1.6 PROCESS DATA
The measurement and calculation data shown below can be read through the SCM-E-EIP. For the full list of
SCM parameters, please refer to
Section 4.3
.
Parameter
Data Type
Resolution
Accuracy
SCM|Status LED
BYTE
-
-
SCM|Temperature
INT
0.1°C
+-2.0°C
P1|Vout
UINT
0.01V
+-2%
P1|Iout
UINT
0.01A
+-2.5%
P1|Vin
UINT
0.01V
+-5.0%
P1|Temperature
SINT
0.1°C
+-8°C
P1|LED Status
BYTE
-
-
P1|Event Flags
WORD
-
-
P1|Time On Now
UDINT
1sec
92-98%
P1|Lifetime On
UDINT
1sec
-
P2|Vout
UINT
0.01V
+-2%
P2|Iout
UINT
0.01A
+-2.5%
P2|Vin
UINT
0.01V
+-5.0%
P2|Temperature
SINT
0.1°C
+-8°C
P2|LED Status
BYTE
-
-
P2|Event Flags
WORD
-
-
P2|Time On Now
UDINT
1sec
-
P2|Lifetime On
UDINT
1sec
-
P1|Alarm Flag
DWORD
-
-
P2|Alarm Flag
DWORD
-
-
NOTES:
•
The accuracy defined in the table above is valid over the entire operating input, load, Vout range and 0–60°C
(unless specified otherwise)
•
P1, P2 Temperature (power supply internal ambient temperature) accuracy at > 50°C
•
Iout accuracy at > 20% of max. operating load
1.7 EVENTS
The events shown below can be flagged through communication with SCM-E-EIP.
Event
Event Code
Origin
Meaning
Short Circuit
Protection
SCP/OCP
PSU
Short circuit fault occurred at the output of the power supply.
This is triggered when the load current is greater than 150% of
the rated load.
Overvoltage
Protection
OVP
PSU
The output voltage of the power supply is greater than 32V for
SDN10 and SDN20.
Power Boost
PB
PSU
Power supply loaded a reactive load which is less than 150% of
the rated load but greater than 125% of the rated load.
Overtemperature
Protection
OTP
PSU
Internal temperature of the power supply exceeding safe
operating levels. This occurs when the main transformer
temperature exceeds 125°C.