NetSure
™
-48 VDC Power System
Installation Instructions, IM582127000100 (Revision A, January 9, 2017)
Spec. No: 582127000100, 582127000103
Document Code: IM582127000100
Model No: 7100
Revision A, January 9, 2017
[19]
Making Electrical Connections
Important Safety Instructions
DANGER! Adhere to the “Important Safety Instructions”
presented at the front of this document.
Wiring Considerations
All wiring and branch circuit protection should follow the current
edition of the American National Standards Institute (ANSI)
approved National Fire Protection Association's (NFPA) National
Electrical Code (NEC), and applicable local codes. For operation in
countries where the NEC is not recognized, follow applicable
codes.
For wire size, branch circuit protection, crimp lug, and general
wiring recommendations; refer to System Application Guide
SAG582127000.
Refer to drawing 031110100 for lug crimping information. Refer
to drawings 031110200 and 031110300 for additional lug
information.
Refer to
for supplemental lug crimping information when
using the special application crimp lug / strap combination.
Table 3.
Supplemental Lug Crimping Information when using the
Special Application Crimp Lug / Strap Combination
Crimp Lug Part No.
Crimp Tool Required
1
,
T&B Model TBM12 or TBM15
Hydraulic Heads
Color
Key
Die
Index/
Code
No.
Die Cat.
Number
245393500
Burndy:
YA25L-4TCG1
Pink
42H
15508
245393600
Burndy:
YA26L-4TCG1
Black
45
15526
245393700
Burndy:
YA27L-4TCG1
Orange
50
15530
245393800
Burndy:
YA28L-4TCG1
Purple
54H
15511
514872
T & B:
256-30695-1879
Yellow
62
15510
Burndy:
YA29L-4TCG1
514873
T & B:
256-30695-1880
Red
71
15514
Burndy:
YA31L-4TCG1
1
The lugs should be crimped to the specifications given in the
manufacturer’s instructions furnished with the crimp tool or lug.
Danger
StockCheck.com