4–20 mA dc Input Signal for Rosemount
3051C
4–20 dc Input Signal for Rosemount
3051S
A. Power supply
B. Load resistor
C. Optional ground
It is recommended that the Rosemount 751 indicator be wired in a parallel
configuration when the 4-20 mA transmitter includes a test terminal.
Utilization of the test terminal is required in a parallel configuration.
Connecting the 751 indicator across the positive and negative terminals of
the 4-20 mA transmitter could impact the loop.
A parallel configuration will allow the removal of the 751 indicator without
affecting the integrity of the 4-20 mA loop. Additionally, spare 751 indicators
can be added without disrupting the loop.