background image

29

PN 20009722 REV F, [08/01/2020]

CAW INFRARED CONTROL SYSTEM - OPERATION

Handheld Remote Operation

• 

When power is first applied to control or after power 

outage, there is three (3) minute delay before cooling or 

heating begins. Protects unit from short cycling due to 

loss of power.

• 

Configure controller with remote DIP switch 4 to NO 

to operate using IR hand held remote controller. DIP 

switch YES to operate using wall mounted remote 

thermostat. See Table 3, Page 24.

• Point IR hand held remote toward cassette’s infrared 

receiver window when entering commands. Cassette 

responds with beep indicating it has successfully received 

transmitted information. See Figure 36, Page 24.

Synchronization

IR hand held remote and cassette’s main control board 

mode synchronization are not in same mode may happen 

if commands are entered into remote when not pointed at 

cassette.
To re-synchronize:

• Enter any command into IR hand held remote while 

pointing at cassette’s infrared receiver window.

• Alternatively, hold POWER/SEND button two seconds. All 

optional IR hand held remote’s settings are transmitted 

to cassette. Cassette responds with beep, indicating it 

received transmitted information.

Temperature Indication

• Room temperature displayed on IR hand held remote is 

temperature at IR hand held remote.

• Microprocessor control located in cassette does not read 

IR hand held remote’s temperature — it uses sensor 

located in return air of cassette.

• Warming or cooling of IR hand held remote alone does 

not effect operation of cassette. Cassette reacts to its 

local temperature sensing element and setpoint selected 

and transmitted by IR hand held remote.

Transmission Limits

• Transmission distance of IR hand held remote is 

approximately 25-30 feet when perpendicular to face of 

cassette.

• Reception distance varies with angle of transmission if 

not perpendicular.

• Reception distance may also vary depending on room 

lighting.

Hibernate Mode

• When IR hand held remote enters hibernate mode, 

display goes dark if no activity on IR hand held remote 

for ten minutes.

• Pressing any button awakens IR hand held remote while 

in hibernate mode. IR hand held remote returns to 

mode it was in prior to entering hibernate mode.

Power

Pressing POWER button momentarily switches unit either 

on or off.

1. 

OFF mode, LCD displays time of day and day of week.

2. 

ON mode, LCD displays room temperature, mode of 

operation cooling, heating, auto (auto changeover), dry 

or Fan mode.

3. 

ON mode, setpoint temperature displays momentarily 

with push of any button except POWER button.

4. 

IR hand held remote transmits all infrared hand held 

controller information to cassette when POWER is held 

down for two (2) seconds.

Mode

• Heating, auto changeover (auto) or dry modes do not 

display if heat source is set to OFF in configuration 

mode.

• MODE button allows selection of mode of operation — 

cooling, heating, auto changeover (ACO), dry or fan 

mode.

• Fan mode either HIGH or LOW appears on LCD.

Fan Operation

Unit utilizes two-speed motor with three operational fan 

modes — high, low, and auto. All modes are continuous fan 

operation.
FAN button allows selection of desired fan speeds in all 

modes except Dry mode.
Dry mode, fan operates constantly at low 

speed. LCD indicates fan speed selection.                                         

High and low are constant fan settings. Fan operates 

continuously, regardless of setpoint or room temperatures.
Auto fan mode is for auto ramping of fan speeds.

1. 

Auto fan mode can only be selected if unit is in heating, 

cooling or auto changeover modes.

2. 

Auto fan mode, speed is determined by microprocessor.

a.

 Speed adjustment is made according to room and 

setpoint temperatures.

B.

 Fan switches to High speed when room temperature 

deviates by more than two degrees from setpoint.

C.

 Fan switches to Low speed if deviation is one degree 

or less.

Louver Operation — CAW18-36

Louver can be set to oscillate during fan operation or open 

to fixed setting.

“Lou” is displayed for two seconds along with “ON or “OFF” 

to indicate louver setting has been changed when LOUVER 

is pressed.

Содержание ComfortWave CAW Series

Страница 1: ...2201 Dwyer Avenue Utica NY 13501 Tel 800 253 7900 www ecrinternational com PN 240009722 REV F 08 01 2020 CAW FAN COIL CASSETTE AIR HANDLER Installation Operation and Maintenance Manual MODELS CAW 08...

Страница 2: ...UL 1995 Check our website frequently for updates www emiretroaire com Receiving Information 3 Important Safety Information 4 General Product Information 5 Dimensional Physical Data 6 Unit Mounting 9...

Страница 3: ...When calling for assistance please have following information ready Model Number_________________________ Serial Number_________________________ Date of installation______________________ Receiving I...

Страница 4: ...service this appliance Read this manual and understand all requirements before beginning installation Safety Information Have a qualified service agency install and service this appliance Turn off el...

Страница 5: ...harge locations use two non adjacent sides Fresh air intake capability with two knockout locations Four plastic air vanes motor driven with auto sweep or fixed position stop setting on models 18 36 Mo...

Страница 6: ...nal Discharge Knockouts 5 in Diameter 3 Available 2 Fresh Air Inlet Knockouts 1 x 2 in 2 Available 3 Condensate Discharge in Diameter 4 Chilled Water IN 5 8 in 5 Chilled Water OUT 5 8 in 6 Condensate...

Страница 7: ...1 Optional Discharge Knockouts 5 in Diameter 3 Available 2 Fresh Air Inlet Knockouts 1 x 2 in 2 Available 3 Condensate Discharge in Diameter 4 Chilled Water IN 7 8 in 5 Chilled Water OUT 7 8 in 6 Con...

Страница 8: ...3 1 5 7 7 4 5 8 FEATURES 1 Optional Discharge Knockouts 5 in Diameter 3 Available 2 Fresh Air Inlet Knockouts 1 x 2 in 2 Available 3 Condensate Discharge Inch Diameter 4 Chilled Water IN 7 8 in 5 Chi...

Страница 9: ...and damage return them to box until ready to install 7 Do not throw away two polystyrene blanking off pieces with packaging See Figure 6 Blanking Off Fascia discharge slot s need blanking off when su...

Страница 10: ...ocate wired wall mounted thermostat to ensure good temperature control Select installation position 1 Position thermostat approximately 5 ft 1 5 m above floor level 2 Avoid external walls and drafts f...

Страница 11: ...able 2 3 Prepare installation guides by folding metal bracket by hand along perforations See Figure 9 4 Lift cassette onto hanging rods 5 Level at correct distance from ceiling with aid of installatio...

Страница 12: ...rborne debris 4 Slope condensate pipe work downward from highest point in direction of water flow with minimum gradient of 1 in per 10 ft 8 mm per 1 m No uphill gradients except in first 18 in 460 mm...

Страница 13: ...ct knock outs are 5 in 133 mm round Fresh air knockouts are a 1 x 2 in 32 x 64 mm rectangular models 08 12 b 3 in 76 mm square models 18 36 2 Cut black insulation around knock out See Figure 15 3 Snip...

Страница 14: ...nnection on chassis Figure 19 Page 15 A Ensure polarized connector 2 position is in proper orientation and connected B Route wires to prevent them from becoming trapped cut broken or chaffed See Figur...

Страница 15: ...2 REV F 08 01 2020 FINAL ASSEMBLY Figure 19 Connect Vane Motor Plug Into Socket On Chassis Figure 20 Connect Infrared Control Cable Figure 21 Secure Fascia To Chassis Figure 22 Adjust Louver Position...

Страница 16: ...5 Connect electrical supply after completing water pipe work 6 Low voltage wiring must be at least 18 AWG Connect Wiring 1 Loosen four screws on front of control box cover Slide cover up and off to a...

Страница 17: ...with wiring diagram facing in after making all connections Secure with four screws Units rated 208 230 Vac primary side of transformer are factory wired for 230 Vac Change transformer tap from orange...

Страница 18: ...18 PN 20009722 REV F 08 01 2020 ELECTRICAL WIRING Figure 29 08 20 Transformer Figure 30 CAW 08 20 Transformer Mounting Figure 31 33 36 Transformer Figure 32 CAW 33 36 Transformer Mounting...

Страница 19: ...r verify thermostat is set to energize the fan with call for heating 1 Fan Operation Some thermostats are equipped with AUTO ON fan switch Placing switch ON will run the fan continuous Placing switch...

Страница 20: ...anel and fill drain pan See Figure 34 3 Adding water activates float switch and pump Water must flow regularly when condensate pump is energized If water does not check pipe slope or see if there are...

Страница 21: ...al only if switch 4 is set to YES enabling wall mounted remote thermostat operation 4 Set switches as desired for application Set Controller Configuration 1 See Figure 37 Page 26 and Pages 24 34 for o...

