The use of the superheat method is highly recommended
for field charging or checking the existing freon charge in
a system. Because each installation is different in terms of
indoor air flow, refrigerant line length, duct variations, etc..,
the factory charge may not be correct for every application.
To assure the best performance from the air-conditioner,
the freon charge should be checked and adjusted, if need
be, on each installation.

For proper superheat readings, a standard low-side
refrigerant gauge and an accurate thermometer is needed.

FIELD CHARGING

A mercury or stem-type thermometer is not adequate for
suction-line temperatures. We recommend electric
thermocouple thermometers (available at most
refrigeration wholesalers); however an accurate remote-
bulb thermometer can be used. When measuring the line
temperature, be sure the thermometer is well installed to
assure accurate measurements. The chart below gives
superheat values at various outdoor temperatures. Allow
at least 5 minutes running time between charge
adjustments for the unit to stabilize.

Example:

Suction pressure is 65 psi. which equals 38

°

 F on 

The

R-22  Scale of the Low-Side Gauge.

Suction line temperature taken at the unit is 70

°

 F. 70

°

 F

minus 38

°

 F equals 32

°

 F superheat.

Outdoor temperature is 90

° 

F; indoor temperature is 80

°

 F.

Intersection of the indoor-temperature and outdoor-
temperature lines occur on the 12

°

 F superheat line.

Add charge to obtain 12

°

 F superheat.

Instructions:

1. Measure suction pressure and determine evaporator-
refrigerant temperature on R-22 scale of low-side gauge.

2. Measure suction-line temperature on suction line of the
unit.

3. Measure outdoor and indoor temperatures.

4. Determine from the table what the superheat should be
for the indoor and outdoor temperatures. (Example
indicates 12

°

 F superheat.)

5. Adjust charge if needed. Be sure unit is running at
stabilized condition.

Note: If operating superheat is more than 5

°

 F above the chart value, add refrigerant. If below the chart

value remove refrigerant. If below the limit line, remove refrigerant.

Содержание VCH Series

Страница 1: ...Rev 2 1 06 04 Nominal Circuits VCH 18 000 24 000 30 000 Btuh HCA 18 000 24 000 Btuh HCH 24 000 30 000 Btuh Enviromaster International LLC 5780 Success Dr Rome NY 13440 Email emi enviromaster com VCH...

Страница 2: ...not fail to properly ground this unit Before servicing the EMI AmericaSeries Vertical or Horizontal In Wall Condensing Unit be sure to disconnect the electrical supply to the unit Do not use the EMI A...

Страница 3: ...tions use high temperature brazing alloys only and protect the valves from overheating If using flux protect the unit from contamination PRE INSTALLATION 1 Unpack the unit and inspect for damage Make...

Страница 4: ...ation are completed Be certain there is no pres sure in the system when repairing a leak Using a suitable vacuum pump evacuate the tubing and indoor section to a minimum of 500 microns service valves...

Страница 5: ...nts The chart below gives superheat values at various outdoor temperatures Allow at least 5 minutes running time between charge adjustments for the unit to stabilize Example Suction pressure is 65 psi...

Страница 6: ...8 230 60 1 1 9 0 25 7 4 48 9 3 197 11 2 15 24 208 230 60 1 1 9 0 25 9 6 60 11 5 197 13 9 20 30 208 230 60 1 1 9 0 25 11 8 73 13 7 197 16 7 25 18 208 230 60 1 0 72 0 125 7 4 48 8 12 197 10 0 15 24 208...

Страница 7: ...s Failure to start due to voltage conditions blown fuses open circuit breakers or other dam ages due to the inadequacy or interruption of electrical service Damage or repairs needed as a consequence o...

Страница 8: ......

Отзывы: