Page: 59
6. ADVANCED MONITORING SCENARIOS
6/2022
Emerson.com/SolaHD
User Guide
A272-365
UDT Element Name
Type
Attribute
Number
Description
iLED_Status
Int
112/212
Integer value representing the status of
the LED
0 = Off (No DC Output)
1 = Steady Green (Normal Operation)
2 = Steady Red (Overtemp Protection)
4 = Blinking Red (Short Circuit)
9 = Blinking Green (Heavy Load)
10 = Blinking Green/Red (Power Boost)
rPresent_OnTime
Real
114/214
Time in hours since last power cycle
rTotal_OnTime
Real
115/215
Total lifetime operating time in hours
6.6.3 UDT_EMERSON_SCM_ALARM
UDT Element Name
Type
Description
iPS1_Event_Flag
Int
Event flag PS 1
iPS2_Event_Flag
Int
Event flag PS 2
bPS1_Temp_Alarm
Bool
Over-temperature alarm PS 1
bPS2_Temp_Alarm
Bool
Over-temperature alarm PS 2
bPS1_Current_Alarm
Bool
Over-current alarm PS 1
bPS2_Current_Alarm
Bool
Over-current alarm PS 2
bPS1_Total_Current_
Warning
Bool
Either the warning limit for combined current or single
supply current has been reached; depends on whether
the SCM is configured for redundant or increased
power mode
bPS1_Total_Current_Critical
Bool
Either the critical limit for combined current or single
supply current has been reached; depends on whether
the SCM is configured for redundant or increased
power mode
bPS1_Total_OnTime_
Warning
Bool
The warning limit for total on-time has been reached
bPS1_Total_OnTime_Critical Bool
The critical limit for total on-time has been reached
bPS1_Current_Trend_Alarm
Bool
Alarm when hourly average load has changed by 10%
or more in the last 24 hours
bPS1_Temp_Trend_Alarm
Bool
Alarm when hourly average internal temperature has
changed by 10% or more in the last 24 hours
bPS2_Total_Current_
Warning
Bool
Either the warning limit for combined current or single
supply current has been reached; depends on whether
the SCM is configured for redundant or increased
power mode