Rosemount 8600 Vortex Flow Meter
Note
Do not scratch or deform any part of the sensor.
2.
Carefully brush the sealing surface clean with a soft bristle brush.
3.
Moisten a cotton swab with an appropriate cleaning liquid.
4.
Wipe the sealing surface. Repeat several times if necessary with a clean cotton
swab until there is minimal dirt residue picked up by the cotton swab.
A. Sealing surface
5.
Place new gasket on sealing surface.
6.
Place new sensor on gasket.
7.
Screw the sensor assembly in place. Tighten the bolts, in a crosswise sequence,
with a 5 mm hex wrench to 70.8 in-lb (8 N-m).
8.
Place the bracket into position.
9.
Tighten the four bolts that anchor the bracket in place
with a 5 mm hex wrench.
10.
Install the flowmeter electronics housing. See
“Replacing the electronics housing”
.
Figure 5
-
9. Sensor Sealing Surface
A