OFF: Allows all diagnostic messages. The temperature transmitter will signal all
diagnostic cases.
For more information, see
.
To signal a diagnostic case, the temperature transmitter interrupts the transfer of
temperature measurements and provides these analog outputs using FOU2:
•
ON: 21.5 mA
•
OFF: 3.5 mA
Note
In a two-wire operation, the temperature transmitter does not provide diagnostic
messages in the event of low voltage.
Diagnostic function (three-wire)
In three-wire operation, the temperature transmitter uses an analog output for
temperature measurement and a switching output for diagnostics and IO-Link
communication.
drEd configures which diagnostic messages the temperature transmitter uses to indicate
failures.
•
ON: Signals only failure diagnostic messages for the analog and switching outputs
(cases 7-9).
•
ONdr: Signals only failure diagnostic messages (cases 7-9) for the analog output and
alarm and failure diagnostic messages (cases 3-9) for the switching output.
•
OFF: Signals only failure diagnostic messages (cases 7-9) for the analog output and all
diagnostic messages (cases 1-9) for the switching output.
Note
Using the switching output in three-wire operation for diagnostics results in the analog
output being disrupted only if a failure is seen. This ensures maximum use of the analog
output.
dOU1 is used to define how the diagnostic output reacts to diagnostic messages:
dOU1
Normal
Warning
Alarm and failure
Normally closed (nc)
Closed
Closed
Open
Normally closed,
extended (nc+)
Closed
Switching open/closed
at 2 Hz
2 Hz
Open
Introduction
Quick Start Guide
January 2019
00825-0100-4329
10
Quick Start Guide
Содержание Rosemount 327T
Страница 1: ...Quick Start Guide 00825 0100 4329 Rev 01 January 2019 Rosemount 327T Temperature Transmitter ...
Страница 2: ...2 ...
Страница 4: ...Contents Quick Start Guide January 2019 00825 0100 4329 4 Quick Start Guide ...
Страница 12: ...Introduction Quick Start Guide January 2019 00825 0100 4329 12 Quick Start Guide ...
Страница 16: ...Installation Quick Start Guide January 2019 00825 0100 4329 16 Quick Start Guide ...
Страница 20: ...Setting range for drW and drA Quick Start Guide January 2019 00825 0100 4329 20 Quick Start Guide ...
Страница 24: ...Product certifications Quick Start Guide January 2019 00825 0100 4329 24 Quick Start Guide ...