A. Detector configurable settings
B. BIT settings
C. Accessory relay options
D. Detection options
E. Lock option
F. 4-20 settings
G. Click to save any changes made, becomes clickable once any settings are changed
Note
Any unavailable options will be grayed out depending on specific detector model
connected.
3.9.1
Detector configurables
These detector parameters may be configured.
Sensitivity
Sets the detector’s sensitivity (in meters). A higher number
indicates greater sensitivity. See relevant product manual for
more information.
Heater mode
Demister settings for clearing condensation from the lens.
Choose from
On
,
Off
, or
Auto
.
Default: Auto
Alarm delay
The delay between detection of a signal and activation of the
alarm. Choose from
0
,
3
,
5
,
10
,
20
,
30
, or
A
(anti-flare).
Default: A
Heater power
Choose from high or low power.
Default: High power
Operation
Reference Manual
June 2021
00809-1500-4975
22
Emerson.com