When installing this thread adapter, refer to manufacturer’s
installation instructions.
Special Conditions for Safe Use (X):
1. Flameproof joints are not intended for repair.
2. Painted enclosures may cause risk from electrostatic discharge. Avoid
installations that could cause electrostatic build-up on painted
surfaces, and only clean the painted surfaces with a damp cloth.
3.7.2 I7 IECEx Intrinsic Safety
Certificate
IECEx BAS 11.0064X
Standards
IEC 60079-0: 2011; IEC 60079-11: 2011
Markings
Ex ia IIC T5/T6 Ga; T6(-60 °C ≤ T
a
≤ +40 °C), T5(-60 °C ≤ T
a
≤ +80
°C)
Special Conditions for Safe Use (X):
1. The enclosure may be made of aluminum alloy and given a protective
polyurethane or epoxy polyester paint finish; however, care should be
taken to protect it from impact or abrasion if located in a Zone 0
environment.
3.8 Brazil
3.8.1 E2 INMETRO Flameproof
Certificate
UL-BR 16.0054X
Standards
ABNT NBR IEC 60079-0:2008 + Errata 1:2011, ABNT NBR IEC
60079-1:2009 + Errata 1:2011
Markings
Ex d IIC T5/T6 Gb; T6(-20 °C ≤ T
a
≤ +40 °C), T5(-20 °C ≤ T
a
≤ +70
°C)
Special Conditions for Safe Use (X):
1. The manufacturer should be contacted for information on the
dimensions of the flameproof joints.
3.8.2 I2 INMETRO Intrinsic Safety
Certificate
UL-BR 15.1094X
Standards
ABNT NBR IEC 60079-0:2008 + ERRATA 1:2011, ABNT NBR IEC
60079-11:2009
Markings
Ex ia IIC T5/T6 Ga; T6(-60 °C ≤ T
a
≤ +40 °C), T5(-60 °C ≤ T
a
≤ +80
°C)
February 2019
Quick Start Guide
Quick Start Guide
15
Содержание Rosemount 751
Страница 1: ...Quick Start Guide 00825 0100 4378 Rev AE February 2019 Rosemount 751 Field Signal Indicator ...
Страница 18: ...4 Declaration of Conformity Quick Start Guide February 2019 18 Rosemount 751 ...
Страница 19: ...February 2019 Quick Start Guide Quick Start Guide 19 ...
Страница 20: ...Quick Start Guide February 2019 20 Rosemount 751 ...
Страница 22: ...Quick Start Guide February 2019 22 Rosemount 751 ...
Страница 23: ...February 2019 Quick Start Guide Quick Start Guide 23 ...