Reference Manual
00809-0200-4728, Rev RA
Section 2: Configuration
April 2015
Figure 2-20. Simulating the Digital Signal with LOI
* Available only if option code (S) or (D) is ordered.
2.11.3
Thermocouple Degradation Diagnostic
Thermocouple Degradation Diagnostic acts as a gauge of the general health of the
thermocouple and is indicative of any major changes in the status of the thermocouple or the
thermocouple loop. The transmitter monitors the resistance of the thermocouple loop to
detect drift conditions or wiring condition changes. The transmitter uses a baseline and
threshold Trigger value and reports the suspected status of the thermocouple based off the
difference between these values. This feature is not intended to be a precise measurement of
thermocouple status, but is a general indicator of thermocouple and thermocouple loop health.
Thermocouple diagnostic must be Enabled as well as connected and configured to read a
thermocouple type sensor. Once the diagnostic has been activated, a Baseline Resistance value
is calculated. Then a Trigger threshold must be selected, which can be two, three, or four times
the Baseline resistance, or the default of 5000 ohms. If the thermocouple loop resistance
reaches the Trigger Level, a maintenance alert is generated.
Note
The thermocouple resistance algorithm does not calculate resistance values while the active
calibrator mode is enabled.
Configure T/C Diagnostic with a Field Communicator
From the
HOME
screen, enter the Fast Key sequence.
The Thermocouple Degradation Diagnostic monitors the health of the entire thermocouple
loop, including wiring, terminations, junctions, and the sensor itself. Therefore, it is
imperative that the diagnostic baseline resistance be measured with the sensor fully
installed and wired in the process, and not on the bench.
Device Dashboard Fast Keys
2, 2, 4, 3, 4
CALIBRAT
DAMPING
VARIABLE MAP
TAG
ALM SAT VALUES
PASSWORD
SIMULATE
SIMULATE
HART REV
....
SIMULATE SNSR 1
SIMULATE SNSR 2*
END SIMUL
BACK TO MENU
EXIT MENU
VIEW CONFIG
SENSOR CONFIG
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
Содержание Rosemount 644
Страница 2: ......
Страница 4: ...iv Reference Manual 00809 0200 4728 Rev RA Title Page April 2015 ...
Страница 10: ...x Reference Manual 00809 0200 4728 Rev RA Table of Contents April 2015 Table of Contents ...
Страница 150: ...140 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 151: ...141 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 154: ...144 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 156: ...146 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 160: ...150 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 161: ...151 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 162: ...152 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 163: ...153 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 164: ...154 Reference Manual 00809 0200 4728 Rev RA Appendix B Product Certifications April 2015 Product Certifications ...
Страница 180: ...Index 2 Reference Manual 00809 0200 4728 Rev RA Index April 2015 Index ...
Страница 181: ......