Note
Point Name is entered as <HART Tag.PARAMETER>. Point Name can be entered using the
list of values (…) or manually entered. The following table gives a list of standard device
parameters which may be considered for Modbus register mapping.
Table 5-1: Device Parameters Available
Parameter
Description
Data type
PV
Primary Variable
32-bit float
SV
Secondary Variable
32-bit float
TV
Tertiary Variable
32-bit float
QV
Quaternary Variable
32-bit float
RELIABILITY
A measure of connectivity to the Gateway
32-bit float
ONLINE
Wireless communications status
Boolean
PV_HEALTHY
Health status for PV
Boolean
SV_HEALTHY
Health status for SV
Boolean
TV_HEALTHY
Health status for TV
Boolean
QV_HEALTHY
Health status for QV
Boolean
PV, SV, TV, and QV (dynamic variables) will vary by device type. Refer to the device’s
documentation for more information on what value is represented by each dynamic
variable.
RELIABILITY and ONLINE relate to wireless communications. RELIABILITY is the percentage
of messages received from the wireless field device. ONLINE is a true/false indication of
whether the device is communicating on the wireless network.
**_HEALTHY parameters are a true/false indication of the health of a particular variable
(** = dynamic variable – PV, SV, etc…). These parameters incorporate critical diagnostics
from the wireless field device as well as communication status.
Note
The **_HEALTHY parameters are a great indication of the health and communications
status of the data values.
State (state value): The value of a data point which drives a Modbus output of 1. For
example, if a data point is reported as either True or False, a state value of True will report a
1 for True and 0 for False. A state of False will report a 0 for True and a 1 for False. State is
only required for register numbers 0-19999 (Boolean, bit, coil, binary, etc…).
Invert: This check box will invert the Modbus output from a 1 to a 0 or a 0 to a 1. Invert is
only used for Boolean values using register numbers 0-19999.
Gain: This value is multiplied to the data value for the purpose of scaling integers. Gain is
only required if scaled is chosen on the Modbus communications page and globe gain and
offset is not chosen.
Offset: This value is added to the data value for the purpose of scaling integers. Offset is
only required if scaled is chosen on the Modbus communications page and globe gain and
offset is not chosen.
Reference Manual
Operation and Maintenance
00809-0200-4420
September 2020
Emerson.com/Rosemount
51
Содержание Smart Wireless Gateway 1420
Страница 1: ...Reference Manual 00809 0200 4420 Rev HE September 2020 Emerson Wireless 1420 Gateway ...
Страница 34: ...Installation Reference Manual September 2020 00809 0200 4420 34 Emerson com Rosemount ...
Страница 42: ...Commissioning Reference Manual September 2020 00809 0200 4420 42 Emerson com Rosemount ...
Страница 62: ...Troubleshooting Reference Manual September 2020 00809 0200 4420 62 Emerson com Rosemount ...
Страница 84: ...DeltaV Ready Reference Manual September 2020 00809 0200 4420 84 Emerson com Rosemount ...
Страница 95: ...Reference Manual 00809 0200 4420 September 2020 Emerson com Rosemount 95 ...