EMKO EAOM-19 Скачать руководство пользователя страница 25

Prm. No.

Definition of Parameter

Unit

Lower / Upper Limit Default

P00

Mains voltage connection level

VAC

60 - 600

320

P01

Mains voltage disconnection level

VAC

60 - 600

300

P02

Mains voltage upper limit

VAC

60 - 600

440

P03

Alternator voltage lower limit

VAC

60 - 600

320

P04

Alternator voltage upper limit

VAC

60 - 600

440

P51

Hz.

30.0 - 75.0

43.0

P06

Number

1 -10

3

P09

Mains transition delay

Minute

0 - 30

3

P10

Single / Three phase selection

Select

1 PH / 3 PH

3 PH

P11

Battery voltage lower limit

VDC

7.2 - 24.0

8.0

P13

Stop / Fuel solenoid selection

StoP / FuEL

FuEL

P14

Stop magnet energising time

0 - 99

20

P16

Starting attempt duration

5 - 99

5

P18

Speed limit for crank disconnection

20.0 - 45.0

40.0

P19

Control on delay

0 - 99

10

P20

Alternator voltage fault control delay

0.0 - 10.0

5.0

P21

Speed fault control delay

Second

5.0

P24

Horn output selection;
0= Alarm output
1= Choke output
2= Simulate fuel solenoid output

0 - 2

0

P25

Choke time

0.8

P15.0
P15.1
P15.2
P15.3

P07

P08

P12

P15

P17

P22

P23

Speed lower limit

Number of starting attempts

Engine cooling time

Horn duration

Mains-Generator or Generator-Mains
change over delay

Configurable failure input-2 (Pin10)
The same as P22

Configurable failure input-1 (Pin9)

Alternator voltage limit for crank
disconnection

Engine started signal

Charge generator
Speed
Alternator voltage
Oil pressure

0

1

2
3
4
5

6

LED flashes and horn sounds.
It is unlatched.
LED flashes and horn sounds
and then stays on until reset.
As "1" plus engine stops.
As "0" but only while engine running.
As "1" but only while engine running.
As "4" plus engine stops if running.
As "4" plus generator contactor
de-energised , if engine running.

Minute

Second

Second

Select

Second

Select

Second

VAC

Hz.

Second

Second

Number

Number

Number

Second

0 - 999

0 - 99

0 = disables cooling process

0.1 - 25.0

no / YES

40 - 360

0 - 8

0 - 8

0 = continuous

no / YES
no / YES
no / YES

0.0 - 10.0

0.0 - 30.0

3

60

1.0

No

YES

No

300

0

0

P26

Generator start delay

0 - 9999

0

P27
P28

Oil sensor selection
Engine Running Time

0
0

Second

Number

Hour

0 - 1

0 - 9999

PoPS

Operator password (P00 to P09, and PoPS)

0 - 9999

0

PtPS

Technician password (P00 to PtPS)

0

Number
Number

0 - 9999

P52

Hz.

30.0 - 75.0

53.0

Speed upper limit

P191

Oil failure control delay

0.0 - 25.0

0.0

Second

7
8

Remote inhibit
Remote start

4.4 Parameter List

25

No

Содержание EAOM-19

Страница 1: ...eration Two user configurable inputs Provides charge generator excitation current Speed sensing from alternator frequency Fully programmable Automatic Transfer Unit For Diesel Generators Led status an...

Страница 2: ...terface of the unit how to access to the parameters description of parameters are explained CONTENTS Installation Operation and Parameters Also in these sections there are warnings to prevent serious...

Страница 3: ...R LIMIT P51 AND UPPER LIMIT P52 FAULT CONTROL DELAY P21 4 5 4 ENGINE COOLING TIME P07 4 5 5 MAINS TRANSITION DELAY P09 4 5 6 BATTERY VOLTAGE LOWER LIMIT P11 4 5 7 STOP FUEL SOLENOID SELECTION P13 4 5...

Страница 4: ...RS 6 1 ALTERNATE DISPLAY DESCRIPTION 6 2 FAILURE INDICATORS DESCRIPTION 6 3 MODE TRANSITION 6 4 MANUAL START 6 5 MANUAL STOP 6 6 AUTO OPERATION 6 7 TEST OPERATION LIST 1 4 Page 40 Page 43 Page 39 Page...

