EM-GS User's Manual
7. Test Run and Application
23
Soft starter parallel connected with one power-line:
If several soft starter parallel installed in the one power line,
the input line reactor should be installed in the middle of the transformer and the soft starter circuit. Reactor should be
installed at each line input side between circuit breaker and soft starter.
The application of surge protection device (SPD):
The surge protection device should be considered to
installed in the application case, where is easily caused trouble by lightning or other reasons, such as over voltage,
over-current, surge interference. Please refer to SPD related documents for details.
7.5 Application examples
The parameters of the different loads are different, please refer to diagram 7.2.
The loading
Voltage ramp
starting time(s)
Voltage ramp
stopping time(s)
Initial
voltage
Voltage ramp
(current limit)
Current limit
to start
Ball mill
machine
20
6
60%
400%
350%
Fan
26
4
30%
400%
350%
Centrifugal
16
20
40%
400%
250%
Piston
compressor
16
4
40%
400%
300%
hoister
16
10
60%
400%
350%
Stirring
machine
16
2
50%
400%
300%
Breaker
16
10
50%
400%
350%
Screw
compressor
16
2
40%
400%
300%
Rotating
conveyor
20
10
40%
400%
200%
Light load
16
2
30%
400%
300%
Convey belt
20
10
40%
400%
250%
Heat pump
16
20
40%
400%
300%