Page
2
SDU 24-BATEM Instruction Manual • A272-148 Rev. 2 9/2021
BaCK-Up time of sdU dC Ups with sdU 24-Batem (in minUtes) versUs load perCentaGe
remarK
: Resistive loads were used to measure the battery run time, using other types of load may result in different battery run time. Run times are based on
new, fully charged battery module at a temperature of 25°C (77°F). Run times may vary due to manufacturing variance of the individual batteries.
dc uPs with sdu 24-batem external battery Pack (ebP)
The external battery module SDU 24-BATEM includes two (2) user replaceable batteries.
sdu 10-24b with sdu 24-batem
load
20% (2a)
40% (4a)
60% (6a)
80% (8a)
100% (10a)
1 EBP
135
52
28
19
14
sdu 20-24b with sdu 24-batem
load
20% (4a)
40% (8a)
60% (12a)
80% (16a)
100% (20a)
1 EBP
48
17
9
6
4
sdU 24-Batem speCifiCations
Parameter
sdu 24-batem
nominal Voltage
24 VDC
Protection
Circuit Breaker: 24V, 25A
charging current
1.2
enclosure dimension in. (mm)
11.5 x 5.57 x 4.57 (292 x 142 x 116)
enclosure type
NEMA 1
terminal connector type
Polarized Powerpole Connectors
batteries
Replaceable - Refer to the instructions for replacement.
accessories
6 ft polarized battery cable
operating temperature
-20o to +50o C
charge temperature
0o to +40o C
storage temperature
-20o to +40o C
Humidity
95% no condensation
Certifications
cULus Listed: UL 508/CSA 107.1, UL/CSA 61010-1, UL/CSA 61010-2-201
cRUus: UL/CSA 60950-1, UL/CSA 62368-1
CE/UKCA: IEC/EN 62368-1, IEC/EN 61010-1,
IEC/EN 61010-2-201
Weight lbs (kg)
16 (7.26)
mounting
Wall/Chassis Mounting