Where required, this file will be provided by the manufacturer.
4.4
Set fixed current 4-20 values
4-20mA is factory calibrated with controlled and certified equipment; there is no need for
additional calibration. This process allows rounding of multimeter values to 4mA and
20mA fixed values.
For different equipment used at the customer site over ±0.05mA, the 4-20mA output can
be fixed to match the reading indicated on the customer's multimeter. The reading can be
adjusted within ±0.05mA.
Procedure
1. Select the
4 mA
radio button
2. Click
Set fixed current
.
3. Enter multimeter reading.
4. Click the
Apply
button.
5. Repeat steps
until you enter value within 4mA ±0.5.
Important
It is essential to enter the final value and click
Apply
.
6. Select the
20 mA
radio button.
7. Click
Set fixed current
.
8. Enter multimeter reading.
9. Click the
Apply
button.
10. Repeat steps
until you enter value within 20mA ±0.5.
Important
It is essential to enter the final value and click
Apply
.
11. Click the
Burn
button to save the changes.