Reference Manual
00809-0100-4835 Rev BE
February 2018
Rosemount 3150 Series
Calibration
38
Figure 3-9b – Example for High Static Line
Pressure Span Correction using Method 1
(SI Units)
Range 4 for a calibration of –0,07 to 0,31 MPa corrected
for 10,34 MPa static line pressure:
1. Calculate the corrected output reading at LRV
= 4 mA + ((0,01 X 10,34 MPa/6,90 MPa X (-0,07
MPa))/0,38 MPa) X 16 mA
= 3,956 mA
2. Calculate the corrected output reading at URV
= 20 mA + ((0,01 X 10,34 MPa/6,90 MPa X 0,31
MPa)/0,38 MPa) X 16 mA
= 20,196 mA
3. At atmospheric static line pressure, apply 0,07 MPa to
the low side process connection (-0,07 MPa), and
adjust the zero until the transmitter output reads 3,956
mA.
4. Remaining at atmospheric static line pressure, apply
0,31 MPa to the high side process connection and
adjust the span until the transmitter output reads
20,196 mA.
5. Check to assure desired outputs are achieved and
repeat steps 3 and 4 if necessary.
When the transmitter is exposed to 10,34 MPa static line
pressure, within specified uncertainties, the output will be 4
mA at -0,07 MPa and 20 mA at 0,31 MPa.
Method 2 for High Static Line Pressure, Ranges 4 and 5
Adjust transmitter pressure input while leaving the output at 4
mA and 20 mA. Use one of the following formula sets
(depending on the pressure units being used to calibrate):
If using English Units (psi):
Corrected LRV pressure input =
Desired LRV – ((S X LRV) X (P/1000))
Corrected URV pressure input =
Desired URV – ((S X URV) X (P/1000))
If using SI Units (MPa):
Corrected LRV pressure input =
Desired LRV – ((S X LRV) X (P/6,90))
Corrected URV pressure input =
Desired URV – ((S X URV) X (P/6,90))
Where:
LRV = Lower Range Value
URV = Upper Range Value
P = Static Line Pressure
Span = Calibrated Span