background image

The Right Fit For Comfort

www.retroaire.com

10

COOLING OPERATION

After connecting the thermostat to the unit place the 

system switch in cool mode. Adjust the set-point tempera-

ture below the room temperature. The compressor and fan 

motors will start and cooling will begin. Place the set-point 

temperature above the room temperature. The compressor 

and condenser fan will stop and the indoor fan will remain 

on for an additional sixty seconds.

IMPORTANT: 

The start of the compressor will not take 

place until the anti-short/random start time period has 

elapsed.

ELECTRIC HEAT OPERATION

Place  the  thermostat  system  switch  in  heat  mode. 

Adjust the set-point temperature above the room tempera-

ture. The electric heat will energize along with the indoor 

fan motor. Heating will continue so long as the set-point 

remains above room temperature. Next place the set-point 

temperature below room temperature. The Electric heater 

will switch off and the indoor fan will remain on for an ad-

ditional sixty seconds.

HYDRONIC HEAT OPERATION 

(Optional)

An optional hydronic heat package may be selected 

in lieu of electric heat. Heating operation is essentially the 

same as that of units with electric heat. With the thermostat 

system switch set to heat and the set-point temperature 

above room temperature, the hydronic valve will open al-

lowing water to flow through the coil. The indoor fan will 

also switch on and warm air will flow from the unit. Heating 

will continue so long as the set-point remains above room 

temperature. Place the set-point temperature below room 

temperature. The hydronic valve will close and indoor fan 

will switch off after the sixty-second purge time has elapsed. 

The hydronic valve is a 24Vac normally open valve. Should 

power be lost to the unit, the valve will default to the open 

position.

HYDRONIC COIL FREEZE PROTECTION

The hydronic package is equipped with a thermostat 

(freeze-stat) that is designed to prevent the hydronic coil 

from freezing. At 35°F the thermostat will switch open the 

hot water valve to prevent the coil from freezing. At 50°F 

the thermostat will reset. If the room thermostat is not call-

ing for heat, the valve will close. The freeze stat is factory 

pre-set and should never need adjusting. However, if the 

adjustment screw is tampered with it will be necessary to 

reset the freeze-stat. To set the freeze stat you will need a 

medium flat bladed screwdriver. Turn the adjusting screw 

counter-clockwise until it stops. Then slowly turn the ad-

justing screw clockwise approximatly 1/8 turn until a click 

is detected. The freeze stat is now set.  

CHOOSING A THERMOSTAT

Enviromaster International offers a thermostat that is 

compatible  with  the  VPAC/VPHP. This  is  a  single  stage 

cool/heat, mercury bulb thermostat that can be used in all 

Retroaire™ cooling, heating or heat pump applications. The 

thermostat has an adjustable set-point range of between 

55°F and 95°F. There are two independent, adjustable stops 

that can limit the heating or cooling range of the thermostat. 

A non-mercury, electronic thermostat is available if needed. 

please contact the factory for more information.

SELECTING A COMPATIBLE THERMOSTAT

When selecting a thermostat other than those offered 

by Enviromaster International, it is important to choose a 

single stage heat/cool, 24V thermostat. For models 09-17, 

do not select a thermostat that requires connection to a 

“C” terminal since these units do not have provisions for 

connecting to a “C” terminal. Only models 19 and 24 have 

provisions  for  connecting  a  “C”  terminal  to  the  unit.  If  a 

thermostat without a “C” terminal is used in a models 19 or 

24, then it is important to insulate the unused brown “C” low 

volt wire to prevent it from shorting at the thermostat.  

COOLING ONLY WITH ELECTRIC OR 

HYDRONIC HEAT 

(VPAC Only)

Select a thermostat that is compatible with a cooling 

- electric heat system. The thermostat should have “R”, “Y”, 

“W” and “G” terminals.

HEAT PUMP WITH ELECTRIC HEAT

(VPHP Only)

Select a thermostat that is compatible with a cooling 

- single stage heat - heat pump system. The thermostat 

should have “R”, “Y”, “O” and “G” terminals. Retroaire™ 

units are single stage heating only. The electric heat and 

heat pump will not operate simultaneously.

FAN OPERATION

Some thermostats are equipped with an auto/on fan 

switch. When this switch is placed in the on position the 

indoor fan will run continuous. When the switch is in the 

auto position the indoor fan will cycle with the call for heat-

ing or cooling. 

FAN PURGE 

(Auto Mode Only)

After the room thermostat has been satisfied, the purge 

feature allows the indoor fan to remain on for an additional 

60 seconds. This increases efficiency by pulling the remain-

ing energy from the unit.

SEQUENCE OF OPERATION

Содержание VPAC

Страница 1: ...00 Certified Company VPAC VPHP SINGLE PACKAGE VERTICAL AIR CONDITIONER HEAT PUMP FOR NEW CONSTRUCTION ONLY Straight Cool Heat Pump Nominal Capacities 9 000 12 000 15 000 17 000 19 000 24 000 Btuh VPAC VPHP Enviromaster International LLC 5780 Success Dr Rome NY 13440 Email info retroaire com ...

Страница 2: ... stated on the rating plate Have proper over current protection i e time delay fuse HACR Breaker as listed on the Rating Plate Failure to follow these instructions can result in a fire explosion or electrical shock causing property damage personal injury or death This manual is intended as an aid to qualified service personnel for proper installation operation and maintenance of the VPAC VPHP Packag...

Страница 3: ...allation Instructions 5 9 Sequence of Operation 10 12 Cleaning and Maintenance 12 Troubleshooting 12 Specifications and Dimensions 13 14 Warranty 15 INSTALLER RESPONSIBILITIES This manual has been prepared to acquaint you with the installation operation and maintenance of this VPAC VPHP PTAC and to provide important safety information in these areas We urge you to read all of the instructions thoro...

Страница 4: ...ess panel standard white or custom colors available PRODUCT DESCRIPTION The VPAC VPHP Single Package Vertical Air Condi tioner SPVAC and Heat Pump SPVHP creates new op tions in layout and space utilization The VPAC VPHP offers low cost operation and quiet comfortable air distribution especially when used in multi room suites apartments healthcare facilities and homes Framed into a concealed closet...

Страница 5: ... position necessary for installation Figure 1 INSTALLATION FOR NEW CONSTRUCTION EXPLODED VIEW OF TYPICAL INSTALLATION Rear View of Door Filter Slide On Back Access Panel Optional Evaporator Coil Manual Fresh Air Door External line cord min 48 located at bottom right for front and right hand controls or bottom left for left hand controls Minimum overall wall thickness must be at least 5 for straigh...

Страница 6: ...VPHP WALL SLEEVE ASSEMBLY CROSS SECTION OF TYPICAL WALL Wall Sleeve Outdoor Louver Interior Wall Lag Holes 4 On Each Side Wall Sleeve Depth Overall Wall Thickness 1 25 Louver Depth 1 2 x 1 2 Foam Gasket Overall Wall Thickness DETERMINING WALL SLEEVE DEPTH Figure 2 Weather Angle Position INSULATION WEATHER ANGLES Back Panel Mounting Holes Install supplied 1 2 x 1 2 foam insulation along top and sid...

Страница 7: ...ot equipped with a drain stub a minimal amount of condensate will during the heating cycle run out the wall sleeve onto the drip edge and away from the building when the drain pan valve opens During the cooling cycle condensate will be funneled to an area near the condensing fan and picked up by the slinger ring The condensate will be slung against the hot condenser coil to evaporate Any excess co...

Страница 8: ...t or front aligned matching the control section alignment of the unit on which it is to be installed 1 The coil package is centered on top of the VPAC VPHP chassis Make sure it is centered over the fan discharge and that the piping package is in the correct position 2 Find the two Z brackets used to clamp the hydronic enclosure to the chassis top Mount these brackets to the chassis top using the h...

Страница 9: ...se as a temporary heating cooling source during construction MANUAL FRESH AIR DAMPER The fresh air manual damper allows the user to move fresh air into the space to be conditioned The damper handle is located below the evaporator coil on the service panel RETURN AIR ACCESS PANEL NOTE Available with solid doors if separate intake is used B C A Frame Assembly Lag Holes 1 5 Rear View Of Door G NOTE A...

Страница 10: ...e adjustment screw is tampered with it will be necessary to reset the freeze stat To set the freeze stat you will need a medium flat bladed screwdriver Turn the adjusting screw counter clockwise until it stops Then slowly turn the ad justing screw clockwise approximatly 1 8 turn until a click is detected The freeze stat is now set CHOOSING A THERMOSTAT Enviromaster International offers a thermostat...

Страница 11: ...valve that will open when outdoor temperatures fall below 50 F This keeps the base pan free of condensate water where it may otherwise freeze during colder outdoor temperatures As part of its normal operation the unit will produce condensate and collect it in the base pan of the unit There it will be picked up by the condenser fan slinger ring and deposited onto the condenser coil During the cooli...

Страница 12: ...lies Some units may require a drop of light oil to motors and or bearing assemblies look for oil cups Check setscrews and motor mounting hardware making sure these are tight 6 Centrifugal fan blades and blower cage assemblies must be clean to operate efficiently Brush and or vacuum as necessary 7 Inspect both indoor and outdoor coils Use a fin comb to straighten out any damaged fins These coils must...

Страница 13: ...5 60 1 0 70 0 125 4 25 26 0 67 0 08 5 62 240 6 7 15 H WIRE 15 208 230 60 1 0 72 0 125 6 40 35 0 80 0 07 7 92 197 9 6 15 6 15P 265 60 1 0 70 0 125 5 40 32 0 67 0 08 6 77 240 8 2 15 H WIRE 17 208 230 60 1 1 20 0 250 7 40 48 1 00 0 15 9 60 197 11 5 15 6 15P 265 60 1 1 30 0 250 6 50 44 0 67 0 08 8 50 240 10 1 15 H WIRE 19 208 230 60 1 1 00 0 250 7 40 48 1 00 0 15 9 40 197 11 3 15 6 15P 24 208 230 60 1...

Страница 14: ... 15 7 17 2 21 2 25 6 30P 230 4000 13700 17 4 18 9 23 2 25 6 30P 265 5310 18200 20 0 21 5 26 5 30 H WIRE 5 208 4089 14000 19 7 21 2 26 1 30 6 30P 230 5000 17100 21 7 23 2 28 7 30 6 30P 7 208 5725 19600 27 5 29 0 35 9 40 H WIRE 230 7000 23900 30 4 31 9 39 5 40 H WIRE 265 6635 22700 25 0 26 5 32 8 35 H WIRE 277 7250 24800 26 2 27 7 34 2 35 H WIRE 10 208 8178 28000 39 3 40 8 50 6 60 H WIRE 230 10000 3...

Страница 15: ...nditions blown fuses open circuit breakers or other damages due to the inadequacy or interruption of electrical service Damage or repairs needed as a consequence of any misapplication abuse improper servicing unauthorized alteration or improper operation Damage as a result of floods winds fires lightening accidents corrosive atmosphere or other conditions beyond the control of EMI Parts not supplied...

Страница 16: ......

Отзывы: