130
Reference Manual
00809-0200-4728, Rev RA
Appendix B: Product Certifications
April 2015
Special Conditions for Safe Use (X):
1.
See certificate for ambient temperature range.
2.
The non-metallic label may store an electrostatic charge and become a source of ignition
in Group III environments.
3.
Guard the LCD cover against impact energies greater than 4 joules.
4.
Consult the manufacturer if dimensional information on the flameproof joints is
necessary.
International
E7
IECEX
Flameproof
Certificate: IECEx FMG 12.0022X
Standards: IEC 60079-0: 2011, IEC 60079-1: 2007
Markings: Ex d IIC T6…T1 Gb, T6(-50 °C
≤
Ta
≤
+40 °C), T5…T1(-50 °C
≤
Ta
≤
+60 °C);
See
for process temperatures.
Special Conditions for Safe Use (X):
1.
See certificate for ambient temperature range.
2.
The non-metallic label may store an electrostatic charge and become a source of
ignition in Group III environments.
3.
Guard the LCD cover against impact energies greater than 4 joules.
4.
Consult the manufacturer if dimensional information on the flameproof joints is
necessary.
I7
IECEX
Intrinsic
Safety
Certificate: [Headmount HART]: IECEx BAS 12.0069X
[Headmount Fieldbus/PROFIBUS, Railmount HART]: IECEx BAS 07.0053X
Standards: IEC 60079-0: 2011, IEC 60079-11: 2011
Markings: Ex ia IIC T6…T4 Ga
See
for Entity Parameters and Temperature Classifications
Special Condition for Safe Use (X):
1.
The equipment must be installed in an enclosure which affords it a degree of protection
of at least IP20 in accordance with the requirements of IEC 60529. Non-metallic
enclosures must have a surface resistance of less than 1G
Ω
; light alloy or zirconium
enclosures must be protected from impact and friction when installed in a Zone 0
environment.
2.
When fitted with the Transient Protector Assembly, the equipment is not capable of
withstanding the 500V test as defined in Clause 6.3.13 of IEC 60079-11:2011. This must
be taken into account during installation.
N7
IECEx Type n - with enclosure
Certificate: IECEx BAS 07.0055
Standards Used: IEC 60079-0:2011, IEC 60079-15:2010
Markings: Ex nA IIC T5 Gc (-40 °C
≤
Ta
≤
+70 °C)
Содержание Rosemount 644
Страница 2: ......
Страница 4: ...iv Reference Manual 00809 0200 4728 Rev RA Title Page April 2015 ...
Страница 10: ...x Reference Manual 00809 0200 4728 Rev RA Table of Contents April 2015 Table of Contents ...
Страница 150: ...140 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 151: ...141 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 154: ...144 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 156: ...146 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 160: ...150 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 161: ...151 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 162: ...152 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 163: ...153 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 164: ...154 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 180: ...Index 2 Reference Manual 00809 0200 4728 Rev RA Index April 2015 Index ...
Страница 181: ......