1592027000 XW10L RTC GB r1.0 09.07.2013.docx
XW10L
3/5
ALL Minimum temperature alarm: (-50.0 ÷ SET °C; -58÷230°F when this temperature is reached
the alarm is enabled, after the “ALd” delay time.
AFH Differential for temperature alarm recovery: (0,1÷25,5°C; 1÷45°F) Intervention differential
for recovery of temperature alarm.
ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm
condition and alarm signalling.
dAo Exclusion of temperature alarm at start-up: (from 0.0 min to 23.5h) time interval between the
detection of the temperature alarm condition after instrument power on and alarm signalling.
CONDENSER TEMPERATURE ALARM
AP2 Probe selection for temperature alarm of condenser: nP = no probe; P1 =thermostat probe;
P2 = second probe; P3 =configurable probe; P4 = Probe on Hot Key plug.
AL2 Low temperature alarm of condenser: (-55÷150°C) when this temperature is reached the
LA2 alarm is signalled, possibly after the Ad2 delay.
Au2 High temperature alarm of condenser: (-55÷150°C) when this temperature is reached the
HA2 alarm is signalled, possibly after the Ad2 delay.
AH2 Differential for temperature condenser alarm recovery: (0,1÷25,5°C; 1÷45°F)
Ad2 Condenser temperature alarm delay: (0÷255 min) time interval between the detection of the
condenser alarm condition and alarm signalling.
dA2 Condenser temperature alarm exclusion at start up: (from 0.0 min to 23.5h, res. 10min)
bLL Compressor off with low temperature alarm of condenser: n = no: compressor keeps on
working; Y = yes, compressor is switched off till the alarm is present, in any case regulation
restarts after AC time at minimum.
AC2 Compressor off with high temperature alarm of condenser: n = no: compressor keeps on
working; Y = yes, compressor is switched off till the alarm is present, in any case regulation
restarts after AC time at minimum.
AUXILIARY RELAY
tbA Alarm relay silencing (with oA3 =ALr):
n= silencing disabled: alarm relay stays on till alarm condition lasts,
y =silencing enabled: alarm relay is switched OFF by pressing a key during an alarm
oA3 Third relay configuration (1-3): dEF, FAn: do not select it!. ALr: alarm; Lig: light; AuS:
Auxiliary relay; onF: always on with instrument on; db= neutral zone; cP2 = second
compressor; dEF2: do not select it!;. HES:. night blind
AoP Alarm relay polarity: it set if the alarm relay is open or closed when an alarm happens. CL=
terminals 1-3 closed during an alarm; oP = terminals 1-3 open during an alarm
DIGITAL INPUTS
i1P Digital input polarity (13-14): oP: the digital input is activated by opening the contact; CL: the
digital input is activated by closing the contact.
i1F Digital input configuration (13-14): EAL= external alarm: “EA” message is displayed; bAL=
serious alarm “CA” message is displayed. PAL= pressure switch alarm, “CA” message is
displayed; dor= door switch function; dEF= NOT USED; AUS=not enabled; Htr= kind of action
inversion (cooling – heating); FAn= not set it; ES= Energy saving; HdF = NOT USED; onF =
to switch the controller off.
did (0
255 min) with i1F= EAL or i1F = bAL digital input alarm delay (13-14): delay between the
detection of the external alarm condition and its signalling.
with i1F= dor: door open signalling delay
with i1F= PAL: time for pressure switch function: time interval to calculate the number of
the pressure switch activation.
i2P 2
nd
digital input polarity (13-19): oP: the digital input is activated by opening the contact; CL:
the digital input is activated by closing the contact.
i2F 2
nd
digital input configuration (13-19): EAL= external alarm: “EA” message is displayed;
bAL= serious alarm “CA” message is displayed. PAL= pressure switch alarm, “CA” message is
displayed; dor= door switch function; dEF= NOT USED; AUS=not enabled; Htr= kind of action
inversion (cooling – heating); FAn= not set it; ES= Energy saving; HdF = NOT USED; onF =
to switch the controller off.
d2d (0
255 min) with i2F= EAL or i2F= bAL 2
nd
digital input alarm delay (13-19): delay between
the detection of the external alarm condition and its signalling.
with i2F= dor: door open signalling delay
with i2F= PAL: time for pressure switch function: time interval to calculate the number of
the pressure switch activation.
nPS Pressure switch number: (0
15) Number of activation of the pressure switch, during the “did”
interval, before signalling the alarm event (I2F= PAL).
If the nPS activation in the did time is reached, switch off and on the instrument to
restart normal regulation.
odc Compressor status when open door: no, Fan = normal; CPr, F_C = Compressor OFF.
rrd Outputs restart after doA alarm: no= outputs not affected by the doA alarm; yES = outputs
restart with the doA alarm.
HES Temperature increase during the Energy Saving cycle:
(-30,0°C
30,0°C) it sets the increasing value of the set point during the Energy Saving cycle.
OTHER
Adr Serial address (1÷244): Identifies the instrument address when connected to a ModBUS
compatible monitoring system.
PbC Type of probe: it allows to set the kind of probe used by the instrument: PbC = PBC probe, ntc
= NTC probe.
onF on/off key enabling: nu = disabled; oFF = enabled; ES = not set it.
dP1 Thermostat probe display
dP2 Second probe display
dP3 Third probe display- optional.
dP4 Fourth probe display.
rSE Real set point: it shows the set point used during the energy saving cycle or during the
continuous cycle.
rEL Software release for internal use.
Ptb Parameter table code: readable only.
8.
DIGITAL INPUTS
The first digital input 13-14 is enabled with P3P = n.
With P3P = n and i1F = i2F the second digital input is disabled
The free voltage digital inputs are programmable by the “i1F” and i2F parameters.
8.1
GENERIC ALARM (i1F or i2F = EAL)
As soon as the digital input is activated the unit will wait for “did” time delay before signalling the
“EAL” alarm message. The outputs status don’t change. The alarm stops just after the digital input is
de-activated.
8.2
SERIOUS ALARM MODE (i1F or i2F = bAL)
When the digital input is activated, the unit will wait for “did” delay before signalling the “CA” alarm
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated.
8.3
PRESSURE SWITCH (i1F or i2F = PAL)
If during the interval time set by “did” parameter, the pressure switch has reached the number of
activation of the “nPS” parameter, the “CA” pressure alarm message will be displayed. The
compressor and the regulation are stopped. When the digital input is ON the compressor is always
OFF. If the nPS activation in the did time is reached, switch off and on the instrument to
restart normal regulation.
8.4
DOOR SWITCH INPUT (i1F or i2F = dor)
It signals the door status and the corresponding relay output status through the “odc” parameter: no,
Fan = normal (any change); CPr, F_C = Compressor OFF.
Since the door is opened, after the delay time set through parameter “did”, the door alarm is
enabled, the display shows the message “dA” and the regulation restarts is rtr = yES. The alarm
stops as soon as the external digital input is disabled again. With the door open, the high and low
temperature alarms are disabled.
8.5
SWITCH THE AUXILIARY RELAY (i1F or i2F = AUS)
With oA3 = AUS the digital input switched the status of the auxiliary relay
8.6
INVERSION OF THE KIND OF ACTION: HEATING-COOLING (i1F or
i2F=Htr)
This function allows to invert the regulation of the controller: from cooling to heating and viceversa.
8.7
ENERGY SAVING (i1F = ES)
The Energy Saving function allows to change the set point value as the result of the SET+ HES
(parameter) sum. This function is enabled until the digital input is activated.
8.8
ON OFF FUNCTION (i1F or i2F = onF)
To switch the controller on and off.
8.9
DIGITAL INPUTS POLARITY
The digital input polarity depends on the “i1P” and “i2P” parameters.
i1P or i2P =CL: the input is activated by closing the contact.
i1P or i2P=OP: the input is activated by opening the contact
9.
TTL SERIAL LINE – FOR MONITORING SYSTEMS
The TTL serial line, available through the HOT KEY connector, allows by means of the external
TTL/RS485 converter, XJ485-CX, to connect the instrument to a monitoring system ModBUS-RTU
compatible such as the X-WEB500/3000/300.
10.
X-REP OUTPUT – OPTIONAL
As optional, an X-REP can be connected to the instrument, trough the dedicated
connector.
To connect the X-REP to the
instrument the following
connectors must be used
CAB/REP1(1m), CAB/REP2
(2m), CAB/REP5 (5m),
11.
INSTALLATION AND MOUNTING
The controller XW10L, shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two
screws
3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-
L). The temperature range allowed for correct operation is 0 - 60 °C. Avoid places subject to strong
vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes.
Let the air circulate by the cooling holes.
11.1
CUT OUT