1. DESCRIZIONE DEI COMPONENTI
GB
GB
6. INSTALLATION OF THE INDOOR UNIT
- Loosen the screws and insert the cable ends completely in the terminal
block, after this tighten the screws.
70 mm
10 mm
10 mm
50 mm
- Pull lightly on the cable to make sure that the cables have been inserted
and secured properly.
- After connecting the cables, never forget to tighten them to the cable
gland.
Power is brought to the outdoor unit.
Alimentation
Magnetothermic
differential/switch
Please use an exclusive source of electrical power for the air conditioner
only, with a dedicated magnetothermic differential/switch
.
Power supplies cables and connecting
- All the feed and connection cables must be approved in conformance
with IEC standards, and for lengths up to 15m., must have a section
not less than:
- Use a multi-pole cable of type H07RN-F
- For lengths over 15m, use the next higher standard section, always
checking that in every case the voltage drop during operation is lower
than 3% of the supply voltage.
- If a cable is damaged it must be replaced by service personnel or by
qualified personnel.
- All cables must have the certificate of conformity.
800
514
55
4
60
85
.5
34
0
12
.0
31
1
815
36
5
333
70
62
10
6
20
R20
R6
61.6
Terminal
Model
Power supply
cable
Connection
cable
X-REVO-0919E
3x 2.5 mm
2
5x 1.5 mm
2
X-REVO-1219E
X-REVO-1819E
X-REVO-2419E
X-REVO-0919EX
3x 2.5 mm
2
4x1.5 mm
2
X-REVO-1219EX
X-REVO-1819EX
X-REVO-1419DE
3x 2.5 mm
2
4x1.5 mm
2
X-REVO-1819DE
X-REVO-2419TE
X-REVO-3619QE
Connect earthing wire.
Earthing wire should not be con- nected to the gas pipe,
water pipe, lightning rod or phone line, incorrect earthing
may cause shock.
Use the correct power supply in accordance with the
nameplate requirements. Otherwise you run the risk of
causing serious damage or the occurrence of a fire.
6.4 Electrical supply
Electrical connections have to be done by qualified personnel, by observing
the current rules in the place where the air conditioner unit has to be
installed. Electrical connection has to be preceded by a careful control
about compatibility between the electrical supply line and the features of
the unit you want to connect.
In the electrical supply line of the unit it is mandatory to foresee a bipolar
switch ( a differential one) with a contact separation of at least 3mm in
every pole.
Attention!
Before doing any work on the units, make sure that the main electrical
supply has been disconnected.
Before interrupting the power supply by means of the switch, turn the air
conditioner off with the remote cont
Connection to the terminal block
Remove the terminal block cover.
Содержание X-REVO-0919E
Страница 41: ...41 IT IT 10 SCHEMI ELETTRICI BLU MARRON EEV EEV EEV Schema elettrico TRIAL 24 kBtu X REVO 2419TE...
Страница 46: ...46 IT IT 1 DESCRIZIONE DEI COMPONENTI IT IT...
Страница 48: ......
Страница 87: ...87 GB GB 10 ELECTRIC DIAGRAM BLU MARRON EEV EEV EEV Electric diagram TRIAL 24 kBtu X REVO 2419TE...
Страница 88: ...GB GB 88 EEV EEV EEV EEV Electric diagrams QUADRIAL 36 kBtu X REVO 3619QE 10 ELECTRIC DIAGRAM...
Страница 93: ......
Страница 94: ......
Страница 95: ......