EM-GS User's Manual
4. Connection and External Terminal
9
4. Connection and External Terminal
4.1 The external terminal
Please see the diagram diagram 4.1:
Diagram 4.1
Terminal
① ②
are by-pass output, are used to control the by-pass contactor. They are normal open contacts and
are closed when finishing starting. The terminal contact capacity is AC 250V/5A.
Terminal
③ ④
are programmable relay output: The delay time is set by
F4
code. The output command type is
set by
FE
code. They are normal open no-power terminals, being close when output valid. Please see the detailed
information in item 5.3. This terminal contact capacity is AC250V/5A.
Terminal
⑤ ⑥
are fault output , they will be closed when there are any fault matters happened to the soft starter
or electricity lost, while at normal case they are open. This terminal contact Capacity is AC250V/0.5A.
Terminal
⑦
are instantaneous stop input, this terminal must be connected with terminal
⑩
when the starter
works normally. But if these two terminals are open, the soft starter will stop, and at this time the starter is at the
state of fault protection. This terminal
⑦
can be controlled by the normally closed output terminals of external
protection device, and it is useless when the
FA
code is set to 0(Primary protection).
Terminal
⑧ ⑨ ⑩
are startup or stop input .There are two ways of connections for your selection; those are
3-wire connection and 2-wire connection. Please see the diagram 4.2
Diagram 4.2
Terminal
⑪ ⑫
are DC 4 ~ 20mA analogue output ,they indicate the current value of motor at real-time working.
The 20mA is full-scale value and that is four times than rated current of nominal power of soft starter, while, we
can connect a 4 ~ 20mADC current meter to check. The max value of output load resistance is 30
0Ω.
Note:
Please make sure that external terminals are in right connection; otherwise, the product may be damaged.
4.2 The communication interfaces
RJ-45 is the standard web line socket.
DB9 socket has RS485 and RS232 interfaces inside.
Please see the diagram 4.3