15 – 90 degrees – indication after 120 minutes
Above 90 degrees – indication after 20 minutes
3.9.4
Detection options
The type of detection can be determined using this section with the following parameters.
Fast
According to model specifications, found in datasheet
Explosion
According to model specifications, found in datasheet
IR only
Single channel selection
UV only
Single channel selection
UV/IR
Double channel selection
3.9.5
Lock option
Modbus
®
Manager offers password protection for various maintenance and administrative
actions.
Not locked
No password required to change detector settings
Locked
Password required to change detector settings; opens dialog box for
setting passwords
Change
passwords
To change the password, the previous password must be entered. If
you do not have the previous password, contact the manufacturer to
receive a time-limited password to reset the password. Once received,
use the
Enable Password reset
button in the
Version
→
Service
menu.
When the “locked” option is selected, access to selected actions is controlled. There are
two independent permission types that allow access to the actions listed in
the detector is locked by passwords. When selecting the “locked” option, a dialog box
opens to enter the maintenance and admin passwords. Both passwords should be entered
by authorized personnel to complete the password setting process. Once completed, only
share the relevant password in accordance with internal policy.
Table 3-1: Permission Types
Action
Permissions
Maintenance
Admin
Reset detector
Yes
Yes
Change password
Authorized personnel only
Manual BIT
Yes
No
Detector setup
No
Yes
Firmware update
No
Yes
Fix 4-20 scale values
No
Yes
Parameter download/upload
No
Yes
Operation
Reference Manual
June 2021
00809-1500-4975
24