4

Liquid

Suction

18

3/8"

5/8"

40

24

3/8"

3/4"

45

30

3/8"

3/4"

68

18

3/8"

5/8"

43

24

3/8"

3/4"

48.5

24

3/8"

7/8"

57.5

30

3/8"

7/8"

59.0

VCH

HCA

HCH

Note: 

Add .5oz /ft. for interconnect refrigerant piping to the ab ove 

charge amounts

PIPING SPECIFICATIONS & CHARGE

Unit

Model

Ref. Line Sizes

Ref. Charge 

Oz. R-22

5. Use of a liquid line filter-drier is recommended. Filter-

driers may be supplied by EMI or be field supplied.
Size the filter-drier properly and follow manufacturer’s
installation recommendations. Be sure to adjust
refrigerant charge as required when adding a filter-
drier.

6. Evacuate and charge the unit.

NOTE:

 

All panels must be in place when operating

the unit for test or charging.

Condensing units are factory charged and shipped with
the service valves front-seated. Ports are provided on the
service valves for evacuation and charge. Use a mani-
fold/gauge set. Test the tubing for leaks. Do not release
the refrigerant in the condensing unit until leak check and
evacuation are completed. Be certain there is no pres-
sure in the system when repairing a leak. Using a suitable
vacuum pump, evacuate the tubing and indoor section to
a minimum of 500 microns (service valves remain front-
seated). Release the refrigerant from the condensing unit
by back-seating the service valves. Always replace and
tighten the caps. The system charge will require adjust-
ments for tubing run, driers, and evaporator coils. EMI rec-
ommends charging by “Superheat.”

START-UP

1. Start the unit and adjust the refrigerant charge by the

“Superheat” or “Temperature vs. Pressure”
method. Data chart is available on page 5

. Avoid

overcharging.

2 Replace any panels and covers removed during

installation and start-up. Thoroughly test the system
for proper operation in cooling. Check the indoor unit
and thermostat for proper operation.

3. Do a final visual inspection. Check for weather

tightness. Repair/correct any deficiencies.

TROUBLESHOOTING

Check to see if the unit has power and if the thermostat is
satisfied. If the unit has power and the thermostat is not
satisfied, refer to the wiring diagram and check control
components for continuity. To obtain further technical
service for this unit, please contact the factory.

Содержание VCH Series

Страница 1: ...Rev 2 1 06 04 Nominal Circuits VCH 18 000 24 000 30 000 Btuh HCA 18 000 24 000 Btuh HCH 24 000 30 000 Btuh Enviromaster International LLC 5780 Success Dr Rome NY 13440 Email emi enviromaster com VCH...

Страница 2: ...not fail to properly ground this unit Before servicing the EMI AmericaSeries Vertical or Horizontal In Wall Condensing Unit be sure to disconnect the electrical supply to the unit Do not use the EMI A...

Страница 3: ...tions use high temperature brazing alloys only and protect the valves from overheating If using flux protect the unit from contamination PRE INSTALLATION 1 Unpack the unit and inspect for damage Make...

Страница 4: ...ation are completed Be certain there is no pres sure in the system when repairing a leak Using a suitable vacuum pump evacuate the tubing and indoor section to a minimum of 500 microns service valves...

Страница 5: ...nts The chart below gives superheat values at various outdoor temperatures Allow at least 5 minutes running time between charge adjustments for the unit to stabilize Example Suction pressure is 65 psi...

Страница 6: ...8 230 60 1 1 9 0 25 7 4 48 9 3 197 11 2 15 24 208 230 60 1 1 9 0 25 9 6 60 11 5 197 13 9 20 30 208 230 60 1 1 9 0 25 11 8 73 13 7 197 16 7 25 18 208 230 60 1 0 72 0 125 7 4 48 8 12 197 10 0 15 24 208...

Страница 7: ...s Failure to start due to voltage conditions blown fuses open circuit breakers or other dam ages due to the inadequacy or interruption of electrical service Damage or repairs needed as a consequence o...

Страница 8: ......

Отзывы: