1592027000 XW10L RTC GB r1.0 09.07.2013.docx
XW10L
4/5
11.2
STEEL FINISHING MOUNTING
1
1
2
2
3
3
4
4
RG-LX gascke
(optional)
12.
ELECTRICAL CONNECTIONS
The instruments are provided with screw terminal block to connect cables with a cross section up to
2,5 mm
2
for the digital and analogue inputs. Relays and power supply have a Faston connection
(6,3mm). Heat-resistant cables have to be used. Before connecting cables make sure the power
supply complies with the instrument’s requirements. Separate the probe cables from the power
supply cables, from the outputs and the power connections. Do not exceed the maximum current
allowed on each relay, in case of heavier loads use a suitable external relay.
N.B. Maximum current allowed for all the loads is 20A.
12.1
PROBE CONNECTION
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid
infiltration. It is recommended to place the thermostat probe away from air streams to correctly
measure the average room temperature.
13.
HOW TO USE THE HOT KEY
13.1
HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1.
Program one controller with the front keypad.
2.
When the controller is ON, insert the “Hot key” and push
o
key; the "uPL" message
appears followed a by flashing “End”
3.
Push “SET” key and the End will stop flashing.
4.
Turn OFF the instrument remove the “Hot Key”, then turn it ON again.
NOTE: the “Err” message is displayed for failed programming. In this case push again
o
key if you
want to restart the upload again or remove the “Hot key” to abort the operation.
13.2
HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY
(DOWNLOAD)
1.
Turn OFF the instrument.
2.
Insert a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller ON.
3.
Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory,
the “doL” message is blinking followed a by flashing “End”.
4.
After 10 seconds the instrument will restart working with the new parameters.
5.
Remove the “Hot Key”..
NOTE the message “Err” is displayed for failed programming. In this case turn the unit off and then
on if you want to restart the download again or remove the “Hot key” to abort the operation.
14.
ALARM SIGNALS
Message
Cause
Outputs
“P1”
Room probe failure
Compressor output acc. to par. “Con” and “COF”
“P2”
Second probe failure
Outputs unchanged
“P3”
Third probe failure
Outputs unchanged
“P4”
Fourth probe failure
Outputs unchanged
“HA”
Maximum temperature alarm
Outputs unchanged.
“LA”
Minimum temperature alarm
Outputs unchanged.
"HA2"
Condenser high temperature
It depends on the “Ac2” parameter
"LA2"
Condenser low temperature
It depends on the “bLL” parameter
“dA”
Door open
Compressor and fans restarts
“EA”
External alarm
Output unchanged.
“CA”
Serious external alarm (i1F=bAL) All outputs OFF.
“CA”
Pressure switch alarm (i1F=PAL) All outputs OFF
14.1
SILENCING BUZZER / ALARM RELAY OUTPUT
If “tbA = y”, the buzzer and the relay are is silenced by pressing any key.
If “tbA = n”, only the buzzer is silenced while the alarm relay is on until the alarm condition recovers.
14.2
ALARM RECOVERY
Probe alarms P1”, “P2”, “P3” and “P4” start some seconds after the fault in the related probe; they
automatically stop some seconds after the probe restarts normal operation. Check connections
before replacing the probe.
Temperature alarms “HA”, “LA” “HA2” and “LA2” automatically stop as soon as the temperature
returns to normal values.
Alarms “EA” and “CA” (with i1F=bAL) recover as soon as the digital input is disabled.
Alarm “CA” (with i1F=PAL) recovers only by switching off and on the instrument.
14.3
OTHER MESSAGES
Pon
Keyboard unlocked.
PoF
Keyboard locked
noP
In programming mode: none parameter is present in Pr1
On the display or in dP2, dP3, dP4: the selected probe is nor enabled
15.
TECHNICAL DATA
Housing: self extinguishing ABS.
Case: facia 38x185 mm; depth 76mm
Mounting : panel mounting in a 150x31 mm panel cut-out with two screws.
3 x 2mm.
Distance between the holes 165mm
Protection: IP20; Frontal protection: IP65 with frontal gasket mod RG-L. (optional)
Connections: Screw terminal block
2,5 mm
2
heat-resistant wiring and 6,3mm Faston
Power supply: 230Vac or. 110Vac or 24Vac
10%
Power absorption: 5VA max.
Display: 3 digits, red LED, 14,2 mm high.
Display: 3 digits, red LED, 14,2 mm high; Inputs: Up to 4 NTC or PTC probes.
Digital inputs: 2 free voltage
Relay outputs: Total current on loads MAX. 20A
compressor: relay SPST 20(8) A, 250Vac
light: relay SPST 8 or 16(3) A, 250Vac
Other output : buzzer (optional)
Serial output : TTL standard; Communication protocol: Modbus - RTU
Data storing: on the non-volatile memory (EEPROM).
Internal clock back-up: 24 hours (only for model with RTC)
Kind of action: 1B; Pollution grade: 2;Software class: A.;
Rated impulsive voltage: 2500V; Over voltage Category: II
Operating temperature: 0÷60 °C; Storage temperature: -30÷85 °C.
Relative humidity: 20
85% (no condensing)
Measuring and regulation range: NTC probe: -40÷110°C (-40÷230°F);
PTC probe: -50÷150°C (-58÷302°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable); Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit
16.
CONNECTIONS
Supply: 120Vac or 24Vac: connect to terminals 11-12
The X-REP output is optional
The light relay can be also 16(5)A according to the model
17.
DEFAULT SETTING VALUES
Label
Name Range
Value Level
Set Set point
LS÷US
3.0 -
-
-
Hy Differential
0,1
25.5°C/ 1
255°F
2.0 Pr1
LS Minimum set point
-50°C
SET/-58°F
SET
-50.0 Pr2
US Maximum set point
SET
110°C/ SET
230°F
110 Pr2
Ot Thermostat probe calibration
-12
12°C /-120
120°F
0.0 Pr1
P2P Second probe presence
n=not present; Y=pres.
n Pr1
OE Second probe calibration
-12
12°C /-120
120°F
0.0 Pr2
P3P Third probe presence
n=not present; Y=pres.
n Pr2
O3 Third probe calibration
-12
12°C /-120
120°F
0 Pr2
P4P Fourth probe presence
n=not present; Y=pres.
n Pr2
O4 Fourth probe calibration
-12
12°C /-120
120°F
0 Pr2
OdS Outputs delay at start up
0÷255 min
0 Pr2
AC Anti-short cycle delay
0
50 min
1 Pr1
Ac1 Second compressor start delay
0÷255s
5 Pr2
rtr P1-P2 percentage for regulation
0 ÷ 100 (100=P1 , 0=P2)
100 Pr2
CCt Continuous cycle duration 0.0÷24.0h
0.0 Pr2
CCS Set point for continuous cycle (-55.0÷150,0°C)
(-67÷302°F)
3.0 Pr2
COn Compressor ON time with faulty probe
0
255 min
15 Pr2
COF Compressor OFF time with faulty probe
0
255 min
30 Pr2
CH Kind of action
cL÷Ht
cL Pr1
CF Temperature measurement unit
°C
°F
°C Pr2
rES Resolution
in=integer; dE= dec.point
dE Pr1
Lod Probe displayed
P1;P2
P1 Pr2
rEd
2
X-REP display
P1 – P2 – P3 – P4 – SEt – dtr
P1 Pr2
dLy Display temperature delay
0 ÷ 20.0 min (10 sec.)
0.0 Pr2
dtr P1-P2 percentage for display
1 ÷ 99
50 Pr2
ACH Kind of action for auxiliary relay
CL; Ht
cL Pr2
SAA Set Point for auxiliary relay
-50,0÷110°C / -58÷230°F
0,0 Pr2
SHy Differential for auxiliary relay
0,1
25.5°C/ 1
255°F
2,0 Pr2
ArP Probe selection for auxiliary relay
nP / P1 / P2 / P3/P4
nP Pr2
Sdd Auxiliary relay operating during defrost
n÷y
n Pr2
ALP Alarm probe selection
nP; P1; P2; P3; P4
P1 Pr2
ALc Temperat. alarms configuration
rE= related to set;
Ab = absolute
Ab Pr2
ALU MAXIMUM temperature alarm
Set
110.0°C; Set÷230°F
110,0 Pr1
ALL Minimum temperature alarm
-50.0°C
Set/ -58°F
Set
-50,0 Pr1
AFH Differential for temperat. alarm recovery
(0,1°C÷25,5°C) (1°F÷45°F)
2,0 Pr2