Reference Manual
00809-0200-4728, Rev RA
Section 6: Troubleshooting
April 2015
6.3
Troubleshooting the 4-20 mA/HART output
Table 6-1. Rosemount 644 Troubleshooting Table for 4-20 mA Output
Symptom or
issue
Potential
source
Corrective action
Transmitter
Does Not
Communicate
with Field
Communicator
Loop
Wiring
Check the revision level of the transmitter device descriptors (DDs) stored in
your communicator. The communicator should report Dev v4, DD v1
(improved), or reference “Field Communicator” on page 3-2 for previous
versions. Contact Emerson Process Management Customer Central for
assistance.
Check for a minimum of 250 ohms resistance between the power supply and
Field Communicator connection.
Check for adequate voltage to the transmitter. If a Field Communicator is
connected and 250 ohms resistance is properly in the loop, then the
transmitter requires a minimum of 12.0 V at the terminals to operate (over
entire 3.5 to 23.0 mA operating range), and 12.5 V minimum to communicate
digitally.
Check for intermittent shorts, open circuits, and multiple grounds.
High Output
Sensor
Input
Failure or
Connection
Connect a Field Communicator and enter the transmitter test mode to check
for a sensor failure.
Check for a sensor open or short circuit.
Check the process variable to see if it is out of range.
Loop
Wiring
Check for dirty or defective terminals, interconnecting pins, or receptacles.
Power
Supply
Check the output voltage of the power supply at the transmitter terminals. It
should be 12.0 to 42.4 Vdc (over entire 3.75 to 23 mA operating range).
Electronics
Connect a Field Communicator and enter the transmitter status mode to
isolate module failure.
Connect a Field Communicator and check the sensor limits to ensure
calibration adjustments are within the sensor range.
Erratic Output
Loop
Wiring
Check for adequate voltage to the transmitter. It should be 12.0 to 42.4 Vdc at
the transmitter terminals (over entire 3.75 to 23 mA operating range).
Check for intermittent shorts, open circuits, and multiple grounds.
Connect a Field Communicator and enter the Loop test mode to generate
signals of 4 mA, 20 mA, and user-selected values.
Electronics
Connect a Field Communicator and enter the transmitter test mode to isolate
module failure.
Содержание Rosemount 644
Страница 2: ......
Страница 4: ...iv Reference Manual 00809 0200 4728 Rev RA Title Page April 2015 ...
Страница 10: ...x Reference Manual 00809 0200 4728 Rev RA Table of Contents April 2015 Table of Contents ...
Страница 150: ...140 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 151: ...141 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 154: ...144 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 156: ...146 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 160: ...150 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 161: ...151 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 162: ...152 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 163: ...153 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 164: ...154 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 180: ...Index 2 Reference Manual 00809 0200 4728 Rev RA Index April 2015 Index ...
Страница 181: ......