Figure 16.
Nominal 208 VAC / 240 VAC Input and Equipment Grounding Connections (1 Feed per 2 Rectifiers, Single Phase)
Rectifier Module Mounting Slots
Shelf #1
Rect.
1
Rect.
2
Rect.
3
Rect.
4
Rect.
5
Rect.
6
Rect.
1
Rect.
2
Rect.
3
Rect.
4
Rect.
5
Rect.
6
Rect.
1
Rect.
2
Rect.
3
Rect.
4
Rect.
5
Rect.
6
Rect.
1
Rect.
2
Rect.
3
Rect.
4
Rect.
5
Rect.
6
Shelf #2
Shelf #3
Shelf #4
Line to Line:
Connect Line 1 to Terminal “AC 1”.
Connect Line 2 to Terminal “AC 2”.
Wire Size Capacity: 6-14 AWG.
Recommended Torque: 18 in-lbs.
RECTIFIER AC INPUT FEEDS
1 FEED PER 2 RECTIFIERS
208 VAC / 240 VAC, 50 Hz / 60 Hz, SINGLE PHASE
FRAME GROUND
CONNECTION
Three 10-32 X 3/4"
Studs and Hardware.
Recommended torque:
23 in-lbs.
AC 2
AC 1
Shelf 2 and 4
Rectifier 6
Shelf 2 and 4
Rectifier 5
Shelf 2 and 4
Rectifier 4
Shelf 1 and 3
Rectifier 6
Shelf 1 and 3
Rectifier 5
Shelf 1 and 3
Rectifier 4
AC 2
AC 1
AC 2
AC 1
AC 2
AC 1
AC 2
AC 1
AC 2
AC 1
AC 2
AC 1
Shelf 2 and 4
Rectifier 3
Shelf 2 and 4
Rectifier 2
Shelf 2 and 4
Rectifier 1
Shelf 1 and 3
Rectifier 3
Shelf 1 and 3
Rectifier 2
Shelf 1 and 3
Rectifier 1
AC 2
AC 1
AC 2
AC 1
AC 2
AC 1
AC 2
AC 1
AC 2
AC 1
GND
GND
GND
FRAME GROUND
CONNECTION
Three 10-32 X 3/4"
Studs and Hardware.
Recommended torque:
23 in-lbs.
GND