Страница 22: ...ature Observe three 3 minute minimum time off 8 Verify heating is operational Verify supply air is warmer than room air 9 Use IR hand held remote to enable auto changeover between heat cool Verify Con...

Страница 23: ...W INFRARED CONTROL SYSTEM OVERVIEW WARNING Electrical shock hazard Verify all power is off before removing control box cover Failure to follow these instructions could result in death or serious injur...

Страница 24: ...speed LOW 4 Select infrared handheld controller or wall mounted thermostat control YES Disables infrared hand controller and enables wall mounted thermostat operation Enables dip switches 3 and 2 Cle...

Страница 25: ...25 PN 20009722 REV F 08 01 2020 CAW INFRARED CONTROL SYSTEM OVERVIEW Figure 37 CAW Infrared Hand Held Control...

Страница 26: ...26 PN 20009722 REV F 08 01 2020 CAW INFRARED CONTROL SYSTEM SETTINGS Figure 38 Configuration Settings CAW...

Страница 27: ...able 4 Page 30 to record settings Day of week Mon Tue Wed Thu Fri Sat Sun Louver is closed when fan is off Period of day Morning Day Evening Night Periods provide four time settings to initiate change...

Страница 28: ...28 PN 20009722 REV F 08 01 2020 CAW INFRARED CONTROL SYSTEM SETTINGS Table 4 CAW Microprocessor Controller Dip Switch Settings...

Страница 29: ...oom lighting Hibernate Mode When IR hand held remote enters hibernate mode display goes dark if no activity on IR hand held remote for ten minutes Pressing any button awakens IR hand held remote while...

Страница 30: ...e Fan Operation see Page 30 Dry Mode Dry mode removes humidity from air while maintaining specific setpoint temperature This is done by cycling cooling mode Dry mode will NOT maintain specific humidit...

Страница 31: ...for a Day of week b Period of day C Hour d Minute e Cooling setpoint temperature f Heating setpoint temperature g Auto setpoint temperature Quick Copy CAW INFRARED CONTROL SYSTEM OPERATION Quick Copy...

Страница 32: ...rm LED During normal operation microprocessor keeps track of unit s run time When clean filter time has elapsed Timer Alarm LED flashes four times to indicate filter needs to be cleaned Clean filter t...

Страница 33: ...r appears 4 Clean Filter To aid in filter maintenance cassette controller indicates when schedule filter cleaning is required by flashing Timer Alarm LED During normal operation microprocessor will ke...

Страница 34: ...to clear retaining clips See Figure 41 C Lift filter off grille Place filter on flat surface and vacuum any dust and debris Vacuum all filters and grills Vacuum any accessible unit parts See Figure 42...

Страница 35: ...ling 24Vac is measured across terminals Y and C of water valve Y1 and C of cassette While wall thermostat is calling for cooling or heating and anti short cycle timer delay has elapsed 24Vac can be me...

Страница 36: ...interconnecting wires Terminal W is required for units with electric or hot water heat only Cassette controller will switch chilled water valve on and off through yellow Y low voltage terminal and ho...

Страница 37: ...240 50 1 0 55 1 8 0 6 198 0 7 15 CAW 18 20 220 240 50 1 0 55 1 8 3 2 13 06 14 2 198 17 7 20 CAW 33 36 220 240 50 1 0 5 0 5 1 10 1 10 1 0 198 1 2 15 CAW 33 36 220 240 50 1 0 5 0 5 1 10 1 10 5 4 22 7 23...

Страница 38: ...3 0 6 9 000 9 000 1 8 0 4 650 75 15 900 14 300 3 2 1 0 10 700 10 700 2 1 0 5 80 24 000 17 700 4 8 2 5 18 000 15 100 3 6 1 3 MERV 8 72 9 500 9 000 1 9 0 4 7 800 7 400 1 79 0 5 460 75 11 000 9 900 2 2...

Страница 39: ...L DATA CONNECTIONS 08 12 18 20 30 36 CHILLED WATER INLET in 5 8 7 8 7 8 CHILLED WATER OUTLET in 5 8 7 8 7 8 CONDENSATE in 1 2 1 2 1 2 BRANCH DUCT DIAMETER in 5 5 6 FRESH AIR DUCT DIAMETER in 3 3 3 FIL...

Страница 40: ...All specifications subject to change without notice 2020 ECR International Inc 2201 Dwyer Avenue Utica NY 13501 Tel 800 253 7900 www ecrinternational com BDR THERMEA GROUP...

Отзывы: