.
the communication cable connect loose;
b.
the communication cable is failure;
c.
the connection between the filter board and the outdoor control board is
incorrect or loose;
d.
the connection between the filter board and the terminal is incorrect or
loose;
e.
the indoor control board is failure;
f.
the PFC board is failure;
g. the power board is failure;
h.
the outdoor control board is failure.
Current overload protection
O
a.
the fan motor run abnormally
b.
the condensor and evaporator is dirty;
c.
the air inlet and outlet is abnormally
Maximum current protection
O
a.
the outdoor control board is short circuit;
b.
the drive board is short circuit;
c.
the other components is short circuit
Communication trouble between
outdoor unit and driver
a.
the connection wires connect loose
b.
the outdoor board or drive board is failure;
Outdoor EEPROM in trouble
a.
the EEPROM chip is loose;
b.
the EEPROM chip inserted with opposite direction;
c.
the EEPROM chip is failure
Compressor exhaust temperature
too high protection
O
a.
the compressor exhaust temperature sensor is failure;
b.
the refrigerant of the unit is not enough
Outdoor ambient temperature
sensor in trouble
a.
the outdoor ambient temperature sensor connect loose;
b.
the outdoor ambient temperature sensor is failure;
c.
the outdoor control board is failure
Compressor shell temperature
too high protection
×
O
a.
the compressor exhaust temperature sensor connect loose
b.
the refrigerant of the unit is not enough
Anti-freeze protection with
cooling or overload protection
with heating in indoor unit
×
O
O
a.
the indoor coil temperature sensor connect loose;
b.
the indoor coil temperature sensor is failure;
c.
the indoor control board is failure
d.
the refrigerant system is abnormal.
Compressor drive in trouble
O
×
O
a.
the outdoor drive board is failure; b.the compressor is failure
c.
the outdoor control board is failure
Outdoor fan motor locked rotor
protection
O
O
a.
the connection of the outdoor fan motor is loose;
b.
there are something block the outdoor fan;
c.
the fan motor is failure;
d.
the outdoor control board is failure
Outdoor coil anti- overload protec-
tion with cooling
×
×
a.
the refrigerant is too much;
b.
the outdoor fan motor is failure; c.the outdoor fan is broken;
d.
the condensor is dirty;
e.
the air inlet and air outlet of the indoor unit and the outdoor unit is not
normally
IPM module protection
×
O
×
a.
The IPM board is failure;
b.
The outdoor fan is broken;
c.
The outdoor fan motor is failure;
d.
The outdoor fan has been blocked ;
e.
The condenser is dirty;
f.
The outdoor unit has been installed without standard.
PFC protection
O
×
×
a.
the PFC is failure;
b.
the outdoor drive board is failure
Compressor pre-heating process
O
O
it is normal mode in cold weather
Chip in outdoor board in trouble
×
O
a.
Using the wrong drive board;
b.
Using the wrong compressor.
AC voltage higher or lower
protection
O
a.
the supply voltage is higher or lower than normal;
b.
the inner supply voltage of the unit is higher or lower than normal
Outdoor ambient temperature
too low protection
O
O
a.
Outdoor ambient
temperature too low
When the compressor stops working, the LEDs flash every second (1 sec.) To signal the following anomalies:
Содержание X-REVO-0919E
Страница 41: ...41 IT IT 10 SCHEMI ELETTRICI BLU MARRON EEV EEV EEV Schema elettrico TRIAL 24 kBtu X REVO 2419TE...
Страница 46: ...46 IT IT 1 DESCRIZIONE DEI COMPONENTI IT IT...
Страница 48: ......
Страница 87: ...87 GB GB 10 ELECTRIC DIAGRAM BLU MARRON EEV EEV EEV Electric diagram TRIAL 24 kBtu X REVO 2419TE...
Страница 88: ...GB GB 88 EEV EEV EEV EEV Electric diagrams QUADRIAL 36 kBtu X REVO 3619QE 10 ELECTRIC DIAGRAM...
Страница 93: ......
Страница 94: ......
Страница 95: ......