Страница 5: ...l compliance of the products with the following European standards 2014 35 EU The Low Voltage Directive 2014 30 EU The Electromagnetic Compatibility Directive EN 61000 6 4 2007 EMC Generic Emission St...

Страница 6: ...rator start and load transfer on mains failure via external mains and generator contactors Alarm horn A four digit seven segment display provides extensive monitoring of unit and generator parameters...

Страница 7: ...two years The warranty period starts from the delivery date This warranty is in force if duty and responsibilities which are determined in warranty document and instruction manual performs by the cust...

Страница 8: ...he unit against damage and to prevent failure Keep the power off until all of the wiring is completed so that electric shock and trouble with the unit can be prevented Never attempt to disassemble mod...

Страница 9: ...p UV Hz OFF AUTO TEST VL31 L3N VL23 L2N VL12 L1N PROG TEST RESET G G EAOM 19 MAN START MAN STOP RPM VV FAILED TO START HIGH TEMPERATURE LOW OIL PRESSURE OVER SPEED FAILURE VOLTAGE FAILURE CHARGING FAI...

Страница 10: ...10 2 3 Panel Cut Out 97 mm 3 82 inch min 97 mm 3 82 inch min 69mm 2 72 inch 69mm 2 72 inch...

Страница 11: ...the device through the cut out If the mounting clamps are on the unit put out them before inserting the unit to the panel During installation into a metal panel care should be taken to avoid injury fr...

Страница 12: ...move the device from panel power off the device and the related system 1 Loosen screws 2 Lift the locking tabs located on both the right and left hand sides and pull the fixing clamp from the device w...

Страница 13: ...ed specially should work on this equipment This equipment contains internal circuits with voltage dangerous to human life There is severe danger for human life in the case of unauthorized intervention...

Страница 14: ...E 4 FUSE 3 L L L N N N 13 18 17 16 19 CHARGE GEN D W L B CHARGE GENERATOR FUSE 2 40 A 40 A FUSE 1 BATTERY BAT BAT BAT STARTER BATTERY NEGATIVE MUST BE GROUNDED START RELAY SOLENOID RELAY LOW OIL PRESS...

Страница 15: ...1 6 1 2 1 3 2 2 EAOM 19 Three Phase Connections Schematic For TN C AC Power Systems Connect the unit as shown in the appropriate diagram Section 3 2 1 or 3 2 2 Ensure the battery supply is of the corr...

Страница 16: ...5 16 17 18 19 MAINS N MAINS L1 MAINS L2 MAINS L3 GEN N GEN L1 MAINS RELAY GEN RELAY 5 A 5 A 1 2 3 4 5 6 7 8 9 10 11 BATTERY BATTERY BATTERY START SOLENOID HORN OIL PRESS HIGH TEMP CONF INPUT 1 CONF IN...

Страница 17: ...l pressure switch 7 1 0 Switch to 0 Volt Input from temperature switch 8 1 0 Switch to 0 Volt Configurable failure input 1 9 1 0 Switch to 0 Volt Configurable failure input 2 10 1 0 Switch to 0 Volt I...

Страница 18: ...to BAT if not used 17 Input from generator L1 phase Unit can be programmed to use frequency of alternator output to detect when engine has started 7 Input from Oil Pressure switch The oil pressure swi...

Страница 19: ...is in the Programming Mode The LED is lit when the unit is in the Programming Mode lit lights off when the unit is in the other modes The LED shows the unit is in OFF position It s colour is red The L...

Страница 20: ...used for Programming the Unit and features explained in section 6 25 Failure Indicators Detailed information about this subject is explained in section 6 2 The button used for starting the engine whe...

Страница 21: ...while the unit is in mode Press the OFF 17 button If the engine is running it will stop and the LED 6 lights on Then proceed as follows OFF Not2 User can access to parameters to and only P00 P09 P28 O...

Страница 22: ...ter by pressing Enter button Change the parameter value with increment and decrement buttons Press Enter button to confirm the changed value or access the following parameter Press Enter button to con...

Страница 23: ...d This selection is done with increment and decrement buttons Press the Enter button Press the increment button Enter password with increment and decrement buttons Not1 If Enter button is pressed and...

Страница 24: ...ERIOD OF 2 MINUTES THE UNIT WILL RETURN TO THE NORMAL OPERATION SCREEN i Operation Screen User can access to the following parameter by pressing Enter button Change the parameter value with increment...

Страница 25: ...cooling time Horn duration Mains Generator or Generator Mains change over delay Configurable failure input 2 Pin10 The same as P22 Configurable failure input 1 Pin9 Alternator voltage limit for crank...

Страница 26: ...lls below the Disconnection Level Conversely if the mains voltage is low and the load is running on the generator the unit will not restore the mains supply to the load until the mains voltage reaches...

Страница 27: ...21 This is the time the generator is to run off load once the load transfer signal has ceased This gives the engine time to cool down before shutdown Parameter P07 defines the duration of this cooling...

Страница 28: ...es that the engine has started 0 1 Speed Limit for Crank Disconnection 2 Alternator Voltage Limit for Crank Disconnection 3 See Section 4 5 10 4 5 8 Stop Magnet Energised Time P14 4 5 9 Engine Started...

Страница 29: ...if this input is active while the generator was starting the module will stop the Generator 8 In AUTO mode if one of the configurable inputs are selected as 8 Remote Start the unit doesn t perform the...

Страница 30: ...i 4 5 17 Engine Running Time P28 The user can change the engine running time value by using this parameter i To prevent to changing unit program parameters by unauthorised personel don t allow to the...

Страница 31: ...the LED flashes and the LED 3 lights off 9 Check the unit will change to the STOP position and the LED 8 lights on 10 Restore the engine to operational state reconnect the fuel solenoid 11 Press the...

Страница 32: ...s and the generator after a further delay shuts down 1 Check that the mains is connected to the unit 2 Press the TEST 11 button At this moment the LED 1 will light on 3 Check that the generator starts...

Страница 33: ...age L1 L2 prefix L GEN V Generator voltage GEN FRG Generator frequency Hz BATTERY Battery voltage The LED will flash if the unit detects an engine stopping error When the DISPLAY MODE 23 button is pre...

Страница 34: ...ALARM VL23 VL31 F Battery Voltage VL12 GEN V GEN FRQ BATTERY ALARM VL23 VL31 F Enginen Working Time VL12 GEN V GEN FRQ BATTERY ALARM VL23 VL31 F Mains Voltage L1 N Press the display mode button again...

Страница 35: ...r Frequency Hz VL12 GEN V GEN FRQ BATTERY ALARM VL23 VL31 F Battery Voltage VL12 GEN V GEN FRQ BATTERY ALARM VL23 VL31 F Engine Working Time Press the display mode button Press the display mode button...

Страница 36: ...roper level If the contact will not open the engine is running and it continues the LED flashes and the Horn is sounded and engine shuts down without any cool down period The unit decides to the Over...

Страница 37: ...EAOM 19 measures battery voltage at the EAOM 19 terminals Depending on the size and length of the cable to the battery this may be somewhat less than the voltage as measured at the battery Configurab...

Страница 38: ...hould go off 6 5 Manual Stop The LED 8 is lit and engine is stopped when the MAN ENGINE STOP 20 button is pressed When the MAN ENGINE STOP 20 button is pressed while the load connected to the generato...

Страница 39: ...ure switch and wiring Check that oil pressure switch is of the normally closed type opens on oil pressure Check engine temperature and cooling systems Check switch and wiring Check that temperature sw...

Страница 40: ...midity 25 C to 70 C 40 C to 85 C 90 max non condensing II Appliances portable equipment II Normal office or workplace non conductive pollution Continuous 8 to 32 V max operating current is 240 mA Batt...

Страница 41: ...rature LED Low oil pressure LED Over speed LED Generator voltage failure LED Charge generator failure LED Battery voltage failure LED Configurable input 1 LED Configurable input 2 LED TEST mode LED PR...

Страница 42: ...ONTROLLER ANALOG TO DIGITAL CONVERTOR COUNTER TIMER MAINS GENERATOR VOLTAGE SENSING CONDITIONING FREQUENCY SENSING FROM GENERATOR VOLTAGE LED DISPLAYS INDICATORS BATTERY MAINS L1 GEN N GEN L1 MAINS L2...

Страница 43: ...Generator Mains change over delay P18 Speed limit for crank disconnection P19 Control on delay P20 Alternator voltage fault control delay P21 Speed fault control delay P22 P23 Spare input 2 Pin10 Spa...

Отзывы: