6.7.2. Page-2 Parameters
SAMPLE TIME
PID output calculation period for selected channel is can be adjusted according to this parameter.
SET MINIMUM
PID minimum set value for selected channel is can be adjusted according to this parameter.
Default
SAMPLE TIME
PID Sample Time For Channel-X
60.0
1.4
1.4
SET MINIMUM
PID Minimum Set Value For Channel-X
1700.0
-100.0
0.0
Parameter
Explanation
SET MAXIMUM
PID Maximum Set Value For Channel-X
1700.0
-100.0
400.0
TUNE (1.A/2.S)
PID Tune Selection For Channel-X
SOFT START
PID Ouput Power On Ramp Time For Channel-X
600
0
0
ALARM TYPE
Alarm Type Selection
0
-
-
sec.
0
2
0
0
3
min.
Min.
Max.
Unit
{
SET MAXIMUM
PID maximum Set value for selected channel is can be adjusted according to this parameter.
TUNE (1.A / 2.S)
Tune selection for selected channel is can be adjusted according to this parameter.
After tune operation is finished without any problem, device saves new PID parameters to memory and
the tune parameter value is
to 0 automatically. If parameter value,
0 = Tune off
1 = Auto tune (Limit Cycle Tuning) operation
2 = Self tune (Step Response Tuning) operation
being changed
SOFT START
PID output for selected channel is reaches to the %output value that is measured when power first applied
to the device at the end of the this parameter time. If parameter value is adjusted to 0 value or If there is a
sensor break failure, then Soft-Start operation is canceled.
ALARM TYPE
Alarm type for selected channel is can be adjusted according to this parameter. If parameter value,
0 = Alarm Off,
1 = Low Alarm,
2 = High Alarm,
3 = Band Alarm is selected.
O
C
O
C
Techncian Parameter
Page Number
Channel Number
Channel
Selection Buttons
Channel number is can be seen upper left side of the display and can be selected by pressing
the channel selection buttons (1, 2, 3 or 4).
ii
If no operation is performed for 20 seconds in technician parameters section, device turns to
main operation screen automatically.
ii