Page: 26
Emerson.com/SolaHD
User Guide
A272-365
3. MONITORING
6/2022
The following table provides the allowable range for settable fields in the User Configurable Alarms. In
case of SDN Temperature, the user can select to input either in Fahrenheit or in Celsius. The system will
adjust the minimum and maximum values accordingly.
Range
Parameter
Min
Max
Units
SDN Current High
0
200
Amps
SDN Temperature High (°C)
-50
+150
deg C
SDN Temperature High (°F)
-58
+302
deg F
The user configurable Alarm Flags can be monitored according to the two tables below. A 32-bit integer
has been allocated for this purpose, which corresponds to Inst 400 and 401 the table in
Section 4.3.2
.
At this time, only Bits 2 and 3 are used, and the other bits are reserved for future functionality.
If an alarm limit is exceeded, the corresponding Bit position in the 32-bit Alarm Flag becomes High.
Bit Number
Bits 4-31
Bit 3
Bit 2
Bits 0, 1
Description
"0
(reserved for
future use)"
Internal Temperature >
Threshold
Output Current >
Threshold
"0
(reserved for
future use)"
Internal Temp
Output Current
Register Value
<= Threshold
<= Threshold
0x00000000
<= Threshold
> Threshold
0x00000004
> Threshold
<= Threshold
0x00000008
> Threshold
> Threshold
0x0000000C