1592027000 XW10L RTC GB r1.0 09.07.2013.docx 

XW10L 

4/5 

11.2

 

STEEL FINISHING MOUNTING  

1

1

2

2

3

3

4

4

RG-LX gascke

(optional)

 

12.

 

ELECTRICAL CONNECTIONS 

The instruments are provided with screw terminal block to connect cables with a cross section up to 
2,5 mm

for the digital and analogue inputs. Relays and power supply have a Faston connection 

(6,3mm). Heat-resistant cables have to be used. Before connecting cables make sure the power 
supply complies with the instrument’s requirements. Separate the probe cables from the power 
supply cables, from the outputs and the power connections. Do not exceed the maximum current 
allowed on each relay, in case of heavier loads use a suitable external relay. 
N.B. Maximum current allowed for all the loads is 20A. 

12.1

 

PROBE CONNECTION 

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid 
infiltration. It is recommended to place the thermostat probe away from air streams to correctly 
measure the average room temperature. 

13.

 

HOW TO USE THE HOT KEY  

13.1

 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When the controller is ON, insert the “Hot key” and push 

o

 key; the  "uPL"  message 

appears followed a by flashing “End” 

3.

 

Push “SET” key and the End will stop flashing. 

4.

 

Turn OFF the instrument remove the “Hot Key”, then turn it ON again. 

 
NOTE: the “Err” message is displayed for failed programming. In this case push again 

o

 key if you 

want to restart the upload again or remove the “Hot key” to abort the operation. 

13.2

 

HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY 

(DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert  a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller ON. 

3.

 

Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory, 
the “doL” message is blinking followed a by flashing “End”. 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the “Hot Key”.

NOTE the message “Err” is displayed for failed programming. In this case turn the unit off and then 
on if you want to restart the download again or remove the “Hot key” to abort the operation. 

14.

 

ALARM SIGNALS 

Message  

Cause 

Outputs 

“P1” 

Room probe  failure 

Compressor output acc. to par. “Con” and “COF” 

“P2” 

Second probe  failure 

Outputs unchanged 

“P3” 

Third probe  failure 

Outputs unchanged 

“P4” 

Fourth probe  failure 

Outputs unchanged 

“HA” 

Maximum temperature alarm 

Outputs unchanged. 

“LA”  

Minimum temperature alarm 

Outputs unchanged. 

"HA2" 

Condenser high temperature 

It depends on the “Ac2” parameter 

"LA2" 

Condenser low temperature 

It depends on the “bLL” parameter 

“dA” 

Door open 

Compressor and fans restarts  

“EA”  

External alarm 

Output unchanged. 

“CA”  

Serious external alarm (i1F=bAL)  All outputs OFF. 

“CA” 

Pressure switch alarm (i1F=PAL)  All outputs OFF 

14.1

 

SILENCING BUZZER / ALARM RELAY OUTPUT 

If “tbA = y”, the buzzer and the relay are is silenced by pressing any key.  
If “tbA n”, only the buzzer is silenced while the alarm relay is on until the alarm condition recovers. 

14.2

 

ALARM RECOVERY  

Probe alarms P1”, “P2”, “P3” and “P4” start some seconds after the fault in the related probe; they 
automatically stop some seconds after the probe restarts normal operation. Check connections 
before replacing the probe. 

Temperature alarms “HA”, “LA” “HA2” and “LA2” automatically stop as soon as the temperature 
returns to normal values. 
Alarms “EA” and “CA” (with i1F=bAL) recover as soon as the digital input is disabled. 
Alarm “CA” (with i1F=PAL) recovers only by switching off and on the instrument. 

14.3

 

OTHER MESSAGES 

Pon 

Keyboard unlocked. 

PoF 

Keyboard locked 

noP 

In programming mode: none parameter is present in Pr1 
On the display or in dP2, dP3, dP4: the selected probe is nor enabled 

15.

 

TECHNICAL DATA 

Housing: self extinguishing ABS. 
Case: 
facia 38x185 mm; depth 76mm 
Mounting : panel mounting in a 150x31 mm panel cut-out with two screws. 

 3 x 2mm. 

 

Distance between the holes 165mm 

Protection: IP20; Frontal protection: IP65 with frontal gasket mod RG-L. (optional) 
Connections: Screw terminal block 

 2,5 mm

2

 heat-resistant wiring and 6,3mm Faston 

Power supply: 230Vac or. 110Vac or 24Vac 

 10%  

Power absorption: 5VA max. 
Display
: 3 digits, red LED, 14,2 mm high.  
Display: 3 digits, red LED, 14,2 mm high; Inputs: Up to 4 NTC or PTC probes. 
Digital inputs
: 2 free voltage 

Relay outputs: Total current on loads MAX. 20A 

compressor: relay SPST 20(8) A, 250Vac  
light: relay SPST 8 or 16(3) A, 250Vac  

Other output : buzzer (optional) 
Serial output : TTL standard; Communication protocol: Modbus - RTU 
Data storing
: on the non-volatile memory (EEPROM). 
Internal clock back-up: 24 hours (only for model with RTC) 
Kind of action: 1B; Pollution grade: 2;Software class: A.;  
Rated impulsive voltage: 2500V; Over voltage Category: II 
Operating temperature: 
0÷60 °C; Storage temperature: -30÷85 °C.  
Relative humidity: 20

85% (no condensing) 

Measuring and regulation range: NTC probe: -40÷110°C (-40÷230°F);  

PTC probe: -50÷150°C (-58÷302°F) 

Resolution: 0,1 °C or 1°C or 1 °F (selectable); Accuracy (ambient temp. 25°C):  ±0,7 °C ±1 digit 

16.

 

CONNECTIONS 

 

Supply: 120Vac or 24Vac: connect to terminals 11-12 
The X-REP
 output is optional 
The light relay can be also 16(5)A according to the model 

17.

 

DEFAULT SETTING VALUES 

Label 

Name Range 

Value Level 

Set  Set point 

LS÷US 

3.0 - 

Hy  Differential 

0,1

25.5°C/ 1

 255°F 

2.0 Pr1 

LS  Minimum set point 

-50°C

SET/-58°F

SET 

-50.0 Pr2 

US  Maximum set point 

SET

110°C/ SET 

 230°F 

110 Pr2 

Ot  Thermostat probe calibration 

-12

12°C /-120

120°F 

0.0 Pr1 

P2P  Second probe presence 

n=not present; Y=pres. 

n Pr1 

OE  Second probe calibration 

-12

12°C /-120

120°F 

0.0 Pr2 

P3P  Third probe presence 

n=not present; Y=pres. 

n Pr2 

O3  Third probe calibration 

-12

12°C /-120

120°F 

0 Pr2 

P4P  Fourth probe presence 

n=not present; Y=pres. 

n Pr2 

O4  Fourth probe calibration 

-12

12°C /-120

120°F 

0 Pr2 

OdS  Outputs delay at start up 

0÷255 min 

0 Pr2 

AC  Anti-short cycle delay 

 50 min 

1 Pr1 

Ac1  Second compressor start delay 

0÷255s 

5 Pr2 

rtr  P1-P2 percentage for regulation 

 0 ÷ 100 (100=P1 , 0=P2) 

100 Pr2 

CCt  Continuous cycle duration 0.0÷24.0h 

0.0 Pr2 

CCS  Set point for continuous cycle (-55.0÷150,0°C) 

(-67÷302°F) 

3.0 Pr2 

COn  Compressor ON time with faulty probe 

 255 min 

15 Pr2 

COF  Compressor OFF time with faulty probe 

 255 min 

30 Pr2 

CH  Kind of action 

cL÷Ht 

cL Pr1 

CF  Temperature measurement unit 

°C 

 °F 

°C Pr2 

rES  Resolution 

in=integer; dE= dec.point 

dE Pr1 

Lod  Probe displayed 

P1;P2 

P1 Pr2 

rEd

X-REP display 

P1 – P2 – P3 – P4 – SEt – dtr 

P1 Pr2 

dLy  Display temperature delay   

0 ÷ 20.0 min  (10 sec.)  

0.0 Pr2 

dtr  P1-P2 percentage for display 

 1 ÷ 99 

50 Pr2 

ACH  Kind of action for auxiliary relay  

CL; Ht 

cL Pr2 

SAA  Set Point for auxiliary relay 

-50,0÷110°C /  -58÷230°F 

0,0 Pr2 

SHy  Differential for auxiliary relay 

0,1

25.5°C/ 1

 255°F 

2,0 Pr2 

ArP  Probe selection for auxiliary relay 

nP / P1 / P2 / P3/P4 

nP Pr2 

Sdd  Auxiliary relay operating during defrost 

n÷y 

n Pr2 

ALP  Alarm probe selection  

nP; P1; P2; P3; P4 

P1 Pr2 

ALc  Temperat. alarms configuration 

rE= related to set; 

Ab = absolute 

Ab Pr2 

ALU  MAXIMUM temperature alarm 

Set

110.0°C; Set÷230°F 

110,0 Pr1 

ALL  Minimum temperature alarm 

-50.0°C

Set/ -58°F

Set 

-50,0 Pr1 

AFH  Differential for temperat. alarm recovery 

(0,1°C÷25,5°C) (1°F÷45°F) 

2,0 Pr2 

Содержание XW10L

Страница 1: ...e reaches the set point value again Time Temper Compr SET ON In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters COn and COF 3 3 CH HT HEATING APPLICATION Time Temper Heating ON SET SET HY Time The Hy value is automatically set under the Set Point If the temperature decreases and reaches set point minus differential the regulation output is ac...

Страница 2: ...s the set point LS Minimum set point 50 C SET 58 F SET Sets the minimum value for the set point US Maximum set point SET 110 C SET 230 F Set the maximum value for set point Ot Thermostat probe calibration 12 0 12 0 C 120 120 F allows to adjust possible offset of the thermostat probe P2P Second probe presence n not present y present OE Second probe calibration 12 0 12 0 C 120 120 F allows to adjust...

Страница 3: ...PS activation in the did time is reached switch off and on the instrument to restart normal regulation odc Compressor status when open door no Fan normal CPr F_C Compressor OFF rrd Outputs restart after doA alarm no outputs not affected by the doA alarm yES outputs restart with the doA alarm HES Temperature increase during the Energy Saving cycle 30 0 C 30 0 C it sets the increasing value of the s...

Страница 4: ...arm CA with i1F PAL recovers only by switching off and on the instrument 14 3 OTHER MESSAGES Pon Keyboard unlocked PoF Keyboard locked noP In programming mode none parameter is present in Pr1 On the display or in dP2 dP3 dP4 the selected probe is nor enabled 15 TECHNICAL DATA Housing self extinguishing ABS Case facia 38x185 mm depth 76mm Mounting panel mounting in a 150x31 mm panel cut out with tw...

Страница 5: ...second compressor dF2 do not select it HES night blind Lig Pr2 AoP Alarm relay polarity oA3 ALr oP cL cL Pr2 i1P Digital input polarity 13 14 oP opening CL closing cL Pr1 i1F Digital input 1 configuration 13 14 EAL bAL PAL dor dEF Htr AUS dor Pr1 did Digital input alarm delay 13 14 0 255min 15 Pr1 i2P Digital input polarity 13 19 oP opening CL closing cL Pr2 i2F Digital input configuration 13 19 E...