1592027000 XW10L RTC GB r1.0 09.07.2013.docx 

XW10L 

3/5 

ALL Minimum temperature alarm: (-50.0 ÷ SET °C; -58÷230°F when this temperature is reached  

the alarm is enabled, after the “ALd” delay time. 

AFH Differential for temperature alarm recovery: (0,1÷25,5°C; 1÷45°F) Intervention differential 

for recovery of temperature alarm. 

ALd  Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm 

condition and alarm signalling. 

dAo Exclusion of temperature alarm at start-up: (from 0.0 min to 23.5h) time interval between the 

detection of the temperature alarm condition after instrument power on and alarm signalling. 

CONDENSER TEMPERATURE ALARM 
AP2  Probe selection for temperature alarm of condenser: nP
 = no probe; P1 =thermostat probe; 

P2 = second probe; P3 =configurable probe; P4 = Probe on Hot Key plug. 

AL2 Low temperature alarm of condenser:  (-55÷150°C) when this temperature is reached the 

LA2 alarm is signalled, possibly after the Ad2 delay. 

Au2 High temperature alarm of condenser:  (-55÷150°C) when this temperature is reached the 

HA2 alarm is signalled, possibly after the Ad2 delay. 

AH2 Differential for temperature condenser alarm recovery: (0,1÷25,5°C; 1÷45°F) 
Ad2 Condenser temperature alarm delay: (0÷255 min) time interval between the detection of the 

condenser alarm condition and alarm signalling. 

dA2 Condenser temperature alarm exclusion at start up: (from 0.0 min to 23.5h, res. 10min) 
bLL  Compressor off with low temperature alarm of condenser: n = no: compressor keeps on 

working; Y = yes, compressor is switched off till the alarm is present, in any case regulation 
restarts after AC time at minimum. 

AC2 Compressor off with high temperature alarm of condenser: n = no: compressor keeps on 

working; Y = yes, compressor is switched off till the alarm is present, in any case regulation 
restarts after AC time at minimum. 

AUXILIARY RELAY 
tbA  Alarm relay silencing (with oA3 =ALr):  

n= silencing disabled: alarm relay stays on till alarm condition lasts,  
=silencing enabled: alarm relay is switched OFF by pressing a key during an alarm 

oA3 Third relay configuration (1-3):  dEF, FAn: do not select it!. ALr: alarm; Lig: light; AuS

Auxiliary relay; onF: always on with instrument on; db=  neutral zone; cP2 = second 
compressor;  dEF2: do not select it!;. HES:. night blind 

AoP Alarm relay polarity: it set if the alarm relay is open or closed when an alarm happens. CL

terminals 1-3 closed during an alarm; oP = terminals 1-3 open during an alarm 

DIGITAL INPUTS 
i1P  Digital input polarity (13-14): oP: 
the digital input is activated by opening the contact; CL: the 

digital input is activated by closing the contact. 

i1F Digital input configuration (13-14): EAL= external alarm: “EA” message is displayed; bAL

serious alarm “CA” message is displayed. PAL= pressure switch alarm, “CA” message is 
displayed; dor= door switch function; dEF= NOT USED; AUS=not enabled; Htr= kind of action 
inversion (cooling – heating); FAn= not set it; ES= Energy saving; HdF = NOT USED; onF = 
to switch the controller off. 

did (0

255 min) with i1F= EAL or i1F = bAL digital input alarm delay (13-14): delay between the 

detection of the external alarm condition and its signalling. 

with i1F= dor: door open signalling delay 
with i1F= PAL: time for pressure switch function: 
time interval to calculate the number of 
the pressure switch activation. 

i2P 2

nd

 digital input polarity (13-19): oP: the digital input is activated by opening the contact; CL: 

the digital input is activated by closing the contact. 

i2F  2

nd

 digital input configuration (13-19): EAL= external alarm: “EA” message is displayed; 

bAL= serious alarm “CA” message is displayed. PAL= pressure switch alarm, “CA” message is 
displayed; dor= door switch function; dEF= NOT USED; AUS=not enabled; Htr= kind of action 
inversion (cooling – heating); FAn= not set it; ES= Energy saving; HdF = NOT USED; onF = 
to switch the controller off. 

d2d (0

255 min) with i2F= EAL or i2F= bAL 2

nd

 digital input alarm delay (13-19): delay between 

the detection of the external alarm condition and its signalling. 

with i2F= dor: door open signalling delay 
with i2F= PAL: time for pressure switch function: 
time interval to calculate the number of 
the pressure switch activation. 

nPS Pressure switch number: (0 

15) Number of activation of the pressure switch, during the “did” 

interval, before signalling the alarm event (I2F= PAL).  

If the nPS activation in the did time is reached, switch off and on the instrument to 

restart normal regulation. 

odc  Compressor status when open door:  no, Fan = normal; CPr, F_C = Compressor OFF.  
rrd  Outputs restart after doA alarm: no= outputs not affected by the doA alarm;  yES = outputs 

restart with the doA alarm. 

HES Temperature increase during the Energy Saving cycle: 

(-30,0°C

30,0°C) it sets the increasing value of the set point during the Energy Saving cycle.  

OTHER 
Adr   Serial  address
 (1÷244): Identifies the instrument address when connected to a ModBUS 

compatible monitoring system. 

PbC Type of probe: it allows to set the kind of probe used by the instrument: PbC = PBC probe, ntc 

NTC probe. 

onF  on/off key enabling: nu = disabled; oFF = enabled; ES = not set it

dP1  Thermostat probe display 

dP2  Second probe display 
dP3  Third probe display
optional
dP4  Fourth probe display
rSE  Real set point: it shows the set point used during the energy saving cycle or during the 

continuous cycle. 

rEL Software release for internal use
Ptb  Parameter table code: 
readable only

8.

 

DIGITAL INPUTS  

The first digital input 13-14 is enabled  with P3P = n. 
With P3P = n and i1F = i2F the second digital input is disabled 
The free voltage digital inputs are programmable by the “i1F” and i2F  parameters. 

8.1

 

GENERIC ALARM (i1F or i2F = EAL) 

As soon as the digital input is activated the unit will wait for “did” time delay before signalling the 
EAL” alarm message. The outputs status don’t change. The alarm stops just after the digital input is 
de-activated. 

8.2

 

SERIOUS ALARM MODE (i1F or i2F =  bAL) 

When the digital input is activated, the unit will wait for “did” delay before signalling the “CA” alarm 
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated. 

8.3

 

PRESSURE SWITCH (i1F or i2F = PAL) 

If during the interval time set by “did” parameter, the pressure switch has reached the number of 
activation of  the “nPS” parameter, the “CA” pressure alarm message will be displayed. The 
compressor and the regulation are stopped. When the digital input is ON the compressor is always 
OFF.  If the nPS activation in the did time is reached, switch off and on the instrument to 

restart normal regulation. 

8.4

 

DOOR SWITCH INPUT  (i1F or i2F = dor) 

It signals the door status and the corresponding relay output status through the “odc” parameter: no, 
Fan = normal (any change); CPr, F_C = Compressor OFF. 
Since the door is opened, after the delay time set through parameter “did”, the door alarm is 
enabled, the display shows the message “dA” and the regulation restarts is rtr = yES. The alarm 
stops as soon as the external digital input is disabled again. With the door open, the high and low 
temperature alarms are disabled. 

8.5

 

SWITCH THE AUXILIARY RELAY (i1F or i2F = AUS) 

With oA3 = AUS the digital input switched the status of the auxiliary relay 

8.6

 

INVERSION OF  THE KIND OF ACTION: HEATING-COOLING (i1F or 

i2F=Htr)  

This function allows to invert the regulation of the controller: from cooling to heating and viceversa. 

8.7

 

ENERGY SAVING (i1F = ES) 

The Energy Saving function allows to change the set point value as the result of the SET+ HES 
(parameter) sum. This function is enabled until the digital input is activated. 

8.8

 

ON OFF FUNCTION (i1F or i2F = onF)  

To switch the controller on and off. 

8.9

 

DIGITAL INPUTS POLARITY  

The digital input polarity depends on the “i1P” and “i2P” parameters. 
i1P or i2P =CL: the input is activated by closing the contact. 
i1P or i2P=OP
: the input is activated by opening the contact 

9.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS 

The TTL serial line, available through the HOT KEY connector, allows by means of the external 
TTL/RS485 converter, XJ485-CX, to connect the instrument to a monitoring system ModBUS-RTU 
compatible  such as the  X-WEB500/3000/300. 

10.

 

X-REP OUTPUT – OPTIONAL 

As optional, an X-REP can be connected to the instrument, trough the dedicated 
connector. 

 

 

To connect the X-REP to the 
instrument the following 
connectors must be used 
CAB/REP1(1m), CAB/REP2 
(2m), CAB/REP5 (5m), 

11.

 

INSTALLATION AND MOUNTING 

The controller XW10L, shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two 
screws 

 3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-

L). The temperature range allowed for correct operation is 0 - 60 °C. Avoid places subject to strong 
vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. 
Let the air circulate by the cooling holes. 

 

11.1

 

CUT OUT 

 

Содержание XW10L

Страница 1: ...e reaches the set point value again Time Temper Compr SET ON In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters COn and COF 3 3 CH HT HEATING APPLICATION Time Temper Heating ON SET SET HY Time The Hy value is automatically set under the Set Point If the temperature decreases and reaches set point minus differential the regulation output is ac...

Страница 2: ...s the set point LS Minimum set point 50 C SET 58 F SET Sets the minimum value for the set point US Maximum set point SET 110 C SET 230 F Set the maximum value for set point Ot Thermostat probe calibration 12 0 12 0 C 120 120 F allows to adjust possible offset of the thermostat probe P2P Second probe presence n not present y present OE Second probe calibration 12 0 12 0 C 120 120 F allows to adjust...

Страница 3: ...PS activation in the did time is reached switch off and on the instrument to restart normal regulation odc Compressor status when open door no Fan normal CPr F_C Compressor OFF rrd Outputs restart after doA alarm no outputs not affected by the doA alarm yES outputs restart with the doA alarm HES Temperature increase during the Energy Saving cycle 30 0 C 30 0 C it sets the increasing value of the s...

Страница 4: ...arm CA with i1F PAL recovers only by switching off and on the instrument 14 3 OTHER MESSAGES Pon Keyboard unlocked PoF Keyboard locked noP In programming mode none parameter is present in Pr1 On the display or in dP2 dP3 dP4 the selected probe is nor enabled 15 TECHNICAL DATA Housing self extinguishing ABS Case facia 38x185 mm depth 76mm Mounting panel mounting in a 150x31 mm panel cut out with tw...

Страница 5: ...second compressor dF2 do not select it HES night blind Lig Pr2 AoP Alarm relay polarity oA3 ALr oP cL cL Pr2 i1P Digital input polarity 13 14 oP opening CL closing cL Pr1 i1F Digital input 1 configuration 13 14 EAL bAL PAL dor dEF Htr AUS dor Pr1 did Digital input alarm delay 13 14 0 255min 15 Pr1 i2P Digital input polarity 13 19 oP opening CL closing cL Pr2 i2F Digital input configuration 13 19 E...

Отзывы: