8 | CVS HARDWIRED SERIES USER MAnUAL
Figure 6
Table 11: Electrical Connections—Figure 6
Catalog Number
Primary Voltage
Interconnect
Connect Lines to
23-23-150-8
23-23-210-8
23-23-220-8
23-23-230-8
23-23-250-8
120
H1 to H3 to H6 to H8
H2 to H5 to H7 to H10
H1 and H2
208
H2 to H3 H7 to H8
H1 to H6 H4 to H9
H1 and H4
240
H2 to H3 H7 to H8
H1 to H6 H5 to H10
H1 and H5
480
H2 to H3 H5 to H6
H7 to H8
H1 and H10
Secondary Voltage
Interconnect
Connect Lines to
120
---
X1 and X2 OR X3 and X2
240
---
X1 and X3
Table 13: Fusing & Wiring
Catalog
Number
Required Circuit Protection/Minimum Gauge for 90°C Wire
Minimum Gauge for 90°C Wire
Input Voltage
Output Voltage
95–130
175–235
190–260
380–520
475–650
120
208
240
23-23-150-8
10 A/14 AWG
6 A/14 AWG
6 A/14 AWG
3 A/14 AWG
---
14 AWG
23-23-210-8
15 A/14 AWG 10 A/14 AWG 10 A/14 AWG
6 A/14 AWG
---
14 AWG
23-23-220-8
30 A/10 AWG 20 A/12 AWG 15 A/14 AWG 10 A/14 AWG
---
10 AWG
14 AWG
23-23-230-8
45 A/8 AWG
25 A/10 AWG 25 A/10 AWG 15 A/14 AWG
---
8 AWG
12 AWG
23-23-250-8
80 A/4 AWG
40 A/8 AWG
40 A/8 AWG
20 A/12 AWG
---
8 AWG*
10 AWG
*Leads in the wiring compartment must have 105°C sleeving
Table 12: Product Parameters
Catalog Number
VA
BTU Output at Full load, +40°C Ambient
23-23-150-8
500
280
23-23-210-8
1000
519
23-23-220-8
2000
1229
23-23-230-8
3000
1331
23-23-250-8
5000
2117
Содержание Sola HD 23-13-030-2
Страница 1: ...CVS Hardwired Series 60 Hz User Manual ...
Страница 13: ......
Страница 14: ...1 800 377 4384 US 1 847 268 6651 International www solahd com P N A272 283 Rev 2 8 16 ...
Страница 15: ...Série CVS câblée 60 Hz Manuel d utilisation ...
Страница 27: ......
Страница 28: ...1 800 377 4384 É U 1 847 268 6651 international www solahd com P N A272 283 Rev 2 8 16 ...